Laserfiche WebLink
i <br /> Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> f <br /> 8. SUMPIUDC TEST (continued) . <br /> Test Method Developed by ❑ Manufacturer ® Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: <br /> Sump1UDC ID UDC 112 UDC 314 UDC 516 UDC 718 <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 1:11 1:11 12:11 12:11 <br /> Initial Reading 3.0473 4.2790 1.8003 4.0446 <br /> Test End Time 1:26 1:26 12:26 12:26 <br /> Final Reading 3.0473 4.2787 1.7992 4.0433 <br /> Change in Reading 0.0000 0.0003 0.0011 0.0013 <br /> ass Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID UDC 9110 UDC 11112 <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 12:11 12:11 <br /> Initial Reading 2.6814 2.8252 <br /> Test End Time 12:26 12:26 <br /> Final Reading 2.6794 2.8250 <br /> Change in Reading 0.0020 0.0002 <br /> Pass/Fail Criteria 0.002 0.002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked"Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4of5 <br />