GROUND ZERO ANALYSIS, INC. <br /> Vapor Test Well VW-3 <br /> During the vapor extraction test using test well VW-3 as the <br /> extraction well, induced vacuums were observed in wells VW-1, <br /> VW-2 , and VW-6 almost instantaneously No significant induced <br /> vacuums were observed in wells VW-4 , VW-5, and MW-13 during <br /> ' the duration of the test Based on these results an applied <br /> vacuum of 29 inches of water and a flowrate of 50 cfm appears <br /> to be achievable using test well VW-3 as an extraction well <br /> ' Based on these results and results from longer tests performed <br /> on other wells, a radius of influence of approximately 30 to <br /> 35 feet is also indicated <br /> Vapor Test Well VW-4 <br /> As for the other wells, the testing conducted on VW-4 was <br /> designed to evaluate radius of influence, achievable flow rate <br /> and vapor concentrations In addition, the test on VW-4 was <br /> conducted in such a manner as to provide data bearing on the <br /> relationship between applied vacuum and flow rate A vacuum <br /> of 14 inches of water was applied to the well for a period of <br /> 30 minutes, vacuum was then increased to 25 inches for another <br /> 30 minutes, vacuum was increased again to 45 to 46 inches of <br /> water for the balance of the test <br /> During the long term vapor extraction test using test well VW- <br /> 4 as the extraction well, an induced vacuum was observed in <br /> well VW-1 within 4 minutes No induced vacuums were observed <br /> in wells VW-2 , VW-3 , VW-5 (constructed in the same boring) , <br /> VW-6, and MW-13 within 4 minutes Induced vacuums were <br /> observed in wells VW-2 , VW-6, and MW-13 , and the induced <br /> vacuum observed in well VW-1 increased within 7 minutes when <br /> the applied vacuum was increased from 14 to 25 inches of water <br /> and the flow rate was increased from 19 8 to 30 . 8 cfm No <br /> induced vacuums were observed in wells VW-3 and VW-5 when the <br /> applied vacuum and flow rate was stepped up 30 minutes into <br /> the test The induced vacuums observed in wells VW-1, VW--2, <br /> and MW-13 increased within 3 minutes when the applied vacuum <br /> was increased from 25 to 46 inches of water and the flow rate <br /> was increased from 30 8 to 44 cfm The induced vacuum <br /> observed in well VW-6 increased within 9 minutes when the <br /> applied vacuum was increased from 25 to 46 inches of water and <br /> the flow rate was increased No induced vacuums were observed <br /> ' in wells VW-3 and VW--5 when the applied vacuum and flow rate <br /> was stepped up 60 minutes into the test Based on these <br /> results an applied vacuum o= 46 inches of water and a flowrate <br /> of 40 cfm appears to be achievable using test well VW-4 as an <br /> extraction well A radius of influence of approximately 25 to <br /> 30 feet in indicated <br /> 5 <br />