Laserfiche WebLink
LIQUID LINE SOLENOID VALVE (LLSV) WITH <br />208V COIL IN THE 'A' CASE. REF <br />REFRIGERATION PLANS FOR LOCATION. <br />SINGLE POLE RIB <br />FACTORY INSTALLED <br />INSIDE CASE WITH <br />208V COIL, WIRE TO <br />N/O RIB OUTPUT, TYP. <br />INSTALL N/O THERMOSTAT <br />IN EACH CASE, TYP. REF <br />REFRIGERATION PLANS <br />FOR LOCATIONS. <br />CASE 'B'CASE 'A'RCU <br />DEFROST INPUT RIB'S IN EACH <br />CASE FACTORY WIRED SUCH THAT <br />A 208V SIGNAL FROM THE RCU <br />SHALL OPERATE BOTH RIB'S. <br />WIRE LLSV AND THERMOSTAT TO <br />TERMINAL STRIP IN THE RCU. <br />REFER TO RCU <br />MANUFACTURER'S WIRING <br />INSTRUCTIONS. <br />CASE 'B'CASE 'A'RCU <br />WIRE TO RCU DEFROST HEATER CIRCUIT <br />TERMINALS, REFER TO RCU <br />MANUFACTURER'S WIRING INSTRUCTIONS. <br />WIRE TO CASE DEFROST HEATER <br />CIRCUIT TERMINALS, TYP. <br />WIRE CASE RIB'S TO TIME CLOCK 208V <br />N/O TERMINALS IN THE RCU. REFER TO <br />RCU MANUFACTURER'S WIRING <br />INSTRUCTIONS. <br />WIRE CASE THERMOSTATS IN PARALLEL <br />SUCH THAT ANY THERMOSTAT CAN <br />CLOSE THE CIRCUIT TO OPERATE THE <br />LLSV TO RUN THE REFRIGERATION. <br />WIRE ADDITIONAL CASES SERVED <br />BY THE RCU THE SAME AS CASE 'B' <br />REFER TO ELECTRICAL <br />PLANS FOR WIRE SIZES. <br />LIQUID LINE SOLENOID VALVE (LLSV) <br />WITH 208V COIL IN THE 'A' CASE. REF <br />REFRIGERATION PLANS FOR LOCATION. <br />INSTALL N/O THERMOSTAT <br />IN EACH CASE, TYP. REF <br />REFRIGERATION PLANS <br />FOR LOCATIONS. <br />WIRE LLSV AND THERMOSTAT TO <br />TERMINAL STRIP IN THE RCU. <br />REFER TO RCU MANUFACTURER'S <br />WIRING INSTRUCTIONS. <br />WIRE CASE THERMOSTATS IN PARALLEL <br />SUCH THAT ANY THERMOSTAT CAN <br />CLOSE THE CIRCUIT TO OPERATE THE <br />LLSV TO RUN THE REFRIGERATION. <br />WIRE ADDITIONAL CASES SERVED <br />BY THE RCU THE SAME AS CASE 'B' <br />ELECTRIC DEFROST CASE WIRING <br />OFF TIME DEFROST CASE WIRING <br />CONNECT TO LEADS LABELED 208V <br />DEFROST SYNC INPUT LOCATED IN <br />A JUNCTION BOX ON TOP OF CASE. <br />REFER TO CASE MANUFACTURER'S <br />WIRING INSTRUCTIONS. <br />DEFROST INPUT RIB'S IN EACH <br />CASE FACTORY WIRED SUCH THAT <br />A 208V SIGNAL FROM THE RCU <br />SHALL OPERATE BOTH RIB'S. <br />SINGLE POLE RIB <br />FACTORY INSTALLED <br />INSIDE CASE WITH <br />208V COIL, WIRE TO <br />N/O RIB OUTPUT, TYP. <br />FOR HEATCRAFT/HILL PHOENIX <br />RTU'S, SIZE WIRE PER NEC BASED <br />ON RCU OCP SIZE. FOR HUSSMANN <br />RCU'S, USE #14 AWG WIRE. <br />FOR HEATCRAFT/HILL PHOENIX RTU'S, SIZE <br />WIRE PER NEC BASED ON RCU OCP SIZE. <br />FOR HUSSMANN RCU'S, USE #14 AWG WIRE. <br />1 <br />XR75CD <br />2 3 4 5 6 7 8 <br />16 17 18 19 20 21 22 23 24 <br />C <br />1 <br />XR75CD <br />2 3 4 5 6 7 8 <br />16 17 18 19 20 21 22 23 24 <br />C <br />3 <br />1 <br />XR75CD <br />2 3 4 5 6 7 8 <br />16 17 18 19 20 21 22 23 24 <br />C <br />L2 <br />L1 <br />1 <br />XR75CD <br />2 3 4 5 6 7 8 <br />16 17 18 19 20 21 22 23 24 <br />C <br />L2 <br />L1 <br />SR <br />L2 <br />LLSV <br />SR <br />L2 <br />L2 <br />L1 <br />LLSV <br />LLSV <br />WHEN MULTIPLE LLSV'S ARE UTILIZED TO CONTROL THE RE FRIGERATION OF CASES <br />SERVED BY A SINGLE RCU (SUCH AS WHEN CASES ARE NOT LOCATED ADJACENT TO <br />EACH OTHER), WIRE LLSV'S IN PARALLEL SUCH THAT THEY ALL OPERATE <br />SIMULTANEOUSLY. REF REFRIGERATION PLANS FOR LOCATIO NS OF ADDITIONAL <br />CIRCUIT LLSV'S. <br />LLSV <br />WHEN MULTIPLE LLSV'S ARE UTILIZED TO CONTROL THE RE FRIGERATION OF CASES <br />SERVED BY A SINGLE RCU (SUCH AS WHEN CASES ARE NOT LOCATED ADJACENT TO <br />EACH OTHER), WIRE LLSV'S IN PARALLEL SUCH THAT THEY ALL OPERATE <br />SIMULTANEOUSLY. REF REFRIGERATION PLANS FOR LOCATIO NS OF ADDITIONAL <br />CIRCUIT LLSV'S. <br />LIQUID LINE SOLENOID VALVE (LLSV) <br />WITH 208V COIL IN THE 'A' CASE. REF <br />REFRIGERATION PLANS FOR LOCATION. <br />PROVIDE SINGLE POLE <br />RIB INSIDE CASE WITH <br />208V COIL, WIRE TO <br />N/O RIB OUTPUT, TYP. <br />INSTALL N/O THERMOSTAT <br />IN EACH CASE, TYP. REF <br />REFRIGERATION PLANS <br />FOR LOCATIONS. <br />CASE 'B'CASE 'A'RCU <br />WIRE DEFROST INPUT RIB'S <br />IN EACH CASE SUCH THAT A <br />208V SIGNAL FROM THE RCU <br />SHALL OPERATE BOTH RIB'S. <br />WIRE LLSV AND THERMOSTAT TO <br />TERMINAL STRIP IN THE RCU. <br />REFER TO RCU MANUFACTURER'S <br />WIRING INSTRUCTIONS. <br />PROVIDE SINGLE POLE <br />RIB INSIDE CASE WITH <br />208V COIL, WIRE TO <br />N/O RIB OUTPUT, TYP. <br />CASE 'B'CASE 'A'RCU <br />WIRE DEFROST INPUT RIB'S <br />IN EACH CASE SUCH THAT A <br />208V SIGNAL FROM THE RCU <br />SHALL OPERATE BOTH RIB'S. <br />WIRE TO RCU DEFROST HEATER CIRCUIT <br />TERMINALS, REFER TO RCU <br />MANUFACTURER'S WIRING INSTRUCTIONS. <br />WIRE TO CASE <br />DEFROST HEATER <br />CIRCUIT TERMINALS, <br />TYP. <br />WIRE CASE RIB'S TO TIME CLOCK 208V <br />N/O TERMINALS IN THE RCU. REFER <br />TO RCU MANUFACTURER'S WIRING <br />INSTRUCTIONS. <br />ELECTRIC DEFROST CASE WIRING <br />OFF TIME DEFROST CASE WIRING <br />WIRE CASE THERMOSTATS IN PARALLEL <br />SUCH THAT ANY THERMOSTAT CAN <br />CLOSE THE CIRCUIT TO OPERATE THE <br />LLSV TO RUN THE REFRIGERATION. <br />(HEATCRAFT RCU TERMINALS) <br />(HUSSMANN RCU TERMINALS) <br />WIRE ADDITIONAL CASES SERVED <br />BY THE RCU THE SAME AS CASE 'B' <br />REFER TO ELECTRICAL PLANS <br />FOR WIRE SIZES. <br />LIQUID LINE SOLENOID VALVE (LLSV) <br />WITH 208V COIL IN THE 'A' CASE. REF <br />REFRIGERATION PLANS FOR LOCATION. <br />INSTALL N/O THERMOSTAT <br />IN EACH CASE, TYP. REF <br />REFRIGERATION PLANS <br />FOR LOCATIONS. <br />WIRE LLSV AND THERMOSTAT TO <br />TERMINAL STRIP IN THE RCU. REFER TO <br />RCU MANUFACTURER'S WIRING <br />INSTRUCTIONS. <br />WIRE CASE THERMOSTATS IN PARALLEL <br />SUCH THAT ANY THERMOSTAT CAN CLOSE <br />THE CIRCUIT TO OPERATE THE LLSV TO <br />RUN THE REFRIGERATION. <br />(HEATCRAFT RCU TERMINALS) <br />(HUSSMANN RCU TERMINALS) <br />WIRE ADDITIONAL CASES SERVED <br />BY THE RCU THE SAME AS CASE 'B' <br />22-2 (BELDEN 8740 OR <br />EQUIVALENT), TYP. <br />22-2 (BELDEN 8740 OR <br />EQUIVALENT), TYP. <br />FOR HEATCRAFT/HILL PHOENIX <br />RCU'S, SIZE WIRE PER NEC <br />BASED ON RCU OCP SIZE. FOR <br />HUSSMANN RCU'S, USE #14 AWG <br />WIRE. <br />FOR HEATCRAFT/HILL PHOENIX RCU'S, SIZE <br />WIRE PER NEC BASED ON RCU OCP SIZE. FOR <br />HUSSMANN RCU'S, USE #14 AWG WIRE. <br />1 <br />XR75CD <br />2 3 4 5 6 7 8 <br />16 17 18 19 20 21 22 23 24 <br />C <br />1 <br />XR75CD <br />2 3 4 5 6 7 8 <br />16 17 18 19 20 21 22 23 24 <br />C <br />3 <br />LLSV <br />4 <br />N <br />1 <br />XR75CD <br />2 3 4 5 6 7 8 <br />16 17 18 19 20 21 22 23 24 <br />C <br />L2 <br />L1 <br />1 <br />XR75CD <br />2 3 4 5 6 7 8 <br />16 17 18 19 20 21 22 23 24 <br />C <br />L2 <br />L1 <br />L2 <br />L1 <br />SR <br />L2 <br />LLSV <br />4 <br />N <br />SR <br />L2 <br />LLSV <br />WHEN MULTIPLE LLSV'S ARE UTILIZED TO CONTROL THE RE FRIGERATION OF CASES <br />SERVED BY A SINGLE RCU (SUCH AS WHEN CASES ARE NOT LOCATED ADJACENT TO EACH <br />OTHER), WIRE LLSV'S IN PARALLEL SUCH THAT THEY ALL OPERATE SIMULTANEOUSLY. REF <br />REFRIGERATION PLANS FOR LOCATIONS OF ADDITIONAL CIR CUIT LLSV'S <br />LLSV <br />WHEN MULTIPLE LLSV'S ARE UTILIZED TO CONTROL THE RE FRIGERATION OF CASES <br />SERVED BY A SINGLE RCU (SUCH AS WHEN CASES ARE NOT LOCATED ADJACENT TO EACH <br />OTHER), WIRE LLSV'S IN PARALLEL SUCH THAT THEY ALL OPERATE SIMULTANEOUSLY. REF <br />REFRIGERATION PLANS FOR LOCATIONS OF ADDITIONAL CIR CUIT LLSV'S FAXTELSHEET: <br />DRAWN BY: <br />CHECKED BY: <br />DOCUMENT DATE: <br />ISSUE BLOCKCONSULTANTSSTIPULATION FOR REUSEJOB NUMBER:STORE NO:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.PROTO: <br />ARCHITECT OF RECORD: <br />8131 METCALF AVENUE <br />SUITE 300 <br />OVERLAND PARK, KS 66204 <br />www.brrarch.com <br />TEL: 913-262-9095 <br />FAX: 913-262-9044 <br />WWW.HENDERSONENGINEERS.COMR2.1 <br />REFRIGERATION <br />DETAILS 2080622025TRACY, CA06/24/2006/24/202025-248MAP <br />04/24/2004/24/20TRACY, CA3010 W GRANT LINE RDMARIAH B. MEYER <br />TREVOR G. JONES20806220258345 LENEXA DRIVE, SUITE 300LENEXA, KS 66214913.742.5000 913.742.5001 <br />TGJ <br />NTS1DIXELL WIRING DETAIL (FACTORY INSTALLED) <br />NTS2DIXELL WIRING DETAIL (FIELD INSTALLED) <br />ADD SHEET TO SET <br />1 <br />1 07/17/20 CCD#1