Laserfiche WebLink
3" <br />MAX <br />3" <br />MAX <br />INSUGUARD OR COOPER B -LINE <br />SNAP N' SHIELD PIPE SADDLE <br />SECURED TO UNISTRUT. MATCH <br />COLOR OF INSULATION. (TYP) <br />1 5/8"x1 5/8" GALVANIZED <br />UNISTRUT P -1000, 6'-0" MAXIMUM <br />ON CENTERS, 2'-0" MAXIMUM <br />FROM ANY ELBOW. <br />NOTE: FOR OVERHEAD LINES, UNISTRUT HORIZONTAL, TRA PEZE HUNG <br />BOTTOM OF <br />STRUCTURE <br />LOADS MUST BE <br />HUNG WITHIN 3" <br />OF PANEL POINTS <br />THREADED <br />ROD TYP <br />TOP BEAM <br />CLAMP (TYP.) <br />TOP CHORD OF JOIST <br />ROOF <br />PIPING <br />INSULATION1/2" RETAINING <br />NUT, UNSISTRUT <br />P4010T <br />1/2" CHANNEL <br />NUT WITH <br />SPRING, <br />UNISTRUT P1010 <br />07.07.17SUCTION LINE TRAP AT THE BASE <br />OF THERISER AT ALL POINTS <br />WHERE SUCTION LINES RISES. <br />SUCTION LINE <br />(TYP.) <br />INVERTED SUCTION <br />TRAP AT TOP OF <br />RISER. (TYP.) <br />LIQUID LINE <br />(TYP.) <br />INTERMEDIATE SUCTION LINE <br />TRAP IN WALL, VOID SPACE, <br />OR HIDDEN FROM VIEW. <br />INTERMEDIATE TRAP SHOULD <br />BE PLACED AT THE MIDPOINT <br />OF ANY SUCTION LINE RISE <br />WHICH EXCEEDS 16 FEET. <br />REFRIGERANT SUCTION <br />LINES SPACED 8" O.C. <br />MOUNTED ON UNISTRUT <br />(TYP) <br />07.07.17MINIMUM DIST 6"ROOF MEMBRANE <br />REFRIGERATION PIPING <br />(TYP) <br />CUSH -A -CLAMP FIRMLY <br />CLAMPED TO PIPE (TYP) <br />UNISTRUT <br />P -1000 (TYP) <br />DURA -BLOK DB6 -SERIES OR <br />EQUIVALENT CHANNEL <br />SUPPORT. (TYP) <br />SIDE VIEW SECTION VIEW <br />RUN CONDUIT ON <br />UNISTRUT AS <br />NEEDED <br />SUPPORT PIPING AT 6'-0" <br />MAXIMUM ON CENTERS, 2'-0" <br />FROM ANY ELBOW. DO NOT <br />ATTACH BLOCK TO ROOF <br />03.07.18 <br />SUCTION LINE <br />LIQUID LINE <br />ROUTE SUPPLY AND RETURN <br />HEADERS ON TOP OF CASES <br />WHERE POSSIBLE. <br />SPACE AT 4' INTERVALS. (TYP.) <br />ADJUST LOCATION OF DROPS AS REQUIRED. (TYP) <br />PROVIDE TRAP AT BASE. (TYP) <br />REFRIGERATED CASE <br />MANUFACTURER TO PROVIDED <br />TOP CONNECTED CASES. <br />FRONT OF REFRIGERATED CASE. <br />WHERE APPLICABLE, INSTALL LIQUID LINE SOLENOID, EVA PORATOR <br />PRESSURE REGULATOR, AND FULL PORT ISOLATION BALL VA LVES ON TOP OF <br />CASE. PROVIDE VALVE LOCATION IDENTIFICATION TAG OF ENGRAVED <br />PLASTIC. REF SPECIFICATIONS. <br />PROVIDE 26 GAUGE SHEET METAL DRIP PAN WITH MASTIC C OATING <br />(TOP OF CASE) <br />1" EXPANDED POLYSTYRENE <br />OR EQUAL. 6" MINIMUM WIDTH. <br />LENGTH AS REQUIRED. <br />VALANCE FURNISHED BY CASE <br />MANUFACTURER, INSTALLED BY <br />REFRIGERATION CONTRACTOR. <br />REAR HALF OF <br />REFRIGERATED CASE <br />DESIGNATED FOR <br />PIPING AND VALVES. <br />FRONT HALF OF <br />REFRIGERATED CASE <br />DESIGNATED FOR <br />ELECTRICAL AND EMS <br />COMPONENTS. <br />10.25.18 <br />WHERE APPLICABLE <br />PIPE SUPPORT REF <br />HORIZONTAL REFRIGERANT <br />LINE SUPPORT DETAIL <br />ROOF OPENING TO <br />ACCOMMODATE BOTH <br />REFRIGERATION PIPING <br />AND ELECTRICAL <br />CONDUIT <br />MANUFACTURED METAL <br />CURB, INSULATION AND <br />SHEET METAL ENCLOSURE. <br />REF ARCHITECTURAL PLANS <br />SUPPORT PIPING ON <br />ROOF FOR ADEQUATE <br />SLOPE AND SPACING. <br />03.07.18 <br />2'-0" MAX. <br />ELEVATION <br />SUCTION LINE <br />PIPING INSULATION <br />(BEYOND) <br />WALL OR BUILDING STRUCTURE <br />BOLT <br />.020" THICK PVC JACKET FOR ALL <br />REFRIGERATION LINES EXTERIOR <br />TO BUILDING (TYPICAL) <br />TYPICAL <br />LIQUID <br />LINE <br />PLAN <br />INSULATION <br />UNISTRUT <br />INSULATION <br />LIQUID <br />LINE <br />#022 CUSH -A -CLAMP <br />FIRMLY CLAMPED TO <br />PIPE (TYPICAL) <br />TYPICAL SUCTION LINE <br />1 5/8"x1 5/8" GALVANIZED <br />UNISTRUT P -1000, 10'-0" <br />MAXIMUM ON CENTERS <br />NOTE:MAINTAIN TIGHT SPACING BETWEEN PIPING <br />APPLY EXPANDING FOAM TO <br />CLAMPS AND COVER WITH <br />INSULATION IN A CLEAN AND <br />WORKMAN LIKE MANNER. <br />11.17.17 <br />NTS1HORIZONTAL REFRIGERANT LINE SUPPORT DETAIL <br />NTS2INTERMEDIATE SUCTION LINE TRAP DETAIL <br />NTS3REFRIGERATION PIPING SUPPORT (ON ROOF) <br />NTS4 <br />REFRIGERATION PIPE ROUTING FOR <br />TOP FED CASES <br />NTS6ROOF PENETRATION <br />NTS5VERTICAL REFRIGERANT LINE SUPPORT FAXTELSHEET: <br />DRAWN BY: <br />CHECKED BY: <br />DOCUMENT DATE: <br />ISSUE BLOCKCONSULTANTSSTIPULATION FOR REUSEJOB NUMBER:STORE NO:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.PROTO: <br />ARCHITECT OF RECORD: <br />8131 METCALF AVENUE <br />SUITE 300 <br />OVERLAND PARK, KS 66204 <br />www.brrarch.com <br />TEL: 913-262-9095 <br />FAX: 913-262-9044 <br />WWW.HENDERSONENGINEERS.COMR2 <br />REFRIGERATION <br />DETAILS 2080622025TRACY, CA06/24/2006/24/202025-248MAP <br />04/24/2004/24/20TRACY, CA3010 W GRANT LINE RDMARIAH B. MEYER <br />TREVOR G. JONES20806220258345 LENEXA DRIVE, SUITE 300LENEXA, KS 66214913.742.5000 913.742.5001 <br />TGJ <br />ADD SHEET TO SET <br />1 <br />1 07/17/20 CCD#1