Laserfiche WebLink
TAI HI <br /> 011106 TO TnI ce • u rNcr 701 N . Parkcenter Drive, Santa Ana, CA 92705 <br /> p :714/560/8222 www ,tait.com <br /> Identification of Test Procedures for Secondary Containment Testing <br /> To Whom It May Concern : <br /> Tait Environmental Services Inc . utilizes the followingprocedures when conducting Secondary <br /> N t <br /> Containment Testing : <br /> 1 ) Containment Sumps, Transition Sumps, UDCs — Tait follows PEI - 11131200 - 17 Section 6 . 6 for the <br /> accelerated test method . Tait uses the Incon TS- 1000 hydrostatic test equipment following the <br /> attached procedures . <br /> 2 ) Spill Buckets ; Direct Bury & Contained in Sumps — Spill buckets contained in sumps are tested <br /> per PEI - 1200- 17, Section 6 . 2, however Tait Pass/ Fail threshold is 0" drop in one hour. Direct Bury <br /> Spill Buckets are test the same as containment sumps per PEI - 1200- 17 , Section 6 . 6 . <br /> 3 ) Tank Annular Space — testing is conducted per PEI - 1200- 17 , Section 4 . 2 <br /> 4 ) Piping Secondary Containment — Testing is conducted per PEI - RP1200- 17 , Section 5 . 3 <br /> Please consider this letter as our Test Procedure utilized when conducting Secondary Containment <br /> Testing in lieu of either parts or the whole RP1200 document due to copyright infringement . <br />