C <br />2. Insulation shall be installed in accordance with the manufacturer's <br />specification, and shall be rated for temperatures suitable for the <br />application. The insulation in the combustion zone shall be rated for <br />2,200°F. The Flare Manufacturer shall submit for approval, infor- <br />mation on the maximum internal temperature that may be expected, <br />and necessary data for insulating material and the method of <br />attachment in order to demonstrate that the insulating materials are <br />suitable for the intended application. Metal retainers, clip, and wire <br />required to hold the insulation in place shall be protected from the <br />flame by an insulation pad . placed. over them, and they shall be <br />fabricated from Inconel. No metal component shall be in direct <br />contact with the flame. <br />C. Flame Safeguard - A flame safeguard with self -checking UV scanner shall <br />be used to monitor combustion per the UV scanner data sheet. The UV <br />scanner shall have a 1" FNPT connection. The control unit shall include a <br />panel mounted display with remote reset capabilities. <br />D. Additional Components - For proper and safe flare performance several <br />accessories shall be installed as part of the flare assembly. The following <br />accessories shall be supplied and installed on the flare by the Contractor <br />prior to delivery and in accordance with the Drawings and these <br />Specifications. Equipment that may be damaged in transit shall be removed <br />for shipping. <br />1. Manway - A' manway shall be provided for access to the flare <br />interior. The damper assembly may substitute for the manway <br />provided the opening is a minimum 12" x 16", hinged, electrical <br />wires will not require disconnection for access, and access into the <br />flare housing and above the burner assembly is easily obtainable. <br />2. Temperature Element - Couplings shall be welded in the flare <br />housing to accommodate Type K thermocouples. Couplings shall <br />be installed at 1/3 the flare capacity, 2/3 the flare capacity, and at <br />the maximum flare capacity plus 2 feet. The top thermocouple <br />should be located 5 feet below the top of the flare. <br />3. Damper Assembly - The damper assembly supplied by the <br />Contractor shall be controlled by a motor actuator as specified <br />1 herein and on the equipment data sheets. <br />4. Electrical Equipment - Electrical equipment furnished with the <br />flare shall be suitable for operation in outdoor unclassified <br />locations and shall be enclosed in NEMA 4 enclosures. If the flare <br />is located off skid two junction boxes shall be provided, one is for <br />1 low voltage wiring and one is for voltages greater than 100V. <br />North County LFG Collection System 6 FLARE STATION ENCLOSED GROUND FLARE <br />San Joaquin County Public Works Section 11550 <br />