Laserfiche WebLink
Table 3A <br />INTEGRITY TESTING PROGRAM-SCOPE & FREQUENCY <br />KRC TRACY PLANT <br />li Te~; I <br />#1 <br />Tank Volume (GA"' 10,000 <br />Tank Type Horz Tnk <br />Ul2085 <br />Contents Diesel <br />CRDM Sides, Base <br />Seepage <br />RPB AS : design and <br />PCC footing <br />I STI Cateaor·v Category 1 <br />' Visual inspection by facility personnel (as M <br />II per checklist App B) A <br />I' External inspection by certified inspector (as 1 Oyr* <br />I per STI Std SP-00'!) <br />I External inspection by certified inspector (as <br />I perSTi Std SP-001\ <br />EE <br />, <br />I <br />' Tank tightness test nla <br />meeting req'ts of <br />40 CFR 280 (USTs) <br />Legend. <br />CRDrv1: Continuous Release Detection Method <br />RPB: Release Prevention Barrier <br />M: Monthly Q: Quarterly <br />A: Annual <br />* Or ear!ier as recommended by certified inspector <br />based on findings from extemat :nspection <br />J ~2/ #3 <br />Oit vi Jvvl"~"" <br />500 Est. 200 GA <br />Horz Tnk UL 2085 Utility Co Elect <br />Rectangular Transformer <br />Diesel Off Hiahwav Heat Transfer <br />Sides, Base Sides, Base <br />Seepage Seepage <br />AST design and Concrete Pad <br />PCC footing <br />Category 1 Category 1 <br />M M <br />A A <br />10 yr* 10yr* <br />EE EE <br />n/a n/a <br />EE: Inspection not required given use <br />of environmentally equivalent measure