Laserfiche WebLink
Overfill • <br /> Scope <br /> This procedure will provide a Veeder- Root ATG certified technician a procedure to safely test tank overfill <br /> protection . <br /> Reference Documents <br /> • Veeder-Root TL&UX Operators Manual (576013- 610) <br /> • Veeder- Root TL&3XX Setup Manual (576013- 623) <br /> • Veeder- Root TL&450 Setup and Operation Screens Manual (577013940) <br /> • Veeder• Root TL&450PLUS/TLS4 Operator's Manual (577014- 1 1 0) <br /> • Veeder-Root TLS4 Quick Start (577014 -034) <br /> • Veeder• Root Overfill Alarm Installation Guide (576013 -589) <br /> Consoles <br /> TLS -450PLUS, TLS4c, TLS4i , TLS-450 and TLS3XX <br /> Requirements <br /> TL&450PLUS , TLS4c, TLS4i , TL&450 : Automatic Event : Device Task programmed to trigger on Tank Overfill and <br /> close a relay feeding voltage to the Overfill alarm device. <br /> TL&3XX : Output relay programmed to close a relay on a Tank Overfill alarm feeding voltage to the Overfill alarm <br /> device. <br /> Testing Procedure <br /> 1 . Inspection <br /> a. Verify the levels in the tank to make sure there is product in the tank and that the tank is enabled. <br /> b. If the site is currently receiving a delivery, wait until the delivery is complete. <br /> c. If the tank is performing a SLD tank test, stop the test. <br /> 2 . Preparation <br /> a. Turn Alarm filtering off, as this will allow you to clear alarms quicker. Refer to TL&3XX Setup manual <br /> (576013- 623) or TLS4XX on-line help. <br /> r b. Program Delivery delay to 1 minute, this will allow the delivery to be completed quicker. <br /> 1 . Note the customers original value, so you can restore it after the test. <br /> 24 <br /> I <br />