My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2019
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
C
>
COUNTRY CLUB
>
2705
>
2300 - Underground Storage Tank Program
>
PR0231072
>
COMPLIANCE INFO_2019
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
9/22/2021 9:36:52 AM
Creation date
7/28/2020 9:36:35 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2019
RECORD_ID
PR0231072
PE
2361
FACILITY_ID
FA0002048
FACILITY_NAME
TESORO (SPEEDWAY) 68221
STREET_NUMBER
2705
STREET_NAME
COUNTRY CLUB
STREET_TYPE
BLVD
City
STOCKTON
Zip
95204
APN
12121008
CURRENT_STATUS
01
SITE_LOCATION
2705 COUNTRY CLUB BLVD
P_LOCATION
01
P_DISTRICT
003
QC Status
Approved
Scanner
SJGOV\kblackwell
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
206
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
SA N A A Q U I N Environmental Health Department <br /> COUNTY "�"NED <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> TESORO(Shell)68221(WRR 6290) 2705 COUNTRY CLUB BLVD, STOCKTON May 07, 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II, or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> The designated operator failed to check and note all required items on the visual inspection reports. The incorrect <br /> and missing information included the following from the inspection reports: <br /> -Section VI did not include the date. <br /> During the visual inspection, the designated operator shall check that all required testing and maintenance for the <br /> UST system have been completed and shall check all required items on the report. Ensure that designated <br /> operators performing visual inspections at this facility are including all of the required information on the reports. <br /> The designated operator failed to document all the alarms from the attached alarm history on the designated operator <br /> inspection reports and failed to check that they were responded to appropriately. The missing alarms include: <br /> -T1 87 ATG overfill alarm on 11/22/2018 <br /> During the visual inspection, the designated operator shall review the alarm history since the previous inspection, <br /> check that each alarm was documented and responded to appropriately, and attach a copy of the alarm history with <br /> documentation taken in response to any alarms to the report. Ensure that designated operators performing <br /> inspections at this facility are including all of the required information on the reports. <br /> This is a minor violation. <br /> 314 HSC 25290.1, 25290.2, 25291 Failed to have secondary containment or secondary containment not tight. <br /> Secondary containment testing results dated April 4, 2019 indicate failure of all UDC's, and 87 product piping and the <br /> 87 STP sump. <br /> All secondary containment for the UST system must be tight. Immediately have a properly licensed, trained, and <br /> certified contractor repair or replace the failed component under permit and inspection of the EHD. <br /> This is a minor violation. <br /> 319 CCR 2635, 2637.1, 2665, 2712 No spill bucket, failed to contain 5 gallons, no means to keep it empty, or failed to be <br /> tested. <br /> The 91 spill container failed to have a minimum capacity of five gallons. All spill containers shall have a minimum <br /> capacity of five gallons. Immediately contact a properly licensed, trained, and certified contractor to repair or <br /> replace the spill container under permit and inspection of the EHD. <br /> This is a minor violation. <br /> FA0002048 PR0231072 SCO01 05/07/2019 <br /> EHD 23-01 Rev.09/28/2018 Page 5 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />
The URL can be used to link to this page
Your browser does not support the video tag.