Restrained Thermal End Loads and Guide Spacing
<br /> Opeirating Twnperature OF(Based on insiallation temperature of 75F)
<br /> 0(YF 21•
<br /> LoadsGuide Thermal Guide Thermal Guide Thermal Guide Thermal Guide Thermal
<br /> size Spacing End Load Spacing End Load Spacing End Load Spacing End Load Spacing End
<br /> 2 11.4 223 9.5 294 8.5 339 8.0 356 7.8 356
<br /> 3 17.1 451 14.3 595 12.8 685 12.0 720 11.8 719
<br /> 4 22.0 540 18.5 713 16.5 821 15.4 863 15.1 862
<br /> 6 32.3 1,161 27.1 1,532 24.3 1,764 22.6 1,855 22.2 1,853
<br /> 8 42-0 1,648 35.2 2,175 31.5 2,503 29.4 2,633 28.9 2,630
<br /> 10 52.0 2,417 43.6 3,189 39.0 3,671 36.4 3,861 35.7 3,856
<br /> 12 61.7 3,306 51.7 4,363 46.3 5.021 43.2 5,281 42.4 5,274
<br /> 14 70.5 4.714 59.1 6,220 52.9 7,158 49.3 7,530 48.4 7,520
<br /> 16 80.4 6,077 67.4 8,018 60.3 9,228 56.3 9,707 55.3 9,694
<br /> 18 89.5 7,113 75.0 9,386 67.1 10,802 62.6 11,363 61.5 11,347
<br /> 20 99.4 8,043 83.3 10,612 74.6 12,214 69.5 12,847 68.3 12,830
<br /> 24 120.0 11,126 100.0 14,681 89.6 16,896 1 83.6 17,773 82.1 17,748
<br /> OTHER CONSIDERATIONS
<br /> Testing:
<br /> The recommended field test procedure for Red Thread 11 pipe is Pipelines operating at low pressures subjected to severe thermal
<br /> to conduct the following cyclic pressure test. The piping system cycling should be tested at 1','^times the piping system pressure
<br /> should be pressurized to 11/times the operating design pressure, rating.
<br /> ten times. The tenth pressurization should be maintained for 1-8
<br /> hours and the line inspected for leaks. Do not field test until all supports, anchors and guides are
<br /> properly installed.
<br /> Field test pressures are limited to 11;2 times the maximum cyclic
<br /> rating of the lowest rated component in the system. The maximum Water Hammer:
<br /> test pressure should not exceed 450 psig for any system without Care should be taken when designing an FRP piping system to
<br /> consulting NOV Fiber Glass Systems. eliminate sudden surges. Soft start pumps and slow actuating
<br /> valves should be considered.