Laserfiche WebLink
COS PW ID:9378277 MAR 22'99 10:25 N0.002 P.03 <br />is <br />n <br />-CONTINUED CONDITIONS FOR N-3057-1-0 Page: 2 <br />8 - The VOC concentration of the exhaust steam shall be determined using aflame Ionization detector. <br />The laboratory *results shall be received by the District prior to commencing system operatiolt. <br />9 - The influent and effluent hydrocarbon concentrations shall be mca9ured three times per day for at <br />least 15 minutes for each sampling, 2 days per week for the first month and weekly thereafter. <br />10 - The maximum 93% sulfuric acid injection rate into the well water shall he 0.032 ml per liter of well <br />water. <br />11 - The igjcction rate of the 9390 sulfuric acid shall be adjusted such that there are no sulfuric acid <br />emissions to the atmosphere. <br />12 - bogs shall be kept and shall include: 1. The daily system operating time. 2. The influent and <br />effluent hydrocarbon concentrations taken at the times specified. 3. The stack flow in CFM. <br />13 - The to s shall also include the quantity of well waterpprocessed by the air stripper and the quantity <br />of 93 <sutfuric acid injected into the water entering the air stripper. <br />14 - The logs shall be kept for a period of two years anti shall be made available for District inspection <br />upon request. <br />CS 011579 <br />City of Stockton 190855-0046 <br />