D. Results of Testing/Servicing <br /> S-ftware Version Installed VR 1.01 <br /> _.n tete the foil Ing checklist: <br /> X Yes i No' Is the audible alarm operational? <br /> X Yes ❑ No' Is the visual alarm operational? <br /> X Yes ❑ No' Were all sensors visually inspected,functionally tested,and confirmed operational? <br /> X Yes r:i No' Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will not interfere with their <br /> proper operation? <br /> U Yes No' If alarms are relayed to a remote monitoring station,is all communications equipment(e.g.modem)operational? <br /> X N/A <br /> X Yes = No` For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment monitoring system <br /> N/A detects a leak,fails to operate,or is electrically disconnected? If yes:which sensors initiate positive shut-down? (Check all that apply) <br /> X Sumplfrench Sensors; X Dispenser Containment Sensors. Did you confirm positive shut-down due to leaks and sensor <br /> failure/disconnection? X Yes; ❑No. <br /> Yes X No` For tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e. no mechanical overfill prevention <br /> N/A valve is installed),is the overfill warning alarm visible and audible at the tank fill point(s)and operating properly? If so,at what percent <br /> of tank capacity does the alarm trigger? % <br /> X Yes' No Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced and list the <br /> manufacturer name and model for all replacement parts in Section E,below. <br /> Yes' X No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) u Product; ❑Water. If <br /> es,describe causes in Section E,below. <br /> X Yes - No` Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable <br /> X Yes - No' Is all monitoring equipment operational per manufacturer's specifications? <br /> "In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: <br /> • $3 87 Vent-vac.could not get it to go into high liquid,only went into no vac. <br /> • 304 Sensor bad in UDC 3-4.Replaced.Retested and passed. <br /> Monitoring System Certification Page 2 of 4 12107 <br /> 2 2/21/07 <br />