Laserfiche WebLink
f <br /> Underground Storage Tank <br /> i <br /> Secondary Containment Testing Report Form <br /> 6. TANK SECONDARY.CONTAINMENT TEST <br /> Test Method Developed by ❑ Manufacturer ® Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ® Vacuum ❑ Hydrostatic <br /> Test Equipment Used: <br /> Tank ID 87-1 87-2 91 <br /> Tank Manufacturer <br /> Tank Capacity <br /> Test Start Time 8:25 8:41 8:41 <br /> Initial Reading 10"hg 10"hg 10"hg <br /> Test End Time 9:25 9:41 9:41 <br /> Final Reading 10"hg 10"hg 10"hg <br /> Change in Reading 0 0 0 <br /> Pass/Fail Criteria 0 0 0 <br /> Tightness Test Results ® Pass ❑ Fall ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail <br /> 7, PIPE"SECONDARY CONTAINMENT TEST <br /> Test Method Developed by ❑ Manufacturer ® Industry Standard ❑ Professional Engineer <br /> Test Type ® Pressure ❑ Vacuum ❑ Hydrostatic <br /> Test Equipment Used: <br /> Pipe Run ID 87-1 87-2 91 <br /> Pipe Manufacturer Smith Smith Smith <br /> Test Start Time 8:30 8:30 8:30 <br /> Initial Reading 5 5 5 <br /> Test End Time 9:30 9:30 9:30 <br /> Final Reading 5 5 5 <br /> Change in Reading 0 0 0 <br /> Pass/Fail Criteria 0 0 0 <br /> Tightness Test Results 1 ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail <br /> Pipe Run ID <br /> Pipe Manufacturer <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass/Fail Criteria <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail I ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked"Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 2 of 5 <br />