Laserfiche WebLink
Underground Storage Tank <br /> Monitoring System Certification Form <br /> 8. IN-TANK GAUGING TESTING <br /> ® Check this box if in-tank gauging is used only for inventory control. <br /> ❑ Check this box if NO tank gauging equipment is installed. Yes No NA <br /> (Do not complete this section if either box is checked.) <br /> All wiring has been: 1) visually inspected for kinks, breaks and proper entry and El I] EJ <br /> and 2) tested for ground faults <br /> Were all in-tank gauging probes visually inspected for damage and residue buildup El [I ❑ <br /> to ensure that floats move freely, functionally tested, and confirmed operational? <br /> Was accuracy of system's product level readings tested? ❑ ❑ ❑ <br /> Was accuracy of system's water level readings tested? ❑ ❑ ❑ <br /> Were all probes reinstalled properly? ❑ ❑ ❑ <br /> Were all items on the equipment manufacturer's maintenance checklist completed? ❑ ElElProbe ID Probe Mode/ Tank Monitored Pass Fail <br /> ❑ El <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> 9. COMMENTS <br /> 11/19/2020 - Found 208 in #11/12 was bad, replaced, retested, test passed. <br /> Found 304 in #3/4 and #9/10 was bad. Replaced the 304 in #3/4, retested, test passed. <br /> Need to return to replace the 304 in #9/10 and top off brine through out site. <br /> 11/30/2020 -Topped off brine. <br /> Found sensor in #9/10 now works, no replacement needed. Retested, test passed. <br /> Page 6 of 8 <br />