PLUMBING LEGEND
<br />SYMBOL
<br />DESCRIPTION
<br />WASTE
<br />SOIL, WASTE OR SANITARY SEWER BELOW GRADE OR SLAB
<br />GW
<br />GREASE WASTE BELOW GRADE
<br />AW
<br />ACID WASTE
<br />CW
<br />SOIL, WASTE OR SANITARY SEWER ABOVE GRADE OR SLAB
<br />- - - - - -
<br />VENT PIPING
<br />-
<br />COLD WATER PIPING
<br />- -
<br />HOT WATER PIPING
<br />---
<br />HOT WATER RETURN PIPING
<br />T
<br />TEMPERED WATER PIPING
<br />F
<br />FILTERED WATER PIPING
<br />G
<br />GAS PIPING - PRESSURE NOTED
<br />CA
<br />COMPRESSED AIR PIPING
<br />FS
<br />FIRE SPRINKLER PIPING
<br />SD
<br />STORM DRAIN PIPING
<br />P4TR
<br />PRESSURE AND TEMPERATURE RELIEF PIPING
<br />CD
<br />CONDENSATE DRAIN PIPING
<br />'
<br />EXISTING PIPING OR FIXTURE TO BE REMOVED OR ABANDONED IN PLACE
<br />--111---
<br />UNION
<br />-Df3--- , SOV
<br />SHUT OFF VALVE
<br />tea- <4 GV
<br />GATE VALVE
<br />___0_ GV/VB
<br />GATE VALVE IN VALVE BOX
<br />-}- CKV
<br />CHECK VALVE - DIRECTION OF FLOW INDICATED
<br />--i�--- BV
<br />BALL VALVE
<br />C>
<br />AUTOMATIC GAS SHUT-OFF VALVE
<br />P4TRV
<br />PRESSURE AND TEMPERATURE RELIEF VALVE
<br />-� GCO, FCO
<br />GRADE CLEAN OUT, FLOOR CLEAN OUT
<br />�t-- CO, WCO
<br />CLEANOUT, WALL CLEANOUT
<br />-® FD
<br />FLOOR DRAIN
<br />�-- FS
<br />FLOOR SINK
<br />-+ HB
<br />HOSE BIBS
<br />-+- -�}- POC
<br />POINT OF CONNECTION
<br />I.E.
<br />INVERT ELEVATION
<br />FF.
<br />FINISHED FLOOR
<br />/FT
<br />PER FOOT
<br />US,UF,UG
<br />UNDER SLAB, UNDER FLOOR, UNDERGROUND
<br />FA, TA
<br />FROM ABOVE, TO ABOVE
<br />FB, TB
<br />FROM BELOW, TO BELOW
<br />TYP.
<br />TYPICAL
<br />(N)
<br />NEW
<br />(E), EXISTING
<br />EXISTING TO BE FIELD VERIFIED BY CONTRACTOR
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />AFG
<br />ABOVE FINISHED GRADE
<br />ABC
<br />ABOVE CEILING
<br />CI
<br />CAST IRON
<br />VCP
<br />VITRIFIED CLAY PIPE
<br />V, VR, VTR
<br />VENT, VENT RISER, VENT THRU ROOF
<br />A WD
<br />WASTE, WASTE DROP
<br />HW, HWD, HWR
<br />HOT WATER, HOT WATER DROP, HOT WATER RISER
<br />CW, CWD, GWR
<br />COLD WATER, COLD WATER DROP, COLD WATER RISER
<br />TDL
<br />TOTAL DEVELOPED LENGTH
<br />FIXTURE CONNECTION SCHEDULE
<br />SYMBOL FIXTURE DESCRIPTION
<br />VENT
<br />WASTE
<br />WATER
<br />0
<br />GAS
<br />DIRECT
<br />IIID.
<br />CW
<br />HW
<br />BTUH
<br />WC
<br />WATER CLOSET, FV
<br />2
<br />3
<br />-
<br />11/4
<br />-
<br />-
<br />L
<br />LAVATORY
<br />11/z
<br />2
<br />1-114"
<br />3/4
<br />3/4
<br />-
<br />MS
<br />MOP SINK
<br />11/2
<br />2
<br />-
<br />1/2
<br />1/2
<br />6.3
<br />FD/FS
<br />2" FLOOR DRAIN/SINK
<br />2
<br />2
<br />-
<br />-
<br />72.5
<br />7.5
<br />FD/FS
<br />3" FLOOR DRAIN/SINK
<br />2
<br />3
<br />-
<br />-
<br />-
<br />-
<br />13
<br />3 -COMPARTMENT SINK
<br />DIRECT CPG 104.3
<br />JOINT.
<br />BFP
<br />14
<br />DISHWASHER
<br />BEVERAGE MACHINES, COFFEE MACHINE, TEA BREWER AND ESPRESSO
<br />-
<br />11/2
<br />-
<br />3/4
<br />-
<br />15
<br />HOT FOOD WELL
<br />-
<br />-
<br />3/4
<br />1/2
<br />-
<br />-
<br />IS
<br />SODA STATION
<br />-
<br />-
<br />3/4
<br />1/2
<br />-
<br />-
<br />19
<br />COFFEE MAKER
<br />-
<br />-
<br />3/4
<br />1/2
<br />-
<br />-
<br />NO.
<br />HAND SINK
<br />11/2
<br />2
<br />-
<br />'/2
<br />I/2
<br />-
<br />21
<br />ICE MACHINE
<br />-
<br />-
<br />3/4
<br />I/2
<br />-
<br />_
<br />22
<br />PREP SINK
<br />TOTAL
<br />FU
<br />3 -COMPARTMENT SINK
<br />1
<br />3
<br />3
<br />GENERAL PLUMBING NOTES
<br />1. ALL EQUIPMENT AND MATERIALS USED SHALL BE NEW AND SHALL
<br />BE EQUAL IN QUALITY, TYPE, CAPACITY AND ACCESSORIES TO THE
<br />EQUIPMENT NOTED ON THE DRAWINGS. ADJUSTMENTS TO
<br />CONSTRUCTION AND ACCESSORIES ON SUBSTITUTED EQUIPMENT
<br />MAY BE REQUIRED TO ACHIEVE THIS EQUALITY, AND SHALL BE
<br />INCLUDED AT NO EXTRA COST TO THE OWNER MAKE ANY CHANGES
<br />IN PIPING, FRAMING, ETC., AS REQUIRED TO ACCOMMODATE
<br />SUBSTITUTED EQUIPMENT.
<br />2, INSTALL ALL EQUIPMENT AND MATERIALS AND PERFORM ALL WORK
<br />IN ACCORDANCE WITH ALL APPLICABLE CODES. APPLICABLE
<br />CODES SHALL INCLUDE, BUT NOT BE LIMITED TO THE LATEST
<br />EDITIONS OF THE UNIFORM MECHANICAL CODE FOR THE STATE OF
<br />CALIFORNIA, UNIFORM PLUMBING CODE FOR THE STATE OF
<br />CALIFORNIA, CALIFORNIA CODE OF REGULATIONS (CCR), UNIFORM
<br />FIRE REGULATIONS AND TITLE 24 ENERGY EFFICIENCY STANDARDS.
<br />WHERE HEAVIER GAGES OF MATERIAL, LARGER SIZES OR MOR_
<br />STRINGENT REQUIREMENTS THAN THE CODES ARE REQUIRED BY THE
<br />CONTRACT DOCUMENTS, SUCH INCREASED REQUIREMENTS SHALL
<br />APPLY.
<br />3, PIPING MATERIALS SHALL BE AS FOLLOWS:
<br />WASTE AND VENT SHALL BE SCHEDULE Ofd PVC.
<br />POLYVINYL CHLORIDE (PVC) PLASTIC PIPE. ALL
<br />PIPE, COUPLINGS AND FITTINGS SHALL BE MANUFACTURED OF
<br />MATERIAL CONFORMING TO ASTM D 1185. PLASTIC SOLVENT CEMENT
<br />FOR PVC PLASTIC PIPE SHALL CONFROM TO ASTM D 2235.
<br />ACID RESISTANT WASTE AND VENT SHALL BE SCHEDULE 40 PVC.
<br />POLYVINYL CHLORIDE (PVC) PLASTIC PIPE. ALL
<br />PIPE, COUPLINGS AND FITTINGS SHALL BE MANUFACTURED OF
<br />MATERIAL CONFORMING TO ASTM D 1185. PLASTIC SOLVENT CEMENT
<br />FOR PVC PLASTIC PIPE SHALL CONFROM TO ASTM D 2235.
<br />CONDENSATE DRAIN PIPING: TYPE DWV COPPER TUBING AND
<br />FITTINGS OR SCHEDULE 40 GALVANIZED STEEL PIPE AND
<br />MALLEABLE IRON FITTINGS. (PVC PIPING WILL NOT BE
<br />ACCEPTABLE.)
<br />WATER PIPE (HOT AND COLD WATER): TYPE L BELOW GRADE,
<br />TYPE M ABOVE GRADE, COPPER TUBING, HARD -TEMPER, WITH
<br />WROUGHT COPPER FITTINGS. SOLDERING / BRAZING MATERIAL
<br />SHALL BE LEAD FREE, SILVER SOLDER BELOW GRADE, 95-5 OR
<br />SIMILAR ABOVE GRADE. CAPPED OR PLUGGED OUTLETS SHALL BE
<br />SCHEDULE 40 SCREWED BRASS. ELBOWS AT BRANCH OUTLETS
<br />SHALL BE SCREWED OUTLET, WITH EARS, FOR NAILING OR SCREWING
<br />TO WALL BACKING.
<br />GAS PIPING: PIPING SHALL BE BLACK STEEL, STM A-53, WITH
<br />MALEABLE STEEL FITTINGS. PIPE SIZES 3" AND OVER SHALL
<br />HAVE WELDED JOINTSt SIZES 2-1/2" AND SMALLER MAY BE THREADED
<br />OR MELDED, AT CONTRACTOR'S OPTION, EXCEPT THAT ,ALL PIPING
<br />UNDERGROUND SHALL BE WELDED, REGARDLESS OF SIZE.
<br />4. PIPING AND EQUIPMENT ACCESSORIES SHALL BE AS FOLLOWS:
<br />PROVIDE STOPS FOR ALL FIXTURES. STOPS SHALL HAVE
<br />THREADED INLETS, SIMILAR TO SPEEDWAY SR 3112. STOPS WITH
<br />BRAZED (SOLDERED) OR COMPRESSION INLET CONNECTIONS WILL
<br />NOT BE ALLOWED.
<br />PROVIDE ELBOWS AT ALL PIPING PENETRATIONS OF WALLS TO
<br />STOPS. ELBOWS SHALL HAVE NAILING EARS, AND SHALL BE
<br />SECURELY FASTENED TO THE STRUCTURE. NIPPLES THROUGH THE
<br />WALLS SHALL BE IPS WEIGHT THREADED COPPER OR BRASS.
<br />PROVIDE TRAPS FOR ALL FIXTURES. TRAPS FOR SINKS AND LAV$
<br />SHALL BE BRASS, 11 GAGE MINIMUM THICKNESS, WITH INTEGRAL
<br />CLEANOUT
<br />PROVIDE CHROME PLATED ESCUTCHEON PLATES ON ALL PIPES
<br />PASSING THROUGH WALLS OR CEILINGS. ALL EXPOSED PIPING
<br />SHALL BE CHROME PLATED.
<br />PROVIDE PERMANENT CLEVIS TYPE HANGERS FOR ALL PIPING.
<br />WIRE, ROPE, WOOD BLOCKING OR PERFORATED METAL TAPE WILL
<br />NOT BE ACCEPTED. PROVIDE PLASTIC WRAPPING OF PIPE WHERE
<br />DISSIMILAR METALS OCCUR SUCH AS BETWEEN COPPER AND IRON
<br />PIPING AND SUPPORTS.
<br />PROVIDE WRAP ON WASTE, HOT AND COLD WATER PIPING UNDER
<br />ADA ACCESSIBLE PLUMBING FIXTURES. PLUMBEREX
<br />"PRO -EXTREME" ONE-PIECE PROTECTOR WITH FULL ROTATION
<br />OPTION, AND 3-M DUAL LOCK FASTENERS SECURED WITH SELF
<br />LOCKING NYLON STRAPS.
<br />5. CATHODIC PROTECTION:
<br />WRAP ALL COPPER OR STEEL WATER PIPING UNDER FLOOR OR
<br />BELOW GRADE WITH TWO LAYERS OF PABCO-WRAP, OR SIMILAR
<br />MATERIALS, INCLUDING ALL JOINTS. GAS PIPING BELOW GRADE
<br />SHALL BE WRAPPED AS DESCRIBED FOR WATER PIPING, OR, AT
<br />CONTRACTOR'S OPTION, MAY HAVE EXTRU-COAT OR SIMILAR
<br />COVERING. ALL FIELD JOINTS SHALL BE WRAPPED AS FOR BARE
<br />PIPING JOINTS. PLACE EXTRU-COAT GAS PIPING IN A SAND OR
<br />SIEVED EARTH BED, WITH SIMILAR COVERING TO A LEVEL OF 4"
<br />ABOVE TOP OF PIPE.
<br />WRAP WATER, WASTE AND GAS PIPING THROUGH THE FLOOR SLAB
<br />WITH I/2" THICK FIBERGLASS, 2" ABOVE _Ahl=�
<br />SURFACES.
<br />GENERAL PLUMBING NOTES (cont.)
<br />1. INSTALLATION:
<br />INSTALL ALL PIPING IN ACCORDANCE WITH THE UNIFORM PLUMBING
<br />CODE WITH THE STATE OF CALIFORNIA AMENDMENTS. SLOPE ALL
<br />WASTE PIPING AS INDICATED ON THE DRAWINGS, AND ALL WATER
<br />PIPING TO INSURE ELIMINATION OF AIR CAREFULLY GRADE ALL
<br />WASTE PIPING TO ENSURE A UNIFORM SLOPE IS ACHIEVED, WITHOUT
<br />ANY DIPS OR HIGH POINTS IN THE PIPING.
<br />CAREFULLY TRENCH FOR ALL UNDERGROUND PIPING, AVOID OTHER
<br />UTILITIES, AND REPAIR ANY DAMAGES TO SAME CAUSED BY THE
<br />WORK OF THIS CONTRACT. PROVIDE PROPER SHORING FOR ALL
<br />DEEP TRENCHES, AS REQUIRED BY THE SAFETY REGULATIONS OF
<br />THE STATE OF CALIFORNIA, AND BY OSHA. PROVIDE ALL REQUIRED
<br />BARRICADES, WARNING SIGNS, ETC. CAP ALL PIPING ENDS AT THE
<br />CLOSE OF THE DAY'S WORK TO PREVENT ENTRY OF FOREIGN
<br />MATERIALS. FLUSH PIPING OF ALL DEBRIS BEFORE CONNECTING TO
<br />FIXTURES.
<br />EMBED ALL UNDERGROUND PIPING, OTHER THAN GAS PIPING, IN
<br />SIEVED EARTH FOR A DEPTH OF 4" ABOVE THE PIPE. SMOOTH THE
<br />TRENCHING BELOW THE PIPING FREE FROM ANY ROCKS OR SIMILAR
<br />OBSTRUCTIONS, AND PROVIDE SPACE FOR BELLS OR MECHANICAL
<br />JOINTS FOR ALL WASTE PIPING. LATERALLY BRACE PIPING TO
<br />PREVENT PIPE MOTION DURING BACK FILLING OPERATIONS.
<br />PROVIDE SHOCK ABSORBERS AT HOT AND COLD WATER AT ALL
<br />FIXTURES. ABSORBER SHALL BE A LINE SIZE PIPE RISER
<br />CONNECTING TO A 12" HIGH CAPPED PIPE CHAMBER SIZED ONE
<br />SIZE LARGER THAN THE RISER A SINGLE MECHANICAL SHOCK
<br />ABSORBER MAY BE UTILIZED FOR A BATTERY OF FIXTURES,
<br />PROVIDED THE ABSORBER IS SIZED FOR THE MAIN LINE SERVING
<br />THE BATTERY OF FIXTURES.
<br />CHLORINATE ALL WATER PIPING FOR A PERIOD OF 8 HOURS, BY
<br />CHARGING WITH A CHLORINE OR HYPO CHLORITE SOLUTION TO
<br />ACHIEVE A 5 PPM STRENGTH AT THE FIXTURE FURTHEST FROM THE
<br />POINT OF APPLICATION. UPON COMPLETION OF CHLORINATION,
<br />FLUSH ALL PIPING UNTIL NO CHLORINE CAN BE DETECTED BY
<br />TASTE.
<br />AFTER CHLORINATION AND ALL TESTING HAS BEEN COMPLETED,
<br />CLEAN ALL FIXTURE STRAINERS, AND SET WATER FLOWS FROM
<br />FIXTURES IN ACCORDANCE WITH THE REQUIREMENTS OF T24, CCR
<br />8, TESTS:
<br />TEST ALL GAS PIPING FOR A PERIOD NOT LESS THAN TWO HOURS
<br />AT A PRESSURE OF NOT LESS THAN 10 PSIG, USING SOAP AND
<br />WATER OR SIMILAR MATERIALS AT ALL JOINTS. WELDED GAS PIPING
<br />SHALL BE TESTED PER UPC/GPC.
<br />TEST ALL WASTE AND VENT PIPING FOR A PERIOD OF NOT LESS
<br />THAN 8 HOURS BY CAPPING OR PLUGGING ALL JOINTS TO A LEVEL
<br />OF THE HIGHEST FIXTURE OR FITTING, FILLING THE SYSTEM WITH
<br />WATER AND OBSERVING FOR LEAKS, TEST UNDERGROUND SECTION
<br />OF PIPE WITH A RISER TO ACHIEVE THE PRESSURE EQUIVALENT TO
<br />THE HIGHEST FIXTURE OR FITTING.
<br />TEST WATER PIPING AT 100 PSIG FOR A PERIOD OF EIGHT HOURS,
<br />OBSERVING FOR ANY VISIBLE LEAKS. TEST PIPING AGAIN WITH
<br />FIXTURES INSTALLED AT 60 PSIG.
<br />REPAIR ANY LEAKS FOUND BY REMAKING THE JOINT. DO NOT USE
<br />CAULKING OR SIMILAR METHODS TO CORRECT LEAKS. UPON
<br />REPAIRING ANY LEAKS FOUND, AGAIN TEST THAT PORTION OF THE
<br />SYSTEM AS DESCRIBED ABOVE.
<br />g. PROVIDE SIX COPIES OF SUBMITTALS WITH MFR'S OPERATING AND
<br />MAINTENANCE DATA FOR ALL ITEMS OF EQUIPMENT INSTALLED.
<br />INDICATE THE EXACT MODEL($) OF EQUIPMENT, WHERE THE
<br />MANUFACTURER'S DATA INCLUDES MODELS OTHER THAN THOSE
<br />INSTALLED. BIND THE INFORMATION IN 3 RING BINDERS, WITH
<br />DIFFERENT TYPES OF EQUIPMENT INDEXED. PROVIDE A SHEET
<br />INDICATING THE CONTRACTOR'S (AND SUBCONTRACTOR'S) NAMES,
<br />ADDRESSES AND TELEPHONE NUMBERS. INCLUDE ALSO THE
<br />PREFERRED SOURCE$ OF SPARE PARTS FOR THE EQUIPMENT
<br />INSTALLED, INCLUDING ADDRESSES, TELEPHONE NUMBERS, ETC.
<br />10, CONTRACTOR SHALL VERIFY ALL WORK CONDITIONS, PRIOR TO
<br />COMMENCING WORK, INCLUDING, BUT NOT LIMITED TO: PIPING SIZES,
<br />INVERT ELEVATIONS, POINTS OF CONNECTION, FIXTURES AND
<br />EQUIPMENT, STRUCTURAL ELEMENTS AND MATERIALS INDICATED AS
<br />EXISTING, AS WELL AS THE COORDINATED INSTALLATION OF ALL
<br />NEW WORK MATERIALS, EQUIPMENT, ETC. VERIFY THE LOCATION AND
<br />REQUIRED PIPING CONNECTIONS OF ALL HVAC OR OTHER
<br />MECHANICAL EQUIPMENT. NOTIFY ARCHITECT OF ANY
<br />DISCREPANCIES PRIOR TO TRENCHING OR COMMENCING OTHER
<br />WORK.
<br />11. ROUTE CONDENSATE PIPING FROM EQUIPMENT TO NEAREST
<br />APPROVED RECEPTOR ALL CONDENSATE SYSTEMS SHALL
<br />TERMINATE INTO THE STORM DRAINAGE SYSTEM, UNLESS NOTED
<br />OTHERWISE, AND SHALL OTHERWISE BE INSTALLED IN ACCORDANCE
<br />WITH ALL APPLICABLE LOCAL AND STATE CODES. CONNECT TO
<br />EQUIPMENT COMPLETE WITH VENTED P -TRAP.
<br />12. MECHANICAL EQUIPMENT AND IDENTIFICATION TAGS SHOWN ON
<br />DRAWING ARE FOR THE COORDINATION OF UTILITIES ONLY, REFER
<br />TO MECHANICAL DRAWINGS FOR EQUIPMENT SPECIFICATIONS.
<br />WATER PIPE SIZING CHART
<br />PIPE SUES CALCULATED BASED ON UPC/CPC APPENDD( A
<br />1/2"
<br />0.545
<br />2.4
<br />3.3
<br />2
<br />0
<br />2.4 3.3
<br />2
<br />314"
<br />0.785
<br />6.3
<br />4.2
<br />7
<br />0
<br />6.3 4.2
<br />7
<br />1""
<br />1.025
<br />12.8
<br />5.0
<br />16
<br />0
<br />12.8 5.0
<br />16
<br />1-114"
<br />1.265
<br />22.2
<br />5.7
<br />34
<br />5
<br />19.6 5.0
<br />28
<br />1-V2"
<br />1.505
<br />35.0
<br />6.3
<br />66
<br />20
<br />27.7 5.0
<br />46
<br />Z.
<br />1.985
<br />72.5
<br />7.5
<br />236
<br />116
<br />48.2 5.0
<br />119
<br />PLUMBING SCHEDULE
<br />SYMBOL
<br />DESCRIPTION
<br />PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL FIXTURES IN THIS
<br />SCHEDULE OR THEIR APPROVED EQUIVALENT. REFER TO
<br />F-
<br />ARCHITECTURAL DRAWINGS FOR ALL MOUNTING HEIGHTS OF FIXTURES.
<br />WC -1
<br />ACCESSIBLE WATER CLOSET: KOHLER "K-4405 "HIGHLINE" FLUSH
<br />VALVE TYPE, 11/81/2" TOP SPUD, FLOOR MOUNTED, 10" ROUGH/81N, WHITE
<br />VITREOUS CHINA, ELONGATED BOWL, DIRECTS/&FED SIPHON JET ACTION,
<br />128 GFF, RIM 111/81/2" AFF. UNIT COMPLETE WITH KOHLER "K -46101/8C
<br />OPEN FRONT SEAT LESS COVER, MATCHING BOLT CAPS, SLOAN
<br />W
<br />"ROYAL" "III -128 CHROME PLATED FLUSH VALVE, TRIP LEVER LOCATED
<br />ON OPEN SIDE OF FIXTURE. UNIT SHALL CONFORM TO STATE ACCESS
<br />�
<br />REGULATIONS AND TITLE 24 REQUIREMENTS FOR ACCESSIBLE
<br />INSTALLATIONS.
<br />LAVATORY: KOHLER -2005 "KIN STOW WA HU VI%MODEL HIN ,
<br />W
<br />-
<br />F CHICAGO CHROME PLAT D FAUC2
<br />40
<br />Q-Al2A-43A"T,
<br />�Na
<br />T C X T
<br />(0.5 GPM FLOW), AND METAL GRID DRAIN ASSEMBLY. INSULATE WATER
<br />AND WASTE PIPING. UNIT SHALL CONFORM TO STATE ACCESS
<br />REGULATIONS AND TITLE 24 REQUIREMENTS FOR ACCESSIBLE
<br />INSTALLATIONS.
<br />2" FD
<br />FLOOR DRAIN: JR. SMITH " 2005(A), 5" DIAMETER NICKEL BRONZE TOP
<br />WITH 2" PIPE, FLANGE AND SEEPAGE PAN. PROVIDE TRAP PRIMER
<br />CONNECTION.
<br />3" FS
<br />FLOOR SINK: JR5 PRODUCTS 0325-YO3 WITH CAST IRON BODY,
<br />ENAMELED INTERIOR, 6" DEEP SUMP, FLANGE AND SEEPAGE PAN,
<br />ALUMINUM BOTTOM DOME STRAINER, HALF GRATE, 3" OUTLET, CAULK
<br />JOINT.
<br />BFP
<br />WATTS SD3-MF 3/8" ASSE 1022 BACKFLOW PREVENTER FOR CARBONATE
<br />BEVERAGE MACHINES, COFFEE MACHINE, TEA BREWER AND ESPRESSO
<br />MACHINE. DRAIN TO FLOOR SINK.
<br />MS
<br />MOP SINK: FLORESTONE MODEL 'MSR -2424 FLOOR MOUNTED, 3" OUTLET
<br />WITH AMERICAN STANDARD "8344.012 FAUCET WITH TOP BRACE, STOPS
<br />AND VACUUM BREAKER, AND AMERICAN STANDARD 01121.038 DRAIN
<br />WITH STRAINER
<br />eWATER
<br />HEATER: BRADFORD WHITE "EF -60T -125-3N, GAS FIRED, 125,000
<br />i
<br />BTUH INPUT, 60 GALLON STORAGE CAPACITY, 188 GFH RECOVERY AT
<br />60 F RISE. GLASS LINED STORAGE TANK, MAGNESIUM ANODE,
<br />INSULATED AND JACKETED, CAST IRON BURNER, PRESSURE AND
<br />TEMPERATURE RELIEF VALVE. INSTALL WITH EXPANSION TANK, AMTROL
<br />"ST -5 "THERM-X-TROL", DIAPHRAGM TYPE, PREPRESSURIZED TANK
<br />WATER AND WASTE SERVICE CALCULATIONS
<br />JOB NAME: TAQUERIA LA ESTRELLA DATE: 01/14/20
<br />FIXTURE TYPE
<br />NO.
<br />WASTE
<br />COLD WATER
<br />HOT WATER
<br />TOTAL
<br />WATER
<br />FU
<br />TOTAL
<br />FU
<br />TOTAL
<br />FU
<br />TOTAL
<br />FU
<br />3 -COMPARTMENT SINK
<br />1
<br />3
<br />3
<br />1.125
<br />1.125
<br />1.125
<br />1.126
<br />1.5
<br />LAVATORY
<br />1
<br />1
<br />1
<br />0.75
<br />0.76
<br />0.75
<br />0.75
<br />1
<br />MOP SINK
<br />1
<br />3
<br />3
<br />2.26
<br />2.26
<br />2.25
<br />2.25
<br />3
<br />HAND SINK
<br />2
<br />2
<br />4
<br />1.5
<br />3
<br />1.5
<br />3
<br />4
<br />PREP SINK
<br />1
<br />3
<br />3
<br />1.6
<br />1.6
<br />1.5
<br />1.6
<br />2
<br />WATER CLOSET, 1.28 FV
<br />2
<br />4
<br />8
<br />6
<br />10
<br />0
<br />0
<br />10
<br />MISC EQUIP (ICE, SODA, COFFI
<br />2
<br />1
<br />2
<br />1
<br />2
<br />0
<br />0
<br />2
<br />FUTURE RESTAURANT (SMALL
<br />0
<br />30
<br />0
<br />30
<br />0
<br />0
<br />0
<br />0
<br />FUTURE RESTAURANT (LARGE
<br />0
<br />60
<br />0
<br />60
<br />0
<br />0
<br />0
<br />1 0
<br />TOTAL FU
<br />1
<br />24.0
<br />20.6
<br />8.6
<br />1 23.6
<br />EQUIVALENT COLD WATER FLOW RATE (GPM): 37 GPM
<br />ADDITIONAL DEMAND LOAD (GPM) 0 0 GPM
<br />PRESSURE AVAILABLE AT STREET MAIN (PSI): 40 PSI
<br />MINIMUM REQUIRED FIXTURE PRESSURE (PSQ: 8 PSI
<br />1 6 IFT 3 PSI
<br />ELEVATION RISE (FT):
<br />METER LOSS (PSI): 3 PSI
<br />BACKFLOW PREVENTER LOSS (PSI): 10 PSI
<br />ADDITIONAL LOSSES (PSI): 0 PSI
<br />EQUIVALENT PIPE LENGTH FROM METER TO MOST REMOTE FIXTURE (FT 300 FT
<br />FRICTION LOSS PRESSURE AVAILABLE (PSI): 16.40
<br />MAXIMUM ALLOWABLE FRICTION LOSS (PSI/100 FT): 5.47
<br />WATER FLOWVELOCITY (FPS): 3.79
<br />CALCULATED FRICTION HEAD LOSS (PS111100 FT): 1.54
<br />MINIMUM REQUIRED 'WATER' PIPE SIZE (INCHES): 2
<br />MINIMUM REQUIRED 'WASTE' PIPE SIZE (INCHES): 3
<br />(CALCULATIONS PER THE UPCICPC)
<br />Q DESCRIPTION DATE
<br />D
<br />©BLDG DEPARTMIE
<br />0
<br />A
<br />STAMP
<br />�NPRC ' S •c •.��c
<br />Na.958
<br />Sp'• .,CIVIL, . ��P
<br />Date Signed: January 15, 2020
<br />Q
<br />W
<br />F-
<br />M
<br />W-�Q
<br />W
<br />V
<br />Z
<br />Q
<br />�
<br />apV
<br />00I
<br />W
<br />-
<br />W
<br />40
<br />Z
<br />�Na
<br />cy
<br />m
<br />SHEET TITLE
<br />ILUMBING LEGENI
<br />AND SCHEDULES
<br />DATE OCTOBER 8, 2019
<br />DRAWN BY EH
<br />CHECKED BY BC
<br />SCALE: as noted
<br />SHEET
<br />il
<br />
|