Laserfiche WebLink
Underground Storage Tank <br /> Monitoring System Certification Form <br /> 7. LINE LEAK DETECTOR TESTING <br /> ❑ Check this box if line leak detectors ARE NOT installed. (Do not complete this section.) <br /> Simulated rate verified: (Check all that apply) <br /> ® 3 GPH ❑ 0.1 GPH ❑ 0.2GPH Yes NO] <br /> o NA <br /> Has the testing apparatus been properly calibrated? ® ❑ ❑ <br /> For emergency generator tank systems, does the LLD create an audible and visual ❑ Elalarm when a leak is detected? <br /> For mechanical LLDs, does the LLD restrict the flow through the pipe when a <br /> release is detected? ❑ ❑ <br /> For electronic LLDs, does the turbine automatically shut off when a leak is ® El Eldetected? <br /> For electronic LLDs, does the turbine automatically shut off if any portion of the ® ❑ ❑ <br /> monitoring system is disabled or disconnected? <br /> For electronic LLDs, does the turbine automatically shut off if any portion of the ® ❑ ❑ <br /> monitoring system malfunctions or fails a tightness test? <br /> For electronic LLDs, have all accessible wiring connections been visually inspected ® El El <br /> kinks and breaks? <br /> Were all items on the equipment manufacturer's maintenance checklist ® El Elcompleted? <br /> Were all LLDs confirmed operational within regulatory requirements? ® I ❑ 1 . ❑ <br /> LLD/D LLD Model Lines Monitored Pass Fail <br /> 87 PLLD 87 ® ❑ <br /> 91 PLLD 91 ® ❑ <br /> DSL PLLD DSL ® ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> Describe all answers marked "No"or "Fail'and proposed remedy in Section 9. <br /> List all Monitoring equipment either rep/aced or repaired in Section 9. <br /> Page 5 of 8 <br />