Laserfiche WebLink
Overfill Alarm/Ack Switch Installation Guide Wiring Overfill Alarm without Acknowledgement Switch <br /> Wiring Overfill Alarm without Acknowledgement Switch <br /> 1. Pull one wire for neutral from the Overfill Alarm to the power panel. <br /> 2. Pull one wire from the Overfill Alarm to the console for connection to the alarm relay. <br /> T Pull one wire for line from the alarm relay in the console to the power panel. <br /> O4. "Turn power Off and connect wiring according to the wiring diagram in Figure 4 and Tahle 1. <br /> O <br /> ® N <br /> Overfill Alarm <br /> (cover open) <br /> Horn Time <br /> Delay Relay <br /> To Console Relay- <br /> See Console Connection <br /> Table in this manual <br /> Customer supplied <br /> junction box <br /> N L <br /> To power panel <br /> Figure 4.Overfill Alarm only wiring connections <br /> Table 1.- Console Connections <br /> TLS-350 TLS-350 <br /> TLS2 or TLS-50 or TLS-300 1/0 Combo 4 Relay Out- TLS-4XX <br /> TLS-IB TLS-HLD Output Relay Relay put Module Overfill Alarm <br /> Input Connection Connection Connection Connection Connection Relay Connector <br /> Overfill Alarm without Acknowledge Switch(see Figure 4) <br /> Overfill Alarm terminal 2 J6,1 J5,1 NO NO NO NO <br /> Line(from power panel) J6,2 J5,2 C C C C <br /> Overfill Alarm with Acknowledge Switch(see Figure 3) <br /> Ack Switch terminal 1 J6,1 J5,1 NO NO NO NO <br /> Ack Switch terminal 5(line) J6,2 J5,2 C C C C <br /> 6 <br />