Laserfiche WebLink
(EADIli <br /> JONES COVEY GROUP, INC. <br /> DEVELOPERS <br /> /CONSTRUCTORS <br /> MECHANICAL / ELECTRONIC LEAK DETECTOR CERTIFICATION <br /> SITE: Pilot Flying J 617 DATE: v • • 2 0 1 9 <br /> State Facility# CONTACT: Manager <br /> PHONE: 209 339-4066 <br /> JOB M 197230-1-2 <br /> Tank # 1 2 <br /> Product Diesel#2 Diesel#2 <br /> LD Manufacturer VMI VMI <br /> LD Model VMI LD3000 VMI LD3000 <br /> Sump Condition N/A NIA <br /> Operation Pressure <br /> 37 Psi 40 Psi <br /> (PSI) <br /> Opening Time(Sec) 22 Sec 41 Sec <br /> Metering Pressure <br /> 25 Psi 30 Psi <br /> (PSI) <br /> Functional Element <br /> Holding Pressure 32 Psi 32 Psi <br /> Leak Rate LD Detected <br /> (GPH) 3.00GPH 3 00GPH <br /> Does LD Detect 3 GPH <br /> Leak Rate? Yes Yes <br /> LD Serial 100309016 00309015 <br /> Comments: <br /> Technician Jose Ochoa License Number ICC#8004551 VMI-3032 <br /> Signature /. 1�* <br /> 9595 Lucas Ranch Rd.#100 Rancho Cucamonga,CA 91730 <br /> Office (909)972-7581 Fax(909)484-0300 Fax California State License#804431 A,B,HAZ <br />