DCR-1006A Level Controller Rev. B2, 7/15 <br /> Relay Trip Types <br /> NEAR: <br /> Activates whenever the reading is less than the Trip Value. <br /> EXCLSV (Exclusive): <br /> Activates whenever the reading is less than the Trip Value or greater than the <br /> Trip Value + Trip Window. <br /> H NEAR (Hysteresis Near): <br /> Activates until the reading exceeds the Trip Value + Trip Window, then <br /> deactivates until the reading falls below the Trip Value. <br /> FAR: <br /> Activates whenever the reading is greater than the Trip Value. <br /> INCLSV (Inclusive): <br /> Activates whenever the reading falls within the Trip Window. <br /> H FAR (Hysteresis Far): <br /> Activates whenever the reading exceeds the Trip Value + Trip Window, and <br /> remains active until the reading drops below the Trip Value. Once deactivated <br /> the relay will remain inactive until the reading once again exceeds the Trip <br /> Value + Trip Window. <br /> OFF: <br /> Disables the relay. <br /> LOE (Loss of Echo): <br /> Holds the relay active unless a loss of echo condition (no target detected) <br /> occurs. <br /> INPUT (Switched Input): <br /> Activates or deactivate the relay based on the state of the switched input <br /> (closed or open). <br /> PGO <br /> 32 <br />