' I <br /> 1 <br /> ELECTRICAL SPECIFICATIONS <br /> GENERAL NOTES: WORKING CLEARANCES FOR PANELS & SWITCHBOARDS <br /> 1 . ELECTRICAL INSTALLATION SHALL COMPLY WITH TITLE 24, CALIFORNIA 1, COORD14ATE WITH OTHER TRADES TO ENSURE CODE REQUIRED WORKING <br /> CODE OF REGULATIONS, INCLUDING THE FOLLOWING: CLEARANCES, ACCESS, ETC. FOR PANELS AND SWITCHBOARDS PER C.EC, <br /> TITLE 24, CCR, PART 2, 2016 CBC SECTIONS 110-16 AND 384-4, <br /> TIRE 24, CCR, PART 3, 2016 CEC TESTING: <br /> TIRE 24, CCR, PART 4, 2016 CMC PICNIC AND OUTDOOR <br /> TITLE 24, CCR, PART9. 2018 CFC 1 , THE ENTIRE ELECTRICAL INSTALLATION SHALL BE FREE FROM SHORT CIRCUITS KITCHEN AREA <br /> ALLAPPLICABLE LOCAL CODES. AND IMPROPER GROUNDS, TEST ALL WIRING AND CONNECTIONS FOR CONTINUITY <br /> 2, ELECTRICAL CONTRACTOR SHALL PROCURE AND PAY FOR ALL LICENSES ETC, AND GROUNDS BEFORE ANY FIXTURES OR EQUIPMENT ARE CONNECTED AND <br /> REQUIRED TO CARRYON AND COMPLETE THE WORK. PERMIT BY OWNER, WHETHER SUCH TESTS INDICATE FAULTY INSULATION OR OTHER DEFECTS, THEY <br /> SHALL BE LOCATED, REPAIRED AND RETESTED AT THE CONTRACTOR'S EXPENSE, <br /> 3, PROVIDE ALL LABOR, MATERIALS, TOOLS, PUNT EQUIPMENT, TRANSPORTATION AND 2. DEMONSTRATE TO THE OWNER AND THE ENGINEER, THAT THE ENTIRE <br /> PERFORM ALL OPERATIONS NECESSARY FOR ANY REASONABLE INCIDENTAL TO PROPER INSTALLATION IS COMPLETE, N PROPER OPERATING CONDITION AND THAT THE <br /> EXECUTION AND COMPLETION OF ALL 'ELECTRICAL WORK' WHETHER SPECIFICALLY CONTRACT HAS BEEN PROPERLY AND FULLY EXECUTED. PROVIDE ALL <br /> MENTIONED OR NOT; ALLAS INDICATED. SPECIFIED HEREIN, AND/OR IMPLIED THEREBY TO INSTRUMENTS MAKESUCHTESTS. <br /> CARRY OUTTHE APPARENT INTENTTHEREOF. <br /> 4. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED WITH THE UNDERWRITERS' <br /> LABORATORIES, INC., SHALL MEET THEIR REQUIREMENTS AND SHALL BEAR THEIR LABEL <br /> WHEREVER STANDARDS HAVE BEEN ESTABLISHED AND LABEL SERVICE IS REGULARLY <br /> FURNISHED BY THAT AGENCY, <br /> 5, ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH THE SIZE ELECTRICAL LEGEND <br /> AND LOCATIONS OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER POSSIBLE, ELECTRICAL POWER <br /> CONTRACTOR SHALL MAKE USE OF ALL DATA IN ALL CONTRACT DOCUMENTS AND VERIFY <br /> THIS INFORMATION AT THE SITE, CONTRACTOR SHALL BE RESPONSIBLE FOR LAYING OUT ALL LINE VOLTAGE WIRING N CONDUIT, SEE GENERAL NOTES <br /> AND INSTALLING HIS WORK TO AVOID INTERFERENCE WITH OTHER TRADES. —rff— TICKS = # OF #12 WIRE, SHORT = HOT, LONG NEUTRAL, DOT GROUND, <br /> UNLESS NOTED OTHERWISE <br /> e. CONDUCTORS SHALL BE COPPER CONDUCTORS TYPE THWN UNLESSOTHERWISE <br /> NOTED OR REQUIRED BY CODE. 'I{ 120V OUTLET, +1 B' TO BOTTOM OF BOX <br /> S = SIGN <br /> 7, WORK SHOWN ON THE DRAWINGS TO BE INSTALLED UNDERGROUND SHALL BE F = FLOOR <br /> INSTALLED AT LEAST 240 BELOW GRADE. BACKFILL IN 60 THICK, PROPERLY MOISTENED GFI = GROUND FAULT INTERUPTER <br /> LAYERS, SOLIDLY PACKED ANDIRON TAMPED TO A DENSITY NOT LESS THAN THAT OF -ws <br /> ADJACENT, UNDISTURBED EARTH, RESTORE SURFACES, ROADWAYS, WALKS, CURBS, 11 COUNTER OUTLET (e)120V PANEL, ADD 20AIP <br /> WALLS, EXISTING UNDERGROUND INSTALLATIONS TO ORIGINAL CONDITION N AN CB FOR NEW ALARM PANELS <br /> ACCEPTABLE MANNER, QUADRUPLEX OUTLET <br /> NAMEPLATES & IDENTIFICATION: HALF SWITCHED OUTLETS <br /> INSTALL ENGRAVED NAMEPLATES FOR EACH PANELSOARD, CABINET, DISCONNECT, ETC. OUTLETS ON EMERGENCY SYSTEMS <br /> NAMEPLATES SHALL BE SECURELY FASTENED TO THE EQUIPMENT WITH #4 PHILLIPS <br /> ROUND HEAD CADMIUM PLATED SELF-TAPPING SCREWS, BRASS BOLT, OR WITH A PLASTIC SD DUCT SMOKE DETECTOR <br /> RESIN ADHESIVE GLUE, GOODYEAR 'PLIEBOND' OR EQUAL <br /> O <br /> WIRING <br /> BOX METHODS: _ <br /> /�J --' <br /> 1 . ALL WIRING SHALL BE INSTALLED W STEEL CONDUffS, CONCEALED N WALL AND MOTOR / DISCONNECT <br /> CEILING U.O.N. o PANELBOARD RESTROOM BUILDING <br /> 2, MINIMUM CONDUIT SIZE SHALL BE 10. MINIMUM ACCEPTABLE CONDUITS ARE ❑ TRANSFORMER / SWITCHBOARD AS NOTED <br /> A. GALVANIZED RIGID STEEL AND <br /> WO <br /> B. GALVANIZED STEEL EMT, OREPROVIDE #AMLAHTALL RM <br /> C. LIQUID TIGHTSTEEL FLEX - FOR FINAL CONNECTION TO OUTDOOR EQUIPMENT. DRAFTING NOTATIONS MOUNT ANELAHWALA OF <br /> SILENLS, <br /> D. FLEXIBLE STEEL CONDUIT - FOR INDOOR FINAL CONNECTIONS TO MOUNT PS 48* ABOVE <br /> TOP DECK. NCE <br /> MECHANICAL EQUIPMENT (NOT TO EXCEED 36m), N## KEYNOTE, SEE SCHEDULE BUTTONIS <br /> ALARM PANELS <br /> CONNECT ALARM PANELS TO A <br /> E. PVC BLIND CONDUITSCHEDULEAE40, UNDERGROUND. N## EQUIPMENT TAG, SEE SCHEDULE CIRCUIT IN ADJACENT PANEL WITH <br /> 3. MCNNICABLING SYSTEMS ARE NOT ALLOWED OWED <br /> THIS BUILDING. D FLOATS TO TRIGGER ALARMS WHEN <br /> 4. MC CABLING SYSTEMS ARE NOT ALLOWED IN THIS BUILDING. LEVELS ARE EXCEEDED. <br /> WIRING DEVICES: A REFERENCE TO A DETAIL VIEW 'A• ON SHEET E-2 <br /> E-2 <br /> UNITS SHALL BE EQUALTO THE DEVICES SET FORTH HEREIN, IN STANDARD COLORS <br /> (BROWN, WHITE. GREY, BEIGE OR IVORY) AS SELECTED BY THE ARCHITECT: NEW ELECTRICAL 1'C PVC WITH <br /> EXISTING ELECTRICAL OR DEMOLISHED WHERE NOTED <br /> A. WIRING DEVICES LEVITON # HUBBELL tl P & S # 2FLOAT CABLES J— — <br /> SINGLE POLE SWITCH 1221 1221 20AC1 <br /> THREE WAYSWITCH 1223 1223 2DAC3 (e) (E) EXISTING DEVICE, TO REMAIN N OPERATION r <br /> DUPLEX CONN, OUT, 15A 5262 5262 5262 I <br /> DUPLEX GPI CONV, OUT. GF5262 (r) (R) REMOVE DEVICE, KEEP REMAINDER OF CIRCUIT IN OPERATION HIGH AND HIGH-HIGH I 12'C-2#12+1#12GND (e)FUSED MAIN DISCONNECT <br /> I LOOP POWER TO <br /> DEVICE PLATES: (RR) REMOVE, RELOCATE AND RECONNECT DEVICE ON EXISTING CIRCUIT, EXTEND CIRCUIT FLOATS, SEE CIVIL PLANS t EACH ALARM PANEL. <br /> WITH SECTIONS OF TANKS I <br /> I <br /> ALL DEVICE PLATES FOR INDOOR USE SHALL DE SMOOTH NYLON APPROVED EQUAL FINISHED CEILING FOR MOUNTING HEIGHTS I PROVIDE NEMA 3R JUNCTION BOX <br /> U S <br /> UNLESS OTHERWISE NOTED. ALL DEVICE PLATES FOR OUTDOOR USE SHALL BE RAISED MOUNTING HEIGHTS _ _ J BELOW ALARM PANELS, WITH <br /> METAL' AUDIBLE FIRE ALARM APPLIANCE _ _ - - EYS SEALS BETWEEN FLOATS <br /> - — - <br /> 2. DEVICE COVERS FOR SURFACE MOUNTED BOXES SHALL BE 12NOT LESS THEN 90' AFF OR AT AND ALARM PANELS,' RAISED STEEL PLATES. LEAST 6' BELOW CEILING - - - <br /> WEATHERPROOF COVERS TO BE SNAP TYPE COVERS. <br /> 3. DEVICE PLATES FOR TELEPHONE AND COMPUTER OUTLETS TO BE PROVIDED BY VISUAL APPLIANCE TO BE - - - - <br /> OWNER'SVENDOR. ALL TELEPHONE AND COMPUTER SYSTEM WIRING BY OWNER'S NOT LESS THAN 80' AFF MIN, - _ - - <br /> VENDOR. AND 12' TYPICAL TO BO TOMORE THAN 96' AFF <br /> SUPPORTS: FIRE ALARM MANUAL <br /> PULL STATION SHALL NOT <br /> 1 . FURNISH ALL NECESSARY FOUNDATIONS, SUPPORTS, BACKING, ETC., FOR ALL SYSTEMS FURNITURE REQUIRE 71GHT GRASPING, <br /> ELECTRICAL ENCLOSURES, CONDUITS AND EQUIPMENT. CONNECTIONS +15' TO PINCHING OR TWISTING OF <br /> 2. ATTACH ALL BOXES, CABINETS, ETC. TO WOOD WITH WOOD OR LAG SCREWS, TO BOTTOM OF BOXES THE WRIST' <br /> METAL WITH MACHINE SCREWS OR BOLTS AND TO CONCRETE WITH EXPANSION ANCHORS CONVIENCE OUTLETS, p ® <br /> AND MACHINE SCREWS OR BOLTS. PHONE & DATA OUTLETS, —0 THERMOSTAT <br /> AW TO BOTTOM OR WALL PHONE <br /> GROUNDING: OF BOX <br /> LIGHT SWITCHES <br /> 1 . GROUND AND BOND ALL EQUIPMENT AS REQUIRED BY GOVERNING CODES AND D DD 482TOTOP <br /> SPECIFICALLY INCLUDING SWITCHBOARD, PANELBOARDS, MOTOR CASES, ETC, OF BOX <br /> FINISHED FLOOR <br /> PANELBOAROS: <br /> UNITS SHALL BE FLUSH OR SURFACE MOUNTED AS INDICATED ON THE PANELSCHEDULE, <br /> WITH THE NUMBER AND SIZE OF BREAKERS INDICATED ON THE PANEL SCHEDULE. SINGLE <br /> POLE, TWO POLE AND THREE POLE BREAKERS SHALL BE BOLT-ON TYPE. THE PANEL <br /> DOORS SHALLHAVE FLUSH TYPE LOCKS, ALL LOCKS SHALL BE KEYED ALIKEAND HAVE 1 ELECTRICAL PLAN WW TANK <br /> TYPEWRITTEN DIRECTORIES INDICATING FIXTURES, EQUIPMENT, OR OUTLETS SERVICED BY <br /> EACH BREAKER. ALL BUSSING SHALL BE COPPER. SCALE: 1 /a• = l l-0- <br /> SUBMITTALGRINDSTONE JOE'S WATER SYSTEM DATE <br /> HCSpOFE65/ 711 N Pershing Avenue 10-28-2019L % Date c9 D C. `wk DRAWN BY MMS FC KJELDSEN DESIGN 14900 W. HIGHWAY Q #90 <br /> e <br /> s � `�d sti �m <br /> Stoddon, CA 95203 LODICA95242 SHEET IDENTIFICATION <br /> 1 00 2 Engineering �' ENP.N<. 5- Q-2t GZEllja3 CHECK BY RCS S S I N N O C K 209-946-0268 El <br /> B I = 2 50 years HORIZONTAL DATUM ORIGNAL DRAWNG SCALE N N E U D E C K 1550 Harbor Drive, Suite 212 ELECTRICAL PLAN G I <br /> SHEET OF <br /> 1/20 IIIc. CIVIL ENGINEERS <br /> °o ' �fcTRwp � � =83, ZONE 3 0 . 1 " West Sacramento, CA 95691 KSNPROJECTFILENO. <br /> 4512Fe*a RwrDfvF. RoddmrA95219 COr uulOa- VERTICAL DATUM www.ksninacom 916-003-5900 <br /> 209-478-82/0 1 wx ks-elg.m 401 DESCRIPTION DATE APPR. NAVD88 � 2414-0010 <br /> C:\Users\RichardSmilhUiCS ENGINEERINGNrojects - OocumenlsUcsn GnrkdStonWJoes\GRINDSTONE ELECTRICALM <br />