Laserfiche WebLink
Page 2 of 3 <br /> no% LEAK DETECTION <br /> T E C H N O L O G I E S rNc <br /> Exclusive Providers for MDleake MSleako DPleako and <br /> PHDleake Testing Technologies <br /> 1889 N Oracle Road ❑ Tucson, AZ 85705 ❑ Phone 855-255-5325 ❑ FAX: 1-520.509-3720 <br /> 141 E Harney Lane Log of Repaired Leak/s <br /> Tank Information CONFIDENTIAL <br /> TK-1-87 TK-2-91 TK-3-DSL <br /> Tank Volume: 20000 8000 12000 <br /> Manufacture: Xerxes Xerxes Xerxes <br /> Interstice: Brine Brine Brine <br /> Depth To Tank: 203" 205" 205" <br /> Tank Dia: 10ft 10ft I ]Oft <br /> Depth of LiqUid:1 No Fuel No Fuel I No Fuel <br /> Depth to Ground Water: NA <br /> Tank Sump Boots Turbine <br /> Manufacture: Xerxes Bravo Red Jacket <br /> UDC/Dispensers Information <br /> Number of Dispensers: 6 <br /> Manufacture: Gilbarco <br /> Shear Valve Manufacture: OPW <br /> Containment Boots: Bravo <br /> Piping Information <br /> Manufacture <br /> Product Lines: Smith <br /> Vapor Return/Vent: Smith <br /> Flex: Fire-Flex <br /> Spill Buckets: OPW <br /> EVR: Healy <br /> Log of Repaired Leaks <br /> Reference# Date Time Status System Component IManufacture <br /> 97 5/21/20 11:26 Leak Final TK-1-87 STP Sump Leak on ATG brass to faceshield adaptor. OPW <br /> 125 5/21/20 13:41 Leak Final TK-1-87 Fill Vapor Sump Leak on coupler to nipple Pipe <br /> 126 5/21/20 13:41 Leak Final TK-1-87 Fill Vapor Sump Leak on fill riser to tank Pipe <br /> Log of Unrepaired Leaks <br /> Reference# Date Time Status System Component Manufacture <br /> None <br />