CA GREEN CODE REQUIREMENTS ,
<br /> 1. PER CALGREEN SECTION 5.303.2, PLUMBING FIXTURES SHALL MEET THE MAXIMUM FLOW RATE VALUES SHOWN
<br /> IN TABLE 5.303.2.3. EXCEPTION: BUILDING THAT DEMONSTRATE 20% OVERALL WATER USE REDUCTION. IN THIS
<br /> CASE, A CALCULATION DEMONSTRATING A 2% REDUCTION IN THE BUILDING "WATER USE BASELINE," AS
<br /> ESTABLISHED IN TABLE 5.303.3 SHALL APPLY TO NEW FIXTURES IN ADDITIONS OR AREAS OF ALTERATIONS TO
<br /> THE BUILDING.
<br /> MAXIMUM FIXTURE FLOW RATES:
<br /> FIXTURE TYPE MAXIMUM FLOW RATE
<br /> LAVATORY FAUCETS-NONRESIDENTIAL 0.5 GPM ® 60 PSI
<br /> KITCHEN FAUCETS 1.8 GPM @ 60 PSI z
<br /> METERING FAUCETS 0.25 GALLONS/CYCLE 0
<br /> WATER CLOSETS 1.28 GALLONS/FLUSH
<br /> URINALS 0.5 GALLONS/FLUSH
<br /> w
<br /> 2. PER CALGREEN SECTION 5.303.3.1, THE EFFECTIVE FLUSH VOLUME OF ALL WATER CLOSETS SHALL NOT 0
<br /> EXCEED 1.28 GALLONS PER FLUSH. TANK-TYPE WATER CLOSETS SHALL BE CERTIFIED TO THE PERFORMANCE
<br /> CRITERIA OF THE US EPA WATER SENSE SPECIFICATION FOR TANK-TYPE TOILETS. NOTE: THE EFFECTIVE
<br /> FLUSH VOLUME OF DUAL FLUSH TOILETS IS DEFINED AS THE COMPOSITE, AVERAGE FLUSH VOLUME OF TWO
<br /> REDUCES FLUSHES AND ONE FULL FLUSH.
<br /> 3. PROVIDE READILY ACCESSIBLE AREAS THAT SERVE THE ENTIRE BUILDING AND ARE IDENTIFIED FOR THE
<br /> DEPOSITING, STORAGE, AND COLLECTION OF NONHAZARDOUS MATERIALS FOR RECYCLING. PER SECTION
<br /> 5.410.1.1 ANY ADDITION OR ALTERATION RESULTING IN LESS THAN A 30% INCREASE IN THE TENANT SPACE
<br /> FLOOR AREA IS EXEMPT FROM THIS REQUIREMENT.
<br /> 4. PER CALGREEN SECTION 5.504.3, AT THE TIME OF ROUGH INSTALLATION AND DURING STORAGE ON THE
<br /> CONSTRUCTION SITE AND UNTIL FINAL STARTUP OF THE HEATING, COOLING, AND VENTILATING EQUIPMENT, ALL
<br /> DUCT AND OTHER RELATED AIR DISTRIBUTION COMPONENT OPENINGS SHALL BE COVERED WITH TAPE, PLASTIC, w
<br /> SHEET METAL, OR OTHER APPROVED METHODS TO REDUCE THE AMOUNT OF DUST, WATER, AND DEBRIS WHICH Q
<br /> MAY ENTER THE SYSTEM. o
<br /> 5. PER CALGREEN SECTION 5.504.4.1, ADHESIVES, ADHESIVE BONDING PRIMERS, ADHESIVE PRIMERS, SEALANTS,
<br /> SEALANT PRIMERS AND CAULKS SHALL COMPLY WITH TABLE 5.504.4.1 AND 5.504.4.2. w
<br /> Of
<br /> SEALANT VOC LIMIT: ARCHITECT OF RECORD:
<br /> ARCHITECTURAL 250 SED ARC/
<br /> y/
<br /> DECK 760 i�
<br /> NONMEMBRANE ROOF 300 V CRAIG S.
<br /> ROADWAY 250 BLUME-
<br /> SINGLE-PLY ROOF MEMBRANE 450
<br /> OTHER 420 * NO.-C-31661
<br /> Q .331 2021 (q
<br /> y
<br /> 6. PER CALGREEN SECTION 5.504.4.3, ARCHITECTURAL PAINTS AND COATINGS SHALL COMPLY WITH TABLE �cSC ,�y
<br /> 5.504.4.3. d0 �o
<br /> VOC CONTENT LIMITS FOR ARCHITECTURAL COATINGS:
<br /> INDOOR CARPET ADHESIVES 50
<br /> CARPET PAD ADHESIVES 50 � , O
<br /> OUTDOOR CARPET ADHESIVES 150
<br /> WOOD FLOORING ADHESIVES 100
<br /> RUBBER FLOOR ADHESIVES 60
<br /> SUBFLOOR ADHESIVES 50
<br /> CERAMIC TILE ADHESIVES 65
<br /> VCT AND ASPHALT TILE ADHESIVES 50
<br /> DRYWALL AND PANEL ADHESIVES 50
<br /> COVE BASE ADHESIVES 50
<br /> MULTIPURPOSE CONSTRUCTION ADHESIVES 70 W
<br /> STRUCTURAL GLAZING ADHESIVES 100 m
<br /> SINGLE-PLY ROOF MEMBRANE ADHESIVES 250 D a °
<br /> OTHER ADHESIVES NOT SPECIFICALLY LISTED 50 O r
<br /> SPECIALTY APPLICATIONS PVC WELDING 510 Q °
<br /> cj
<br /> } � 3
<br /> CPVC WELDING 490 a o 3
<br /> ABS WELDING 325
<br /> PLASTIC CEMENT WELDING 250 o °'
<br /> ADHESIVE PRIMER FOR PLASTIC 550 0 � 3-p `o N N
<br /> CONTACT ADHESIVE 80 o V o °`o ° °�_'° `o
<br /> SPECIAL PURPOSE CONTACT ADHESIVE 250 0 J a °
<br /> STRUCTURAL WOOD MEMBER ADHESIVE 140 °
<br /> N ` °' ` ° p
<br /> a `oa�v° �
<br /> TOP AND TRIM ADHESIVE 250 o o-o
<br /> J ;, ° c
<br /> c -p a� 0o0�
<br /> SUBSTRATE SPECIFIC APPLICATIONS METAL TO METAL 30 0 �+ ° °'ate n+' a N
<br /> PLASTIC FOAMS 50 v - , 10-
<br /> POROUS MATERIAL (EXCEPT WOOD) 50 aci N E - o.5 °'o
<br /> WOOD 30 0 � o.5o °cv,a
<br /> N o C °p '
<br /> FIBERGLASS 80 OO " -.• c L 0'a
<br /> N p 0 o L O
<br /> 7. PER CALGREEN SECTION 5.504.4.3.2, VERIFICATION OF COMPLIANCE WITH THIS SECTION SHALL BE PROVIDED �' r- ..2 °-° p
<br /> w 2 -p 0.5' E U c
<br /> AT THE REQUEST OF THE ENFORCING AGENCY. DOCUMENTATION MAY INCLUDE, BUT IS NOT LIMITED TO, THE o c Ucy o N O
<br /> FOLLOWING: ma � L 0 ° N
<br /> 1. MANUFACTURER'S PRODUCT SPECIFICATION m ° ~` ° o p
<br /> 2. FIELD VERIFICATION OF ON-SITE PRODUCT CONTAINERS 2 ° � ami `o
<br /> N p N c
<br /> U ? U
<br /> O p
<br /> a N p,� U+N+
<br /> 8. PER CALGREEN SECTION 5.504.4.6, RESILIENT FLOORING SYSTEMS SHALL COMPLY WITH THE VOC-EMISSION v o ° 8- a
<br /> ,� aN �—
<br /> LIMITS DEFINED IN THE 2012 CHPS CRITERIA AND LISTEN ON ITS HIGH PERFORMANCE PRODUCTS DATABASE, o 0 0 , ° a o
<br /> PRODUCTS COMPLIANT WITH CHPS CRITERIA CERTIFIED UNDER THE GREENGAURD CHILDREN & SCHOOLS U
<br /> 0 N L O
<br /> PROGRAM, CERTIFIED UNDER THE FLOORSCORE PROGRAM OF THE RESILIENT FLOOR COVERING INSTITUTE, OR g'm u�° cc,a�
<br /> SHALL MEET CALIFORNIA DEPARTMENT OF PUBLIC HEALTH 2010 SPECIFICATION. Wo o o � o 20.3 o o
<br /> o ® v T3 `o Lo
<br /> enc
<br /> w 5 a
<br /> 9. PER CALGREEN SECTION 5.508.1, RECYCLE AND/OR SALVAGE FOR REUSE A MINIMUM OF 65 PERCENT OF THE a U) o L L�, °
<br /> NONHAZARDOUS CONSTRUCTION OR DEMOLITION WASTE IN ACCORDANCE WITH SECTION 5.408.1.1, 5.408.1.29 OR w a'3
<br /> c-w M
<br /> 5.408.1.3 OR MEET A LOCAL CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT ORDINANCE, WHICHEVER IS a
<br /> MORE STRINGENT. Ztk
<br /> bi
<br /> rn00
<br /> r w o m o Q w
<br /> 10. PER CALGREEN SECTION 5.504.1.3, TEMPORARY VENTILATION. THE PERMANENT HVAC SYSTEM 00 o 0 o 0 N
<br /> w N w Q (n \ O
<br /> SHALL ONLY BE USED DURING CONSTRUCTION IF NECESSARY TO CONDITION THE BUILDING OR Z o 0 N
<br /> AREAS OF ADDITION OR ALTERATION WITHIN THE REQUIRED TEMPERATURE RANGE FOR MATERIAL o z - z > � a o
<br /> AND EQUIPMENT INSTALLATION. IF THE HVAC SYSTEM IS USED DURING CONSTRUCTION, USE RETURN o z o
<br /> AIR FILTERS WITH A MINIMUM EFFICIENCY REPORTING VALUE (MERV) OF 8, BASED ON ASHRAE (n O ci
<br /> 52.2-1999, OR AN AVERAGE EFFICIENCY OF 30 PERCENT BASED ON ASHRAE 52.1-1992. REPLACE
<br /> ALL FILTERS IMMEDIATELY PRIOR TO OCCUPANCY, OR, IF THE BUILDING IS OCCUPIED DURING
<br /> ALTERATION AT THE CONCLUSION OF CONSTRUCTION. Q
<br /> U
<br /> W
<br /> 11. PER CALGREEN SECTION 5.504.3, COVERING OF DUCT OPENINGS AND PROTECTION OF MECHANICAL
<br /> EQUIPMENT DURING CONSTRUCTION. AT THE TIME OF ROUGH INSTALLATION AND DURING STORAGE ON THE
<br /> CONSTRUCTION SITE UNTIL FINAL STARTUP OF THE HEATING, COOLING AND VENTILATING EQUIPMENT, ALL DUCT
<br /> AND OTHER RELATED AIR DISTRIBUTION COMPONENT OPENINGS SHALL BE COVERED WITH TAPE, PLASTIC,
<br /> SHEETMETAL OR OTHER METHODS ACCEPTABLE TO THE ENFORCING AGENCY TO REDUCE THE AMOUNT OF
<br /> DUST, WATER AND DEBRIS WHICH MAY ENTER THE SYSTEM.
<br /> 12. PER CALGREEN SECTION 5.504.7, ENVIRONMENTAL TOBACCO SMOKE (ETS) CONTROL. WHERE OUTDOOR
<br /> AREAS ARE PROVIDED FOR SMOKING, PROHIBIT SMOKING WITHIN 25 FEET OF BUILDING ENTRIES, OUTDOOR AIR o
<br /> INTAKES AND OPERABLE WINDOWS AND WITHIN THE BUILDING AS ALREADY PROHIBITED BY OTHER LAWS OR 0 O Q z $
<br /> REGULATIONS; OR AS ENFORCED BY ORDINANCES, REGULATIONS OR POLICIES OF ANY CITY, COUNTY, CITY z of _
<br /> AND COUNTY, CALIFORNIA COMMUNITY COLLEGE, CAMPUS OF THE CALIFORNIA STATE UNIVERSITY, OR CAMPUS 0 Q Dw g
<br /> OF THE UNIVERSITY OF CALIFORNIA, WHICHEVER ARE MORE STRINGENT. WHEN ORDINANCES, REGULATIONS OR
<br /> POLICIES ARE NOT IN PLACE, POST SIGNAGE TO INFORM BUILDING OCCUPANTS OF THE PROHIBITIONS. 0 w o w
<br /> LL_ m w Q
<br /> ~ W
<br /> 0 0 J V
<br /> z
<br /> LLJ Q
<br /> LD w
<br /> 0 w N04
<br /> 00 gz w o0
<br /> o0
<br /> w
<br /> 0 X w 0 w Ld
<br /> L
<br /> N W o U) 0
<br /> wOGN1 . 1
<br /> W GENERAL NOTES