Laserfiche WebLink
EXISTING 10 TON DINING AREA ROOFTOP AIR CONDITIONING UNIT ALONG WITH ITS CONNECTED DUCTWORK TO <br /> REMAIN. EXISTING CEILING DIFFUSERS, SIDEWALL REGISTERS &CEILING RETURN REGISTERS TO BE REPLACED <br /> WITH NEW AS SHOWN ON HVAC FLOOR PLAN, THIS SHEET. RECONNECT NEW AIR DEVICES TO EXISTING DUCTWORK 0 <br /> AND PROVIDE NEW DUCT EXTENSIONS AS REQUIRED. ALL EXISTING AIR DEVICES TO BE REMOVED UNDER <br /> DEMOLITION WORK. <br /> EXISTING 8.5 TON KITCHEN AREA ROOFTOP AIR CONDITIONING UNIT ALONG WITH ITS CONNECTED DUCTWORK TO <br /> REMAIN. EXISTING CEILING DIFFUSERS &CEILING RETURN REGISTERS TO BE REPLACED WITH NEW AS SHOWN ON <br /> HVAC FLOOR PLAN, THIS SHEET. RECONNECT NEW AIR DEVICES TO EXISTING DUCTWORK AND PROVIDE NEW DUCT <br /> EXTENSIONS AS REQUIRED.ALL EXISTING AIR DEVICES TO BE REMOVED UNDER DEMOLITION WORK. O oo 1:1oo E:1oo O <br /> 0 x 20 <br /> o EXISTING GREASE EXHAUST HOOD, EXHAUST FAN &CONNECTED DUCTWORK TO REMAIN. <br /> Cn <br /> <� <br /> Z EXISTING ROOFTOP SUPPLY FAN ALONG WITH ITS CONNECTED DUCTWORK TO EXISTING GREASE EXHAUST HOOD <br /> o Z TO REMAIN. <br /> Io <br /> IL� O O O O O <br /> C) ABANDONED VAPOR EXHAUST FAN ON ROOF TO REMAIN,ANY CONNECTED ABANDONED DUCTWORK AVOVE s6o 15 5 <br /> LL CEILING TO BE REMOVED UNDER DEMOLITION WORK. <br /> �~ 16 S-3 16 <br /> EXISTING TOILET EXHAUST FAN &EXHAUST DUCT THRU ROOF TO REMAIN.TOILET ROOM EXHAUST REGISTERS& — — s-4 s-3 s-3 <br /> LU o REMAINING DUCTS TO BE REMOVED UNDER DEMOLITION WORK. COORDINATE WITH DEMOLITION CONTRACTOR. F- — — — — — — — — — — A � <br /> w O 5°° 3°° 3°° Vlvl� architecture <br /> & ALL REMAINING ABANDONED HVAC EQUIPMENT, DUCTWORK, ETC. TO BE REMOVED. COORDINATE WITH — — — — J O 12„0 14 100 100 soo Design Planning Interiors <br /> - - - - — - - - - — - - - - <br /> o DEMOLITION CONTRACTOR. E�i 12"0 637 5th Avenue San Rafael, CA 94901 <br /> Ow <br /> =m E)12110 415-451-2500 415-451-2595 fax <br /> §a F-1 - - - - - - / 7 10"0 23 www.vmarch.com <br /> w>o O 18 I (E)12"0 12" <br /> w a �10 <br /> O 1850 O O 13 12"0 14 <br /> VMI JOB NUMBER <br /> 12 <br /> LU 4 3 1862 <br /> W U 000000000 <br /> Cf)0- 00000000 O <br /> 0000000000 <br /> 00 08808 <br /> a= o 0 0 o <br /> 0 <br /> °°°° 0 <br /> s, 24 _4Ok <br /> O o 11 00 ° 0 600 11 O o0 0 000 0 000 �� <br /> z— 1 o0 0 00 00 OOo 0 <br /> on l7 R_2 00 0 0 00 000 0 00 2 ti��� �N�'Ah� <br /> I 0000 000 000 <br /> n ` °o°o°°o i 2500 <br /> p W O0�0o00000 o0 0 0000 000 0 <br /> IL f °000000008 rc <br /> o 0 1 0 1350 0 3E 1 1 e �, s a c <br /> � 9 <br /> a 150 h 000 N n. (;1 ,) 8 <br /> w I I I 11 <br /> zQ ❑ - - - — - - - - - - - - - - - - - - - - - - - - - - - - - �- s 8110 <br /> tom`, <br /> LU <br /> O 80 O O 8 �� <br /> w <br /> a¢ 1 <br /> >w <br /> z <br /> I I x 18 11 <br /> of — - - - - — - - - - — - - - - — - - — O LJ ao 8110 <br /> CO <br /> \ <br /> LJ 0 <br /> U5 MECHANICAL DEMOLITION NOTES G 18 80 <br /> �' O O O E-1 <br /> M ® O 150 <br /> Uj <br /> co <br /> o ITEM OA RA SA EA PRESSURELU <br /> — — — — — — <br /> m� I I � '� 10"� O O 0 O � , 18 <br /> CO m (E)DINING AC UNIT 900 2700 3600 -- +900 —M <br /> a 0 O O 300 10 <br /> oz <br /> (E)KITCHEN AC UNIT 900 2500 3400 -- +900 21 <br /> O o <br /> F_ M <br /> W= (E)SUPPLY FAN 3200 - - -- +3200 (VERIFY) 400 00 400 wo <br /> O O O <br /> Zo <br /> �z <br /> �a <br /> aU, <br /> cn O <br /> CD <br /> 0 0 (E) HOOD EF -- - - 4400 -4400 (VERIFY) <br /> U)W <br /> w� <br /> QM <br /> (E) TOILET EF -- - - 300 -300 0 0 <br /> Uw <br /> U)z <br /> LL O <br /> O <br /> w< <br /> z of <br /> 0< <br /> Z> <br /> G a TOTAL 5000 4700 +300 <br /> o RECORD DATES <br /> �o <br /> AIR BALANCE CFM SCHEDULE F MECHANICAL FLOOR PLAN 1i4 =1 o A DD SUBMITTAL 9/27/2018 <br /> Uj m BLDG.SUBMITTAL 11/09/2018 <br /> NECK FACE PATTERN EXISTING 10 TON DINING AREA ROOFTOP A.C. UNIT TO REMAIN.ADJUST SUPPLY&OUTSIDE AIR PER AIR BALANCE SCHEDULE. 12 EXISTING MAIN SUPPLY DUCT FROM EXISTING ROOFTOP A.C. UNIT TO REMAIN, VERIFY LOCATION &SIZE. BID SET 12/20/2018 <br /> MARK QUAN DIFF REGISTER TBAR SURF SUP RET EXH ALUMINUM MANUFACTURER MODEL NUMBER REMARKS INSTALL NEW MERV 8 RATED FILTERS. CONTRACT SET <br /> SIZE SIZE CFM EXISTING 8.5 TON KITCHEN AREA ROOFTOP A.C. UNIT TO REMAIN.ADJUST SUPPLY&OUTSIDE AIR PER AIR BALANCE SCHEDULE. 13 CONNECT NEW 12"0 TO EXISTING RECTANGULAR SUPPLY DUCT USING SPIN IN EXTRACTOR. <br /> 0 w 4W INSTALL NEW MERV 8 RATED FILTERS. 14 CONNECT NEW 12"0 SERVING NEW&REPLACED CEILING DIFFUSERS TO EXISTING 12"0 DUCT THAT SUPPLIED SINGLE <br /> U, <br /> S-1 6 12"0 24x24 X 400 X X X TITUS TMSA-AA BLACK FINISH,OBD REPLACED DIFFUSER, VERIFY SIZE&LOCATION. REVISIONS <br /> EXISTING SUPPLY DUCT SYSTEM TO REMAIN EXCEPT WHERE BRANCH DUCTS TO NEW OR RELOCATED CEILING DIFFUSERS <br /> 4W NEED TO BE ADDED OR REMOVED. LOCATIONS OF THESE MODIFICATIONS TO BE VERIFIED IN FIELD. 15 NEW CEILING DIFFUSER TO REPLACE EXISTING, CONNECT TO EXISTING DUCT. 1Q 12/20/2018 Plan Check Comment <br /> o S-2 1 10"0 2424 X 300 X X X TITUS TMSA-AA BLACK FINISH,OBD <br /> w ® EXISTING RETURN DUCT SYSTEM TO REMAIN. 1s NEW CEILING DIFFUSER TO REPLACE EXISTING, CONNECT NEW 10110 DUCT WITH DAMPER. <br /> a VERTICAL <br /> 0 o S-3 4 18x18 2424 X X X X TITUS PAS-AA NO DEFLECTORS,OBD (:E:) EXISTING ROOFTOP GREASE EXHAUST FAN,TYPE 1 HOOD&INTERCONNECTING DUCT TO REMAIN,ADJUST TO 4400 CFM. 17 NEW RETURN GRILLE TO REPLACE EXISTING, CONNECT TO EXISTING DUCT. <br /> w U) <br /> z 300-400 <br /> o S-4 2 1414 2424 X 4W X X X TITUS PCS AA OPPOSED BLADE DAMPER © EXISTING ROOFTOP VAPOR EXHAUST FAN TO REMAIN, CONNECTED DUCTWORK TO BE REMOVED UNDER DEMOLITION WORK. 1a EXISTING CEILING DIFFUSER &CONNECTED DUCTWORK TO BE REMOVED. <br /> 00 <br /> o 500-600 EXISTING ROOFTOP TOILET EXHAUST FAN &DUCT THRU ROOF TO REMAIN. ADJUST TO 300 CFM. 1s EXISTING EXHAUST REGISTER &CONNECTED DUCTWORK TO BE REMOVED. <br /> E a <br /> Q 2W <br /> 00 <br /> N w S-5 2 12x12 24x24 X X X X TITUS PCS AA OPPOSED BLADE DAMPER ® CONNECT 10"0 TO EXISTING EXHAUST DUCT THRU ROOF. 20 REMOVE CEILING DIFFUSER, CLEAN &REINSTALL IN REPLACED T-BAR CEILING.ADJUST TO SUPPLY 100 CFM. <br /> M o 0 1 300-360 <br /> CO 0 z 1W (:I:) EXISTING LAY-IN CEILING GRID &TILES TO BE REPLACED IN DINING AREA. 7 NEW CEILING DIFFUSERS (S-1) &2 NEW CEILING 21 EXISTING THERMOSTAT FOR DINING AREA AIR CONDITIONING UNIT TO BE REMOVED FOR WALL REFINISHING & REINSTALLED. <br /> 0 0� S-6 3 6x6 11x11 X X X X TITUS TDC-AA OPPOSED BLADE DAMPER RETURN REGISTERS (R-1)TO REPLACE EXISTING. CONNECT TO EXISTING DUCTWORK. <br /> N >s 801 I 22 EXISTING THERMOSTAT FOR KITCHEN AREA AIR CONDITIONING UNIT TO BE REMOVED FOR WALL REFINISHING &REINSTALLED. <br /> o a NA 10 EXISTING LAY-IN CEILING GRID &TILES TO BE REPLACED IN DINING ENTRY AREA. NEW CEILING DIFFUSER (S-2)TO REPLACE CLIENT <br /> w fr S-7 1 36x6 38x8 X X X X TITUS 272FS BLACK FINISH,OBD <br /> o O EXISTING IN DIFFERENT LOCATION. CONNECT 10 0 TO EXISTING DUCT&EXTEND TO NEW DIFFUSER LOCATION. 23 VOLUME DAMPER, TYPICAL. PRB MANAGEMENT, LLC. <br /> 600 <br /> w m NA 11 NEW SIDEWALL SUPPLY REGISTERS (S-7&S-8 TO REPLACE EXISTING. NEW REGISTERS TO BE SAME SIZE AS EXISTING THEY ARE 24 EXISTING ROOF ACCESS HATCH. <br /> 01 z S-8 1 24x6 26x8 X X X X TITUS 272FS BLACK FINISH,OBD REPLACING, VERIFY SIZES NOTED IN AIR DEVICE SCHEDULE BEFORE ORDERING. 4709 Mangels Blvd. <br /> E w a 300 25 OUTLINE OF ROOF EQUIPMENT WELL ABOVE. <br /> Uj Farfield,CA 94534 <br /> Uj <br /> o ao <br /> � U DAVE FULWILER <br /> Uj <br /> a <br /> o R-1 2 24x24 26x26 XX X X TITUS 8F BLACK FINISH,OBD <br /> NA HVAC KEY NOTES B <br /> E � NA 1350 TACO BELL REMODEL <br /> 0 0 N R -2 1 46x22 48x24 X 2500 X X X TITUS PAR-AA ALL WORK AND MATERIALS SHALL COMPLY WITH 2016 CALIFORNIA MECHANICAL CODE&ALL OTHER GOVERNING CODES. OBTAIN & PAY FOR ALL NECESSARY PERMITS,FEES&INSPECTIONS REQUIRED BY GOVERNING AUTHORITIES. 1420 ARY LANE <br /> LU 0 <br /> NEW DUCTWORK TO BE FABRICATED, INSTALLED AND SEISMICALLY BRACED PER CALIFORNIA MECHANICAL CODE CHAPTER 6 AND SMACNA HVAC DUCT CONSTRUCTION STANDARDS MANUAL. DIXON, CA 95620 <br /> 2E 01 <br /> N' w NEW ROUND SUPPLY&RETURN DUCTS TO BE WRAPPED RIGID SHEETMETAL, WITH THE EXCEPTION OF THE LAST 5'-011, WHICH MAY BE FLEX.. STORE#3239 <br /> co 1­o <br /> of Q E-1 2 8x8 10x10 X NA 100 X X X TITUS 8F OPPOSED BLADE DAMPER NEW TOILET EXHAUST DUCTS TO BE RIGID SHEETMETAL. <br /> mo <br /> o w MATERIALS EXPOSED WITHIN DUCTS OR PLENUMS TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH CALIFORNIA MECHANICAL CODE SECTION 602.2. <br /> w w DUCT AND PLENUM LINING TO BE MOLD,HUMIDITY AND EROSION RESISTANT, COMPLYING WITH CALIFORNIA MECHANICAL CODE SECTION 604.1. VA09 <br /> Mi 0 DUCT INSULATING WRAP TO BE AT LEAST 1"THICK WITH A FRK FOIL VAPOR BARRIER &HAVE A MINIMUM R VALUE OF 3.5. L5 <br /> WHERITAGE <br /> M �o ALL OUTSIDE AIR INTAKES SHALL BE A MINIMUM OF 10'-0" FROM EXHAUST FANS, FLUE TERMINATIONS AND PLUMBING VENTS. <br /> �I z SUCCESSOR REMODEL <br /> }o FINAL HVAC SYSTEM TESTING AND BALANCING TO BE BY A CERTIFIED AIR BALANCER CONTRACTED BY THE HVAC CONTRACTOR. <br /> _ a LOW VOLTAGE CONTROL WIRING AND ENCLOSING CONDUIT IN THIS WORK. LINE VOLTAGE WIRING BY ELECTRICAL CONTRACTOR. <br /> C� U> <br /> O p Q <br /> Y Z= <br /> U N <br /> O Q <br /> Z <br /> 65 J O= <br /> CD a c <br /> � o C7 <br /> �I N <br /> z <br /> MECHANICAL <br /> Ww Wo <br /> N w z F PLAN <br /> c0o <br /> co <U) <br /> cc Co <br /> (DU) <br /> co �w <br /> o2 <br /> C6 0 M1 0 <br /> AIR DEVICE SCHEDULE D HVAC NOTES C ■ <br />