Hazardous Waste Tank System October <br /> Final Assessment per CCR Title 22 <br /> Premier Hyundai of Tracy, 3480 Naglee Dr. Tracy,CA 95304 2014 <br /> Seismic: Provides tank information, seismic acceleration and seismic <br /> calculations showing evidence that the tank is sufficiently anchored for the <br /> seismic forces that may be anticipated during an earthquake. <br /> Premier Hyundai of Tracy <br /> y Waste Oil Tank <br /> ❑' <br /> Waste Oil Tank <br /> New Motor Oil Tank <br /> I ❑� <br /> 7 Simpson Strong Tie <br /> HI-33 Anchor Brackets <br /> with Trubolt Wedge Anchor <br /> 112" Dia x 4 112" with 3" <br /> minimum embedment <br /> eight places, Anchor shear strength 3,432 Ibs <br /> Tank LXWXH: 73"X47" X41" <br /> Material: Steel <br /> Construction: UL142 with integral double wall, rectangular <br /> Weight of Tank: 1,063 <br /> Working Volume:432 gallons <br /> Weight of Contents: 3,314 lbs <br /> Combined Weight:4,377 lbs <br /> j Overturning Moment Arm: 20" <br /> Resisting Moment Arm: 23" <br /> Lat/Lon: 37.76, -121.46 <br /> Sds:0.89 <br /> Strandberg Associates 1(866) 388-0404 rwatergu -rwaterguy.com 21 <br />