SAN10 A Q U I N Environmental Health Department <br /> -- COU NTY --- - - <br /> b . In the dispenser sump crossover piping detail for FRP states a 2 " single wall vapor <br /> recovery piping exiting the under dispenser containment . Vapor recovery single wall <br /> cannot be installed . Revise and resubmit . <br /> 10 ) M . 5 . 3 . 12 — in the l : tank sump drain port detail , indicate how the brine communication will be <br /> tested . Revise and resubmit . <br /> 11 ) G . 5 . 3 . 23- In the D- D : side view section diagram , indicate test port depiction for vacuum <br /> communication . Revise and resubmit . <br /> 12 ) G . 5 . 3 . 25 - In the D- D : side view section diagram , indicate test port depiction for vacuum <br /> communication . Revise and resubmit . <br /> If you have any further questions , please contact me at ( 209) 468-3455 . <br /> Thank ou , <br /> Betty o , HS <br /> Environmental Health Specialist <br /> Cc: attn: David F. Allen, BP West Coast, LLC, 4 Centerpointe Drive, La Palma, CA . 90623 <br /> ► CEI VED <br /> MAR r <br /> QLYIRONAIENrtt <br /> DCPAvrN ; I , . . <br /> 2 of 2 <br />