Laserfiche WebLink
Environmental Health DepartmentUnderground Storage Tank Program Inspection ReportDate:November 12, 2019Facility Address:6009 N EL DORADO ST, STOCKTONFacility Name:ARCO AM/PMSUMMARY OF VIOLATIONS(CLASS I, CLASS II, or MINOR - Notice to Comply)RemarksItem #204CCR 2712(i) Current monitoring plan approved by the EHD not found on site. OBSERVATION: An approved copy of the monitoring plans were not available for inspection. REGULATION GUIDANCE: A copy of these plans shall be accessible on site at all times. CORRECTIVE ACTION: Immediately locate and retain a copy on site.This is a minor violation.215CCR 2712(i) Failure to retain a copy of the permit to operate at the facility. OBSERVATION: A copy of the UST operating permit was not found on site. REGULATION GUIDANCE: A copy of the UST operating permit and all attachments and conditions shall be retained at the facility. CORRECTIVE ACTION: Immediately obtain a copy of the permit and retain it on site.This is a minor violation.305HSC 25290.1(e) VPH monitoring of the interstitial spaces of the UST system is not maintained. OBSERVATION: The 87 and diesel fill sump sensor failed when tested. REGULATION GUIDANCE: The interstitial space of the UST shall be maintained, as designed, under constant vacuum or pressure such that a breach in the primary or secondary containment is detected before the hazardous substance is released into the environment. CORRECTIVE ACTION: The sensor was adjusted and retested during the inspection by service technician. This was corrected on site.This is a minor violation.FA0024188 PR0542116 SC001 11/12/2019EHD 23-01 Rev. 9/20/2019Underground Storage Tank Program OIRPage 5 of 71868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjcehd.com