Laserfiche WebLink
Recommended Practices for the Testing and Verification of Spill, Overflh, leak Detection and Secondary Containment Equipment at UST Facilities <br /> 2. Clean lite spill bucket and examine it for dam. 6. 5.1 General . Containment sumps Am liquid- <br /> age . Make sure that it is free of cracks, loose tight stimctures designed to temporarily contain <br /> parts or separation of the bucket fiom the till leaks or spills. In addition , containment sumps <br /> pipe . If the spill bucket is damaged notify the often serve as the leak detection monitoring loca- <br /> owner/operator. tion for doublc�wallcd piping systems . Leakage <br /> 3. Attach the test apparatus to the test port . from the primary containment typically flows by <br /> gravity inside the secondary t onttunment to the <br /> 4. Connect the line from the vacuum source to the sump, where it can be easily observed or detected <br /> test apparatus . by a sensor. <br /> S. If the shill bucket is found to have cracks, loose This section describes a hydrostatic test method , <br /> parts or separation of the bucket from the fill There are vacuum test methods available for con= <br /> Pipe-, it is not considered to be liquid-tight . This tainment sumps . Consult the manufacturer before <br /> visually indicates a test failure. performing a vacuum test. <br /> 6.4. 5 Test Procedure . <br /> (VOTE : Follow the manufacturer 's instructions <br /> 1. Slowly apply a vacuum of 15 inches water when testing the interstitial spaces of double - <br /> column to the spill-bucket interstitial space and walled containment sumps . <br /> close the control valve . If a 15 -inch water col- <br /> umn vacuum cannot be attained, the spill bucket 6. 5. 2 Purpose . This section describes the prep <br /> fails the test. See Appendix B for pressure and aration and prmedures to test the integrity of con. <br /> vacuum conversions , tainment sumps to ensure that they do not leak. <br /> 2 . Stan the time-measuretnent device and record 6 . 5 , 3 Description of Test. The containment <br /> the initial vacuum level shown on the gauge . sump is filled to the proper level with water, The <br /> 3 . After I minute, record the ending vacuum level . water level is measured at the beginning and end of <br /> the test . <br /> Upon completion of the test, release the vacuum, <br /> remove the test apparatus and restore the spill 6. 5.4 Test Equipment . Test equipment shall <br /> bucket to its normal operating condition . include ; <br /> 6 .4.6 Pass/ Fall Criterla , If the ending vacuum water; <br /> level is 12 inches water column or greater, the spill measuring stick that is accurate to within i / M <br /> bucket passes the test . (11.063 ) inch and of sufficient length; <br /> If the ending vacuum level is less than 12 incites • stopwatch or other time"measurement device <br /> water column , the spill bucket fails the test, capable of measuring a 1 -second increment. <br /> 6 . 5 Containment Sump Integrity Testing, 6 . 5. 5 Preparation , <br /> 1. Care should be taken when conducting the test <br /> CAUTION : Gaining access to the contain- in the rain or during freezing weather condi- <br /> ment sump requires removing the lid , dons. <br /> cover or dispenser panel that is in place to 2 . Remove and properly dispose of any liquid and <br /> protect the equipment In the sump , These debris ( leaves, sediment and trash) in the cons- <br /> components can be heavy. They may taintnent sump . <br /> require special handling and more than <br /> one person to remove them . Use caution 3 . Inspect the containment sump for damage. <br /> when moving and replacing them when Examine all penetration fittings, conduits, junc- <br /> testingIs complete. During the test, put tion boxes , caps and risers ( if present), and side= <br /> the covers and panels In a safe location wall seams for defects, damage or improperly <br /> where they are secure and Isolated from installed components . if there are loose com- <br /> vehicle and customer traffic . ponents (e.g. , loose penetration fitting clamps <br /> or missing interstitial space caps ) , comet these <br /> items before performing the integrity test . If <br /> pet .org <br />