Laserfiche WebLink
i <br /> Recommended Practices for the Testing and Verification of Spill, Overfill, Leak Detection and Secondary Containment Equipment at UST Facilities <br /> 2. Clean the spill bucket and examine it for dam- 6. 5.1 General . Containment sumps are liquid- <br /> age . Make sure that it is free of cracks, loose tight structures designed to temporarily contain <br /> parts or separation of the bucket from the till leaks or spills , In addition , containment sumps. <br /> pipe . if the spill bucket is damaged notify the often serve as the leak detection monitoring loca- <br /> owner/operator. tion for double walled piping systems , Leakage <br /> 3. Attach the test apparatus to the test port . from the primary contamnient typically flows by <br /> gravity inside the secondary containment to the <br /> 4. Connect the line from die vacuum source to the sump, where it can be easily observed or detected <br /> test apparatus . by a sensor. <br /> 5. 1f the spill bucket is found to have cracks, loose This section descril_ies a hydrostatic test method , <br /> parts or separation of the bucket from the rill There are vacuum test methods available for con- <br /> pipe, it is not considered to be liquid- tight . This tainment sumps , Consult the manufacturer before <br /> �risuall � indicates a test failure. performing a vacuum test. <br /> 6.4. 5 Test Procedure . <br /> NOTE: Follow the manufacturer 's instructions <br /> 1. Slowly apply a vacuum of 15 inches water when testing the interstitial spaces of double- <br /> column to the spill-bucket interstitial space and walled containment sumps , <br /> close the control valve. If a 15-inch water col- - <br /> umn vacuum cannot be attained, the spill bucket 6 , 5, 2 Purpose. This section describes the ptvp- <br /> fails the test. See Appendix B for pressure. and aration and procedures to test the intef=rity of con. <br /> vacuum conversions . tainment sumps to ensure that they do not leak . <br /> 2 . Start die time-measurement device tuid record 6 , 5 ,3 Description of Test . The containment <br /> the initial vacuum level shown on the gauge . sump is filled to the proper level with water. The <br /> 3. Alter I minute , record the ending vacuum level , water level is measured at the bcoinning and end of <br /> the test , <br /> Upon completion of the test, release the vacuum, <br /> remove the test apparatus and restore the spill 6 . 5.4 Test Equipment. Test equipment shall <br /> bucket to its nornial operating condition . include : <br /> 6.4, 6 Pass/ Fail Criteria . If the ending vacuum water, <br /> level is 12 inches water column or greater, the spill measuring stick that is accurate to within 1 / 16 <br /> bucket passes the test , (0.063 ) inch and of sufficient length; <br /> If the ending vacuum level i less than 12 incites • stopwatch or other time" measurement device <br /> water column , the spill ])ticket fails the: rest . capable of measuring a 1 -second increment. <br /> 6, 5 Containment Sump Integrity Testing . 6 . 5. 5 Preparation . <br /> - - - - — — _ - 1. Care should be taken when conducting the test <br /> CAUTION ; Gaining access to the contain- in the run or during freezing weather condi- <br /> ment sump requires removing the lid , tions. <br /> cover or dispenser panel that Is in place to 2. Remove and properly dispose of any liquid and <br /> protect the equipment in the sump . These <br /> components can be heavy. They may debris (leaves, sediment and trash ) in the con- <br /> require special handling and more than tainment sumpr <br /> one person to remove them . Use caution 3 . Inspect the containment sump for damage. <br /> when moving and replacing them when Examine all penetration fittings, conduits, junc- <br /> testingIs complete, During the test, put tion boxes , caps and risers ( if present) , and side- <br /> the covers and panels In a safe location wall seams for defects, damage or intpmperly <br /> where they are secure and Isolated from installed components, if there are loose com - <br /> vehicle and customer traffic . poncnts (e .g„ loose penctnation fitting clamps <br /> or missing interstitial space caps ) , c=orrect these <br /> items before performing the integrity test . If <br /> peLorg 49 <br />