Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by © Manufacturer Q Industry Standard El Professional Engineer <br /> Test Type © Pressure Q Vacuum E Hydrostatic <br /> Test Equipment Used: <br /> Sump/UDC ID 87 STP 89 STP 91 STP UDC 1-2 <br /> Sump Manufacturer Unknown Unknown Unknown Bravo <br /> Sump Depth (inches) 42 43 44 10 <br /> Sump Bottom to Top of 6 7 7 Bottom <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 09:37 10:29 10:29 11:31 <br /> Initial Reading 3.3102 1.2410 1.5437 1.5324 <br /> Test End Time 09:52 10:44 10:44 11:46 <br /> Final Reading 3.3102 1.2392 1.5432 1.5322 <br /> Change in Reading 0 -0.0018 -0.0005 -0.0002 <br /> Pass/Fail Criteria +/- 0.002 +/- 0.002 +/- 0.002 +/- 0.002 <br /> Tightness Test Results Ej Pass rl Fail El Pass rj Fail © Pass © Fail M Pass EFail <br /> Sump/UDC ID UDC 3-4 <br /> Sump Manufacturer Bravo <br /> Sump Depth (inches) 10 <br /> Sump Bottom to Top of Bottom <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 11:31 <br /> Initial Reading 1 .0344 <br /> Test End Time 11:46 <br /> Final Reading 1 .0340 <br /> Change in Reading -0.0004 <br /> Pass/Fail Criteria +/- 0.002 <br /> Tightness Test Results © Pass 0 Fail 0 Pass 0 Fail 0 Pass [rj Fail M Pass Ll Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />