Laserfiche WebLink
SAN )O A Q U I N Environmental Health Department <br /> —COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> COUNTRY MART GAS& FOOD 34243 S CHRISMAN RD, TRACY April 02 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS Il,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> The designated operator failed to document the following: <br /> On the May 2018-March 2019 the DO stated that secondary containment testing was performed on 3/25/18 <br /> however test results found on site stated that it was conducted on 3/28/18. <br /> On the 10/18/18 designated operator(DO)inspection report under <br /> -Section III <br /> The DO failed to add a description to all the components marked N/A or N from section VII <br /> -Section IX <br /> The DO failed to provide mark"Y"or"N"for the question"Are all sensors in containment sumps inspected located <br /> to detect a leak at the earliest opportunity?" <br /> On the 11/21/18 designated operator(DO)inspection report under <br /> -Section III <br /> The DO failed to add a description to all the components marked N/A or N from section VII through XI. <br /> The DO failed to conduct the inspection within 30 days. The october inspection was conducted on 10/18/18 and the <br /> november inspection was conducted on 11/21/18. 32 days apart. <br /> On the 12/12/18 designated operator(DO)inspection report under <br /> -Section III <br /> The DO failed to add a description to all the components marked N/A or N from section VII through XI. <br /> -Section X <br /> The DO failed to mar YES, NO or N/A under the question"Has the line tightness testing been completed within the <br /> required timeframes?"and"Has the tank tightness testing been completed within the required timeframes?" <br /> On the 1/19/19 designated operator(DO)inspection report under <br /> The alarm history was printed out on 1/11/19 and the DO report stated that the inspection was conducted on <br /> 1/19/19. <br /> -Section X <br /> The DO failed to mar YES, NO or N/A under the question"Has the line tightness testing been completed within the <br /> required timeframes?"and"Has the tank tightness testing been completed within the required timeframes?" <br /> During the designated operator inspection,the designated operator shall review the alarm history for the previous <br /> month, check that each alarm was documented and responded to appropriately, and attach a copy of the alarm <br /> history with documentation taken in response to any alarms to the monthly report. Ensure that designated operators <br /> performing inspections at least once every 30 days at this facility and are including all of the required information on <br /> the reports. <br /> This is a repeat violation, Class II. <br /> FA0003290 PR0231801 SCO01 04/02/2019 <br /> EHD 23-01 Rev.09/28/2018 Page 5 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />