Laserfiche WebLink
u <br />A. The performance envelope for the flare is showed below. The flare shall <br />be capable of operating anywhere within this range and still meet the <br />performance and emission guarantees. <br />55 <br />so <br />45 <br />40 <br />g <br />A <br />ig 35 <br />30 <br />25 <br />North County Sanitary Landfill <br />LFG Flare Performance Envelope <br />I Operational I <br />Range <br />20 4— <br />r— , o r` r r— r a <br />700 150 200 250 300 350 400 450 500 550 600 650 700 750 600 <br />SCFtt Landfill Gras <br />PART 2 MATERIALS <br />0411111=40011 WORT M11110 <br />A. Pilot System - The Contractor shall supply a propane pilot gas system <br />furnished with the necessary spark igniter. The pilot, spark igniter, and any <br />other related components which require servicing shall be installed such that <br />they can be conveniently and quickly disassembled and removed for service <br />from outside the flare housing while the flare remains in operation. Parts of <br />the pilot assembly installed inside the flare not in contact with flame shall be <br />fabricated from 316 stainless steel, or when in contact with the main flare, <br />shall be hastalloy or Inconel. <br />B. Flare Insulation and Personnel Protection <br />1. The flame shall be contained inside an insulated steel housing so that <br />the maximum outside skin temperature of the steel housing does not <br />exceed 250°0. <br />North County LFG Collection System 5 FLARE STATION ENCLOSED GROUND FLARE <br />San Joaquin County Public Works Section 11550 <br />