Laserfiche WebLink
(2) Pneumatic ball valve FCV-*V2 for liquid is closed. <br /> (3) PID controller for liquid is disabled. <br /> (4) Atomizing air valve FCV-*V3 remains open. <br /> (5) After operational readiness is achieved and the control room has switched the injection <br /> system on, the system begins injecting as long as aqueous ammonia is required. <br /> Normal Operations <br /> The aqueous ammonia 19%SCR system runs 24 hours a day, 7 days a week. There are no normal <br /> operations associated with the system other than regular system inspections. <br /> (1) Visually inspect the equipment in the system once per shift. (See the operator's shift <br /> rounds and the Maintenance Section) <br /> (2) Record all maintenance and repair work on the system. <br /> (3) Record all preventative maintenance work using the CMMS. (See the Maintenance <br /> Section) <br /> Normal Shutdow <br /> NOTE: Normally the system will never be shut down unless there is a leak or maintenance needs <br /> to be performed on the equipment. <br /> NOTE: The liquid side must always be completely shut-down before the air side is closed. <br /> (1) Injection of liquid can be stopped by either result of a low NOx level downstream or a <br /> change in the operation mode. <br /> (2) If the NOx level downstream trends in the decreasing direction,the control valves FCV*V1 <br /> will close at a rate defined by the PID control loop. The liquid flow rate is reduced until <br /> valves FCV*V1 are closed. <br /> (3) If the NOx level falls below the limiting valve or the liquid control valve is closed, the <br /> running pump is shut down and the pneumatic actuated ball valve FCV*AV2 is closed. <br /> Atomizing air should continue to be injected. <br /> (4) If necessary, shut off the pumps. This can be done through the control system or by <br /> activating the Emergency Stop Button. <br /> (5) Close the flow control valve. <br /> (6) Run the flush sequence, sending waterto the exhaust and removing any residual aqueous <br /> ammonia from the piping. <br /> (7) Once the flush sequence has completed, maintenance can be performed on the system. <br /> (See the line opening procedure) <br /> If the system is to be shut down for a long period (weeks), the valve skid unit must be treated <br /> with preservation oil to protect internal components. <br /> To prevent water hammer and for faster startup, it is recommended to leave the piping filled <br /> during system standstills. <br /> Temporary Operations <br /> There are no Temporary Operations associated with the aqueous ammonia 19% SCR system. If <br /> Temporary Operations are required at a later date, the procedure(s) will be documented by the <br /> Page I B-4 <br />