IDENTIFICATION STAMP <br /> FAN COIL SCHEDULE DIV. OF THE STATE ARCHITECT <br /> APP. 02-117806 INC: 3 <br /> ELECTRICAL BLOWER COOLING HEATING REVIEWED FOR <br /> FAN MIN. TOTAL SENSIBLE AMBIENT TOTAL AMBIENT OPERATING <br /> TYPE MARK TYPE MOUNTING VOLT PHASE MCA MOCP DESIGN CFM E.S.P. OSA TYPE CAPACITY CAPACITY E.A. DB E.A. WB TEMP REFRIGERANT CAPACITY E.A. DB TEMP FILTER SERVICE WEIGHT MFGR MODEL NOTES SS p FLS 0 ACS El <br /> BHP (IN WC) (CFM) (BTUH) (BTUH) (°F) (°F) (°F) (BTUH) (°F) (.F) (LBS.) DATE: 03/03/2020 <br /> PROVIDE LITTLE GIANT #VCMA-20UL CONDENSATE PUMP, 1/30 HP1 115v/lo, 1.5 <br /> FFROM <br /> C 1 CASSETTE CEILING 208 1 6.6 14.1 0.1 615 0.8 20 DX 21,500 18,000 80 67 95 R41 OA 25,600 70 43 MERV 8 SEE PLAN 65 FUJITSU AUU18RGLX AMPS1 93 WATTS. PROVIDE WIRED REMOTE CONTROLLER. INDOOR UNIT POWERED <br /> FROM OUTDOOR UNIT. ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWITCH. <br /> PROVIDE LITTLE GIANT #VCMA-20UL CONDENSATE PUMP, 1/30 HP1 115v/lo, 1.5 <br /> FC 2 DUCTED <br /> SUSPENDED 208 1 6.6 14.1 0.1 615 0.8 45 DX 21,500 18,000 80 67 95 R410A 25,600 70 43 MERV 8 SEE PLAN 115 FUJITSU ARU18RGLX AMPS1 93 WATTS. PROVIDE WIRED REMOTE CONTROLLER. INDOOR UNIT POWERED <br /> FROM OUTDOOR UNIT. ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWITCH. <br /> HEAT PUMP SCHEDULE I <br /> >d <br /> ELECTRICAL C <br /> SEER/ COOLING HEATING SUMMER OPERATINGo <br /> VOLT PHASE MCA MOCP EER <br /> TYPE MARK COP HSPWINTER AMBIENT REFRIGERANT LINE <br /> F CAPACITY CAPACITY AMBIENT DB/WB DB TEMP (IE REFRIGERANT SIZE (LIQ/SUC) SERVICE WEIGHT MFGR MODEL NOTES 0 <br /> (BTUH) (BTUH) TEMP (°F) (LBS.) N x <br /> kn w <br /> ° <br /> ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWITCH. o <br /> HP 1 208 1 18.3 20 21.4/13.4 14.3 10.9 21,500 25,600 95/75 47 R410A 1/4" / 1/2" SEE PLAN 160 FUJITSU AOU18RGLX 0 <br /> 0a <br /> H U <br /> ELECTRICAL CONTRACTOR TO PROVIDE DISCONNECT SWITCH. U b <br /> HP 2 208 1 18.3 20 19/13 14 10.9 21,500 25,600 95/75 47 R410A 1/4" / 1/2" SEE PLAN 160 FUJITSU AOU18RGLX a/ <br /> k <br /> x <br /> PACKAGED HEAT PUMP SCHEDULE <br /> ELECTRICAL BLOWER COOLING HEATING POWER EXHAUST + ° <br /> MIN. TOTAL SENSIBLE AMBIENT TOTAL FILTER FILTER OPERATING <br /> ° <br /> TYPE MARK UNIT NOM. SEER/ COP DESIGN E.S.P. E.A. DB E.A. WB ELEC. HEAT STATIC SIZE SERVICE WEIGHT MFGR MODEL NOTES n O Q <br /> TYPE TONS VOLT PHASE FLA MCA MOCP EER BHP CFM (IN WC) OSA DRIVE TYPE CAPACITY CAPACITY (.F) (.F) TEMP TYPE CAPACITY (kW) VOLTAGE PHASE HP FLA PRESSURE MANUFACTURER MODEL TYPE (IN.) (LBS.) h--I <br /> I(CFM) (BTUH) (BTUH) (°F) (BTUH) <br /> PACKAGED DUEL COMPRESSOR, SINGLE ZONE VAV HEAT PUMP UNIT. FACTORY POWER <br /> PHP 1 HEAT 25 460 3 66 71 90 -/7.4 2.72 15 10,000 1 .1 2115 DIRECT DX 262,520 225,870 84 68 105 HEAT 244,800 - MERV 8 - SEE PLAN 4000 AAON RNA025CO3AJA02 EXHAUST AND ECONOMIZER. COORDINATE CONTROL COMPONENTS WITH CONTROLS <br /> PUMP SYSTEM - PELICAN CONTROLS. COORDINATE REQUIREMENTS WITH POWERED V <br /> PUMP EXHAUST MODULE. PROVIDE TITLE 24 COMPLIANT MICROMETL MODULATING <br /> CENTRIFUGAL POWER EXHAUST AND ULTRA LOW LEAK ECONOMIZER. POWERED ^ N 2 <br /> FACTORY POWER EXHAUST MODULE POWERED EXHAUST TO BE POWERED SEPARATELY FROM ROOFTOP UNIT. PROVIDE HINGED I--I a <br /> THROUGH UNIT ACCESS PANELS. PROVIDE 14" FACTORY CURB. SEE ELECTRICAL DRAWINGS FOR <br /> DISCONNECT SWITCH. PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY AIR <br /> PLENUM OF AC UNIT TO SHUT-OFF UNIT UPON DETECTION OF SMOKE. INSTALL �•G� <br /> IN STRICT ACCORDANCE WITH THE 2016 CALIFORNIA MECHANICAL CODE, SECTION [-I 4 <br /> 608. COORDINATE WITH ELECTRICAL AND/OR FIRE ALARM SYSTEM CONTRACTOR. ~ 'Z <br /> POWER EXHAUST TO MAINTAIN 0.03in-WC. b <br /> DUEL COMPRESSOR, SINGLE ZONE VAV HEAT PUMP UNIT. FACTORY POWER 5 �° <br /> PACKAGED HEAT EXHAUST AND ECONOMIZER. COORDINATE CONTROL COMPONENTS WITH CONTROLS ZI <br /> PHP 2 HEAT 25 460 3 66 71 90 -/7.4 2.72 15 10,000 1 .1 2115 DIRECT DX 262,520 225,870 84 68 105 PUMP 244,800 - MERV 8 - SEE PLAN 4000 AAON RNA025CO3AJA02 SYSTEM - PELICAN CONTROLS. COORDINATE REQUIREMENTS WITH POWERED W <br /> PUMP EXHAUST MODULE. PROVIDE TITLE 24 COMPLIANT MICROMETL MODULATING <br /> CENTRIFUGAL POWER EXHAUST AND ULTRA LOW LEAK ECONOMIZER. POWERED U O <br /> FACTORY POWER EXHAUST MODULE POWERED EXHAUST TO BE POWERED SEPARATELY FROM ROOFTOP UNIT. PROVIDE HINGED ° <br /> THROUGH UNIT ACCESS PANELS. PROVIDE 14" FACTORY CURB. SEE ELECTRICAL DRAWINGS FOR <br /> DISCONNECT SWITCH. PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY AIR w <br /> PLENUM OF AC UNIT TO SHUT-OFF UNIT UPON DETECTION OF SMOKE. INSTALL ° <br /> IN STRICT ACCORDANCE WITH THE 2016 CALIFORNIA MECHANICAL CODE, SECTION <br /> 608. COORDINATE WITH ELECTRICAL AND/OR FIRE ALARM SYSTEM CONTRACTOR. <br /> POWER EXHAUST TO MAINTAIN 0.03in-WC. <br /> PACKAGEDHEAT DUEL COMPRESSOR, SINGLE ZONE VAV HEAT PUMP UNIT. FACTORY POWER <br /> � <br /> PHP 3 HEAT 12.5 460 3 42.4 58 60 12/10.6 3.2 5 5,000 1.0 425 BELT DX 123,076 88,690 77 65.8 105 PUMP 185,487 15 460 3 2 6.6 MEDIUM MICROMETL EXHAUST AND ECONOMIZER. COORDINATE CONTROL COMPONENTS WITH CONTROLS PCD-FLHC-4V MERV 8 (4)20x25x2 SEE PLAN 2000 LENNOX KHA150S4M SYSTEM - PELICAN CONTROLS. COORDINATE REQUIREMENTS WITH POWERED <br /> PUMP EXHAUST MODULE. PROVIDE TITLE 24 COMPLIANT MICROMETL MODULATING b <br /> CENTRIFUGAL POWER EXHAUST AND ULTRA LOW LEAK ECONOMIZER. POWERED <br /> EXHAUST TO BE POWERED SEPARATELY FROM ROOFTOP UNIT. PROVIDE HINGED <br /> ACCESS PANELS. PROVIDE 14" FACTORY CURB. SEE ELECTRICAL DRAWINGS FOR <br /> DISCONNECT SWITCH. PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY AIR <br /> PLENUM OF AC UNIT TO SHUT-OFF UNIT UPON DETECTION OF SMOKE. INSTALL <br /> IN STRICT ACCORDANCE WITH THE 2016 CALIFORNIA MECHANICAL CODE, SECTION <br /> 608. COORDINATE WITH ELECTRICAL AND/OR FIRE ALARM SYSTEM CONTRACTOR. <br /> POWERED EXHAUST TO MAINTAIN 0.03 in-WC. <br /> PACKAGED DUEL COMPRESSOR, SINGLE ZONE VAV HEAT PUMP UNIT. FACTORY POWER <br /> HEAT EXHAUST AND ECONOMIZER. COORDINATE CONTROL COMPONENTS WITH CONTROLS <br /> PHP 4 HEAT 10 460 3 31.2 50 50 12.5/11 3.3 3 4,000 1.0 730 BELT DX 104,261 74,296 77 65.8 105 PUMP 163,137 15 460 3 2 6.6 MEDIUM MICROMETL PCD-FLHC-4V MERV 8 (4)2Ox25x2 SEE PLAN 1750 LENNOX KHA120S4M SYSTEM - PELICAN CONTROLS. COORDINATE REQUIREMENTS WITH POWERED <br /> PUMP EXHAUST MODULE. PROVIDE TITLE 24 COMPLIANT MICROMETL MODULATING <br /> CENTRIFUGAL POWER EXHAUST AND ULTRA LOW LEAK ECONOMIZER. POWERED <br /> EXHAUST TO BE POWERED SEPARATELY FROM ROOFTOP UNIT. PROVIDE HINGED <br /> ACCESS PANELS. PROVIDE 14" FACTORY CURB. SEE ELECTRICAL DRAWINGS FOR <br /> DISCONNECT SWITCH. PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY AIR <br /> PLENUM OF AC UNIT TO SHUT-OFF UNIT UPON DETECTION OF SMOKE. INSTALL <br /> IN STRICT ACCORDANCE WITH THE 2016 CALIFORNIA MECHANICAL CODE, SECTION <br /> 608. COORDINATE WITH ELECTRICAL AND/OR FIRE ALARM SYSTEM CONTRACTOR. <br /> POWER EXHAUST TO MAINTAIN 0.03 in-WC. <br /> MEEHLEIS <br /> MODULAR <br /> BUILDINGS, INC. <br /> A DESIGN BUILD <br /> COMPANY <br /> 1303 E. LODI AVE. <br /> LODI, CA. 95240 <br /> (209) 334-4637 <br /> CA. LIC. NO. 473488 <br /> NV. LIC. NO. 37887 <br /> DRAWN: AT <br /> CHECKED: JD <br /> REVISIONS: <br /> 01/03/20 DSA CORRECTIONS <br /> DATE MAY 1312019 <br /> JOB NO. 19720 <br /> SHEET TITLE <br /> MECHANICAL <br /> SCHEDULES <br /> MEP Et FS / Sustainability / CxA Q�,pFESS/pNq SHEET NO. <br /> 1209 Pleasant Grove Blvd. <br /> Roseville, CA 95678 <br /> p 916-771-0778 M, 6 M -0 , 2 <br /> * REQ. -31- <br /> CONSULTING www.lpengineers.com `s�q�FCHAN\CP���F <br /> Project Navigator P:\I -Project file5\20 19 LP Projects\19-206 I Meehleis- Tokay NS Gym\Mechanical\MP Sheets\192305_MO_2 (Meth Schedules).dwg 113012020 2: 1 I PM <br /> ENGINEERS Job#: 19-2061 F OF CAL\FO <br /> 1 92305_MO_2 (Mech Schedules).dwg 01/30/20 2:1 1 :51 pm Ashton <br />