My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
INSTALL_2021
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
C
>
CAROLYN WESTON
>
0
>
2300 - Underground Storage Tank Program
>
PR0546181
>
INSTALL_2021
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
4/17/2023 9:15:47 AM
Creation date
10/30/2020 4:28:57 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
INSTALL
FileName_PostFix
2021
RECORD_ID
PR0546181
PE
2351
FACILITY_ID
FA0026131
FACILITY_NAME
7-ELEVEN INC. #38616
STREET_NUMBER
601
Direction
W
STREET_NAME
CAROLYN WESTON
STREET_TYPE
BLVD
City
STOCKTON
Zip
95206
APN
16422019
CURRENT_STATUS
01
SITE_LOCATION
601 W CAROLYN WESTON BLVD
P_LOCATION
01
QC Status
Approved
Scanner
SJGOV\kblackwell
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
120
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
2. Page G1.0 incorrectly states that the pipe with the longest run is diesel. This is inconsistent with the plan <br /> drawings. <br /> a. Your response: Added table to G1.0 for longest product piping runs to each dispenser. The longest <br /> product piping run is DSL product piping to dispenser 5 at 165'. <br /> b. Comment: The diesel pipe only runs to dispensers 1 and 5. Please provide the product piping with the <br /> longest TOTAL pipe length. <br /> 3. Provide current contractor's training certifications for installation and testing of all proposed UST <br /> equipment/components. <br /> 4. Provide a drawing indicating the locations of all water wells, septic systems, and storm drains. <br /> a. Your response: Added note to sheet G0.0 indicating water wells,septic systems, and storm drains not <br /> applicable on set. <br /> b. Comment: This site location will not have any storm drains at all? Please explain/clarify. <br /> 5. G12.1: Please clarify the vacuum tubing connection/end point for <br /> a. Vent line in RUL fill/vapor sump <br /> b. Vapor manifold line in PUL fill/vapor sump <br /> c. Diesel vent line in remote vent sump <br /> 6. G12.2:The diesel vent line vacuum tubing in the "Vent Box Vacuum Sensor Detail" appears to be connected to <br /> the sensor. <br /> Can you verify the site address please? When I was assigned this project I was informed that the site did not have an <br /> address yet. Is the official site address 601 Carolyn Weston Blvd? <br /> Vicky Vang-Lee I Environmental Health Specialist <br /> San Joaquin County Environmental Health Department <br /> 1868 E. Hazelton Ave. Stockton, CA 95205 <br /> (209) 616-3028 1 vvang-lee(.isj'gov.org <br /> From: Christopher Kolbe<ckolbe@pmdginc.com> <br /> Sent: Monday,January 11, 20213:00 PM <br /> To:Vang-Lee,Vicky [EHD] <vvang-lee@sigov.org> <br /> Cc: Robert Forloine<rforloine@pmdginc.com>; Crystal.Justice@7-11.com <br /> Subject: RE: 1042991/38616, 601 Carolyn Weston Blvd, Stockton <br /> CAUTION:This email is originated from outside of the organization. Do not click links or open attachments unless you recognize the <br /> sender and know the content is safe. <br /> Vicky, <br /> Here is the link to the 3rd round CUPA comments for our 7-11 project. Please let me know if you need anything <br /> else. Also, do you know how long this next round review should take? <br /> https://spaces.hightail.com/space/looRLrci5z <br /> Christopher Kolbe <br /> FANJob Captain <br /> DESIGN Direct: (707) 921-1308 <br /> 4 <br />
The URL can be used to link to this page
Your browser does not support the video tag.