Laserfiche WebLink
SAN J O A g U I N Environmental Health Department <br /> CC LJ N T Y------- <br /> RCRA Large Quantity Hazardous Waste Generator Inspection Report <br /> Facility Name: Facility Address: Date: <br /> METAL FINISHING SOLUTIONS-STOCKTON 1 1325 EL PINAL DR, STOCKTON August 31, 2020 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 505 CCR 66265.193 Tank system lacks adequate secondary containment or leak detection. <br /> OBSERVATION: Hazardous waste tanks at this facility do not have adequate secondary containment as required <br /> by this section. The pump located between the two waste neutralization tanks appeared to be leaking. Liquid was <br /> observed below the pump. SJC EHD measured the pH of the liquid with pH paper and the result was a pH of 14. <br /> Degradation of the concrete secondary containment was observed around this area and several other spots in the <br /> containment. <br /> REGULATION GUIDANCE: See Title 22 California Code of Regulations section 66265.193 for complete details. <br /> (b)Secondary containment systems shall be: <br /> (1)designed, installed, and operated to prevent any migration of wastes or accumulated liquid out of the system to <br /> the soil, ground water, or surface water at any time during the use of the tank system; and <br /> (2)capable of detecting and collecting releases and accumulated liquids until the collected material is removed. <br /> (c)To meet the requirements of subsection (b)of this section, secondary containment systems shall be at a <br /> minimum: <br /> (1)constructed of or lined with materials that are compatible with the waste(s)to be placed in the tank system and <br /> shall have sufficient strength and thickness to prevent failure due to pressure gradients(including static head and <br /> external hydrological forces), physical contact with the waste to which they are exposed, climatic conditions,the <br /> stress of installation, and the stress of daily operation (including stresses from nearby vehicular traffic); <br /> (2)placed on a foundation or base capable of providing support to the secondary containment system and <br /> resistance to pressure gradients above and below the system and capable of preventing failure due to settlement, <br /> compression, or uplift; <br /> (3)provided with a leak detection system that is designed and operated so that it will detect the failure of either the <br /> primary and secondary containment structure or any release of hazardous waste or accumulated liquid in the <br /> secondary containment system within 24 hours, or at the earliest practicable time if the existing detection technology <br /> or site conditions will not allow detection of a release within 24 hours; <br /> (4)sloped or otherwise designed or operated to drain and remove liquids resulting from leaks, spills, or precipitation. <br /> Spilled or leaked waste and accumulated precipitation shall be removed from the secondary containment system <br /> within 24 hours, or in as timely a manner as is possible to prevent harm to human health or the environment, if <br /> removal of the released waste or accumulated precipitation cannot be accomplished within 24 hours. <br /> Ancillary equipment shall be provided with secondary containment or be inspected daily. <br /> CORRECTIVE ACTION: Immediately correct any deficiencies of the secondary containment by installing a corrosive <br /> resistant coating on the floor and walls of the treatment area secondary containment. This coating is mentioned in <br /> the hazardous waste tank assessment document but does not appear to be currently installed. Consult with your <br /> hazardous waste tank assessment Professional Engineer to determine the correct course of action. Provide a <br /> corrective action statement and supporting documentation to the San Joaquin County Environmental Health <br /> Department(EHD)within 30 days. <br /> This is a Class II violation. <br /> FA0024706 PR0543517 SCO01 08/31/2020 <br /> EHD 22-03 Rev.9/20/2019 Page 13 of 17 RCRA Large Quantity Hazardous Waste Generator OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />