Laserfiche WebLink
The following is an itemized list of aboveground petroleum storage act violations <br /> that have not been addressed for ESCALON UNIFIED SCHOOL DIST as of July 02 , <br /> 2020 . <br /> Open violations from July 16 , 2018 inspection <br /> Violation #612 - Plan failed to include secondary containment, diversionary structures , or equip to <br /> prevent discharge. <br /> The SPCC plan failed to discuss secondary containment for all tanks besides the 10 , 000 gallon diesel and <br /> the used oil tank that was within the diked area . The 1 , 000 gasoline tank was partially addressed with the oil <br /> water separator but portions of the tank are over soil that does not slope towards the oil water separator . <br /> Secondary containment for petroleum containers over 55 gallons in the shop were not addressed in the <br /> SPCC plan . The secondary containment for the new waste oil tank and the 55 gallon drums of used oil <br /> outside of the diked area was not addressed in the SPCC plan. A facility shall provide appropriate <br /> containment and/or diversionary structures or equipment to prevent a discharge. The entire containment <br /> system , including walls and floor, must be capable of containing oil and must be constructed so that any <br /> discharge from a primary containment system will not escape the containment system before cleanup occurs . <br /> Immediately provide adequate secondary containment for all aboveground petroleum storage containers <br /> larger than 55 gallons. <br /> This violation was corrected ❑ This violation will be corrected by (date) <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation 1 , 00o 6A -Un) i A-A; e 1404 0 (A MCA) l <br /> `ice j1 ►9 ON i)EtZ u_llrH ugj? QkejZtr mut To l V I L /vvh-:ML <br /> �dE2►4'S�2 <br /> Violation #613 - Failure to provide appropriate secondary containment , diversionary structures or <br /> equipment. <br /> The diked area holding the 10 , 000 gallon diesel tank appears to have potential escape routes for the diesel <br /> in the event of a release from the primary tank . The seals for the underground pipes appear to be damaged , <br /> allowing for liquid to flow into the piped area . A broken cap for an unknown purpose was also observed in the <br /> diked area allowing for the possible escape of diesel in the event of a release from the primary containment . <br /> A facility shall provide appropriate containment and/or diversionary structures or equipment to prevent a <br /> discharge . The entire containment system , including walls and floor , must be capable of containing oil and <br /> must be constructed so that any discharge from a primary containment system will not escape the <br /> containment system before cleanup occurs . Immediately provide adequate secondary containment for all <br /> aboveground petroleum storage containers larger than 55 gallons . <br /> .lI This violation was corrected ❑ This violation will be corrected by (date) <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation 5e -5 _ I i2 FD )aru b WV9 aS <br /> OF cetN) ry`-/Nr" 61u* T /` tz /4 0 6Z�co/V1) tz- GUAlTAlninnEA) T PC <br /> OTHeg AKcuc`& R4 ,) ND jTuRyct&, CUNT6lNtpL5 H06 ZeeAj c2Dcpjglb <br /> Page 3 of 6 <br />