Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST (continued) <br /> Test Method Developed by ❑ Manufacturer D Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum 0 Hydrostatic <br /> Test Equipment Used: Incon Tester <br /> Sump/UDC ID UDC 9/10 UDC 11/12 UDC 13/14 UDC 15/16 <br /> Sump Manufacturer Bravo Bravo Bravo Bravo <br /> Sump Depth (inches) 31" 31" 31" 31" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 16" 16" 16" 16" <br /> (inches) <br /> Test Start Time 2:43 pm 2:43 pm 2:43 pm 2:43 pm <br /> Initial Reading 2.5817 4.3980 3.7858 3.7192 <br /> Test End Time 2:59 pm 2:59 pm 2:59 pm 2:59 pm <br /> Final Reading 2.5814 4.3977 3.7860 3.7188 <br /> Change in Reading 0.0003 0.0003 0.0002 0.0004 <br /> Pass/Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results 0 Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail <br /> Sump/UDC ID UDC 17/18 UDC 19/20 <br /> Sump Manufacturer Bravo Bravo <br /> Sump Depth (inches) 31" 31" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 16" 16" <br /> (inches) <br /> Test Start Time 11:38 am 11:38 am <br /> Initial Reading 6.6369 3.2834 <br /> Test End Time 11:53 am 11:53 am <br /> Final Reading 6.6366 3.2831 <br /> Change in Reading 0.0003 0.0003 <br /> Pass/Fail Criteria 0.002 0.002 <br /> Tightness Test Results 0 Pass ❑ Fail 0 Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />