Rev. B2, 7/15 DCR-1006A Level Controller <br /> Relay Settings <br /> NOTE: All Trip Value and Trip Window settings must be entered using the <br /> units being displayed. For example if the display is setup to read in gallons, <br /> then the Trip Value and Trip Window parameters would be set in gallons. <br /> TRIP V (Trip Value): <br /> Sets the reading (in the units being displayed) for the first actuation point of the <br /> relay. <br /> TRIP W (Trip Window): <br /> Sets the increase in the reading above the Trip Value to the secondary relay <br /> actuation point. <br /> Example: if the 2nd actuation point is desired at 100 inches of level, and the <br /> Trip Value (the 1st actuation point) is set to 25 inches of level, then the Trip <br /> Window would need to be set to 75 inches (25 + 75 = 100). <br /> TRIP T (Trip Type): <br /> Determines the operational logic performed by the relay (refer to the <br /> descriptions and logic chart on following pages). <br /> A P G%%:i' <br /> 31 <br />