REV DATE BY
<br /> Al 5/31/20 HV
<br /> FIXTURE LEGEND
<br /> CELECTRICAL NOTES:
<br /> OFF-I Li SYMBOL DESCRIPTION L1 1. ALL ELECTRICAL WILL MEET 2019 C.E.C. & TITLE 24 STANDARDS.
<br /> (E)225A2. ALL MAIN FEEDERS TO BE XHHW AL.
<br /> 130 PANELI 3. MINIMUM BRANCH CIRCUIT WIRING 12AWG THHN/THWN.
<br /> (E)EIRE- (E)RECESSED TROFFER W/ 4. MINIMUM EMT CONDUIT/STEEL FLEX SHALL BE 1/2' OR LARGER,
<br /> I I ALARM >< 5. WIRE 12AWG - GAWG THHN SHALL BE COPPER ONLY.
<br /> ACRYLIC LENS 6. FEEDER SIZE S #4 - 250 MCM XHHW SHALL BE AL.
<br /> 1 30'x48" I 7. ALL BRANCH FEEDERS SHALL BE EMT OR PVC SCHEDULE 40,
<br /> (E)WALK-IN I CLEAR I ❑ 8. FUSED DISCONNECTS SHALL HAVE TIME DELAY FUSES 'FRN' 'FRS' TYPE, AND EXTERNALLY
<br /> FREEZER �/ L SPACE J OPERATED HANDLE, COMMERCIAL GRADE ONLY.
<br /> 12'wxl6-1/2'dx78'h 9. ALL ETC,, SHALL MEET 2019 TITLE 24 C.E.C.
<br /> PERSONAL LOCKERS ELARGE SUPPLY REGISTER 0. MAX #ROFNC❑NDUCT❑DING SIINHBOARDSEMT, PVC,ANELS FLEX, SHALL NOT EXCEED ALLOWABLE PER 2019 C.E.C.
<br /> 11. EMT, STEEL ❑R ALUMINUM FLES, SEALTITE SHALL BE STANDARD FOR ALL WIRING METHODS,
<br /> 12,MINIMUM CLEARANCE WILL BE 36' AT ALL SWITCH GEAR LOAD CENTERS, UTILITY
<br /> TRANSFORMER, ETC, PER 2019 C,E,C, TABLE 110-34(A).
<br /> (E)S T❑RAGE 13.MAX NUMBER OF OUTLETS (6) WITH MIN #12AWG AND 20amp SINGLE POLE CIRCUIT BREAKER.
<br /> MAX NUMBER OF OUTLETS (4) WITH MIN #12AWG AND 15amp SINGLE POLE CIRCUIT BREAKER.
<br /> RETURN REGISTER 14,EXTERIOR OUTLETS EXPOSED TO WET LOCATIONS SHALL BE WEATHERPROOF TYPE MANUF BY
<br /> CHEMICAL BELL OR EQUAL.
<br /> CABINET 15.ALL SWITCH GEAR, LOAD CENTERS, DISCONNECTS, ETC. SHALL BE MANUFACTURED BY SQUARE
<br /> D OR EQUAL,
<br /> SINGLE POLE LIGHT SWITCH 16.NO 1/2 SPACE CIRCUIT BREAKERS SHALL BE USED,
<br /> IT ALL LIGHT FIXTURES SHALL BE COMMERCIAL TYPE WITH 'UL' LISTINGS,
<br /> (E)WALK-IN 18.ALL CIRCUITS SHALL BE THHN WIRE,
<br /> < O ® EXHAUST FAN 19.USE 2019 C,E,C, TABLE 310,15(B)(16) FOR SIZING CONDUCTORS WHEN EQUIPMENT IS RATED
<br /> COOLER �/ 9 AND LABELED FOR USE OF 75° C WIRE.
<br /> ILLUMINATED EXIT SIGN W COPPER ALUMINUM OR COPPER-CLAD ALUMINUM
<br /> 30 Amp - #12)K)K THHN 25 Amp - #12)K)K THHN
<br /> O® 20 MIN BATTERY BACK-UP 40 Amp - #10*)K THHN 35 Amp - #10)Km THHN ►--�
<br /> EMERGENCY LIGHTING W/ 55 Amp - #8 THHN 45 Amp - #8 THHN p..
<br /> 75 Amp - #6 THHN 55 Amp - #6 THHN
<br /> $ 20 MIN BATTERY BACK-UP 95 Amp - #4 THHN 75 Amp - #4 THHN (�
<br /> 115 Amp - #3 THHN 85 Amp - #3 THHN
<br /> (E)FIRE SPRINKLER x CONDUCTORS, OTHER THAN FLEXIBLE CORDS, FLEXIBLE CABLES, AND FIXTURE WIRES,
<br /> (E)WARE- SHALL BE PROTECTED AGAINST OVERCURRENT IN ACCORDANCE WITH THEIR AMPACITIES
<br /> SPECIFIED IN 310.15, UNLESS OTHERWISE PERMITTED OR REQUIRED IN 2019 C,E.C. 240,4(A)
<br /> WASHING ® (E)GFCI DUPLEX RECEPTACLE LIGHT/ XHAUST FAN THROUGH 240,4(G). W
<br /> 7 SWITCH SHALL B 20.PR❑VIDE MOTOR DISCONNECTING MEANS PER 2019 C.E.C. 430 PART IX 430.101-430.113.
<br /> INTERC NNECTE 21,CONTROLS AND SWITCHES INTENDED TO BE USED BY THE OCCUPANT OF A ROOM OR AREA TO
<br /> O 6 (E)CLG MOUNTED RECEPTACLE O CONTROL LIGHTING AND RECEPTACLE OUTLETS, APPLIANCES OR CO❑LING, HEATING AND
<br /> B VENTILATING EQUIPMENT, SHALL COMPLY WITH SECTION 2019 C.B.C. 1113-308 EXCEPT THE
<br /> LOW REACH SHALL BE MEASURED TO THE BOTTOM OF OUTLET BOX AND THE HIGH REACH Q
<br /> 4 (E)220V 4-WIRE RECEPTACLE zi SHALL BE MEASURED TO THE TOP OF THE OUTLET BOX. w
<br /> 22.ELECTRICAL RECEPTACLE OUTLETS ON BRANCH CIRCUITS OF 30 AMPS OR LESS AND
<br /> ><
<br /> ® s \\ $ (E)DUPLEX RECEPTACLE COMMUNICATION SYSTEM RECEPTACLES SHALL COMPLY WITH 2019 C.B.C. SECTION 11B-308
<br /> EXCEPT THE LOW REACH SHALL BE MEASURED TO THE BOTTOM OF OUTLET BOX AND THE
<br /> \ 23.HIGH REACH SHALL BE MEASURED TO THE TOP OF THE OUTLET BOX.ALL w
<br /> (N)DUPLEX RECEPTACLE GROUNDU AULTTCIROCUITIINTERUPTERNG SHALLONFORM FOR PERSONNELCLE SHALLOBEFPROVIDED ASAREQUIRED TINN
<br /> - 2108(A) THR❑UGH (E) AND INSTALLED IN A READILY ACCESSIBLE LOCATION PER 2019 CEC
<br /> 210,,8(B). w
<br /> (N)DEDICATEDED RECEPTACLE 24.PANELBOARD SHALL BE PROTECTED BY ❑VERCURRENT PROTECTION DEVICE PER 2019 C.E.C.
<br /> 408.36 PART III.
<br /> (N)2'x4' WOOD 25.PR❑VIDE PARITY SIZED GREEN GROUND WIRE IN ALL CONDUITS/BRANCH CIRCUIT HOMERUNS,
<br /> STUDS @ 24' O.C. 26.VERIFY EXACT CONNECTION REQUIREMENTS, OUTLET TYPE, HEIGHT, & LOCATION OF ALL
<br /> 4 I PANEL LOAD CALCULATIONS 27.KITCHEN EQUIPMENT PRIOR ROUGH-IN, REFER TO EQUIPMENT SCHEDULE & FLOOR PLANS FOR
<br /> 7/-5// MORE INFO,
<br /> DESCRIPTIONQUANTITY DEMAND LOAD 28.ALL CONDUIT PENETRATIONS IN RATED ASSEMBLIES SHALL BE RATED AS PER U,L. RATINGS,
<br /> LIGHTS 11 4'FLUOR @ 128W 1.25 1760 VA 29.D❑ NOT INSTALL ANY OUTLETS BACK TO BACK IN STUD WALLS,
<br /> 30.ALL OUTLET BOXES IN RATED WALLS SHALL BE STEEL.
<br /> 4 , I I 31,RECEPTACLES IN 1-HR CONSTRUCTED WALLS BETWEEN OCCUPANCIES SHALL HAVE A MIN. OF
<br /> 0 o RECEPTICLES 10 PLUGS @ 180W 1.0 1800 VA 24' HORIZONTAL SEPARATION.
<br /> I SIGN 1.0 1200 VA 32.NOT MORE THAN 10 LIGHTS SHALL BE ON ANY LIGHTING CIRCUIT,
<br /> SHOW WINDOW 1.0 1200 VA 33.W,P. GFCI CONVENIENCE RECEPTACLE SHALL BE INSTALLED @ ROOF MOUNTED HVAC UNITS
<br /> 4 I
<br /> EQUIPMENT SANDWICH TABLE 115V/10/3.8A 0.65 284 VA
<br /> 2 WARMERS 120V/10/4.2A 0.65 655 VA PANEL A
<br /> 4 I 5 SOFT SERVES 208V/10/12A 0.65 8112 VA MOUNTING: SURFACE PHASE;3 WIRES;4 w
<br /> W.I.C.EVAPORATOR 115V/10/2.3A 0.65 172 VA LOAD PHASE LOAD PHASE
<br /> W.I.C.CONDENSER 115V/10/11.9AO.65 890 VA LOCATION: STORAGE AMPS 225 V❑LTS;208/120
<br /> 3 -0 3 -0 4 -0 A W.I.F.EVAPORATOR 208V/10/10.1A0.65 1366 VA Q
<br /> _3 CIR LOAD AMP A B C A B C AMP LOAD CIR
<br /> W.I.F.CONDENSER 208V/10/18.1A0.65 1447 VALl u I \7
<br /> HVAC UNIT 208V/30/32.8A 1.0 3939 VA N
<br /> 22,825 VA 1 LIGHTS 20/1 512 1248 20/2 SOFT SERVE 2
<br /> F.L.A.@ 208/12OV/30-TOTAL AMPS=63.4A Q O
<br /> 3 SHOW WINDOW 20/1 1200 1248 4 O
<br /> z (E)BOTTOM OF TRUSS a w kn o
<br /> ( E)SUSPENDED T-BAR CLG S SIGN 20/1 1200 900 20/1 PLUGS 6 o, �
<br /> 1 v
<br /> o 7 Pas, PLUGS 20/1 360 1248 20/2 SOFT SERVE 8
<br /> s 9 BACK PLUGS 20/1 360 1 1248 10 0 0C0N
<br /> 2x4 BLOCKING @ 48 O.C.
<br /> W/ 2-10D NAILS @ EA. END 11 LIGHTS 20/1 896 1248 20/2 SOFT SERVE 12 W W >
<br /> (E)PREP/ I (E)DINING
<br /> KITCHEN cv 13 WARMER 20/1 504 1248 ii,
<br /> 14
<br /> 2"x4" OR 2"X6" TOP PLATE 15 SANDWICH 20/1 437 1248 20/2 SOFT SERVE 16
<br /> I
<br /> 17 WARMER 20/1 504 1248 18 O
<br /> I
<br /> 3 -0 19 SPARE 20/1 1248 20/2 SOFT SERVE 20 W
<br /> 1/2 GYP BD @ EACH SIDE
<br /> o 21 SPARE 20/1 1248 22 Z N
<br /> \
<br /> O 23 SPARE 20/1 360 20/1 GFCI PLUGS 24
<br /> ,1 2"x4" D,F. STUDS @ 24" ❑.C. 25 CONDENSER 40/2 1883 50/2 SPARE 26
<br /> rD
<br /> ® o 27 1883 28 d � a
<br /> 0.145"x3" HILTI X-CP 72 FAST- 29 W.I.F. 20/2 1051 SPARE 30 H O
<br /> ENERS @ 32" ❑.C. MAX, ESR-2379 EVAPORATOR 44 Q U U
<br /> 31 1051 3939 40/3 HVAC 32 CA W
<br /> O � �
<br /> 33 EVAPORATOR
<br /> 20/1 265 3939 34
<br /> 2"x4" OR 2"x6" P,T, SILL PLATE 35 W.I.C. 20/1 1369 3939 36 a
<br /> I CONDENSER
<br /> 37 38
<br /> Job: Commercial
<br /> BASE & FL❑❑RING PER 39 40 Drawn By: Hector
<br /> 21'-0" FINISH SCHEDULE
<br /> ® 41 4 2 Date: 5/3 v2o
<br /> A A EXISTING CONCRETE SLAB
<br /> ELECTRICAL PLAN "EWz!"INTERIOR WALL DETAIL A EXISTING FLOOR PLANIOTAL 4310 4145 5020 893189317695 sh�#261.58_°12
<br /> Scale 1/4" = 1'-O" Scale 1/4" = 1'-O"
<br /> A-3