Laserfiche WebLink
I <br /> Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST (continued) <br /> Test Method Developed by ❑ Manufacturer ® Industry Standard ❑ Professional Engineer <br /> i <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: <br /> Sump1UDC ID UDC 314 UDC 516 UDC 718 UDC 9110 <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 1:38 1:01 2:41 1:51 <br /> Initial Reading 1.2881 2.7414 1.8810 3.4673 <br /> Test End Time 1:53 1:16 2:56 2:06 <br /> Final Reading 1.2880 2.7412 1.8809 3.4682 <br /> Change in Reading 0.00015 0.00021 0.00012 0.00096 <br /> Pass/Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID UDC 11112 <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 1:01 <br /> Initial Reading 3.4557 <br /> Test End Time 1:16 <br /> Final Reading 3.4554 <br /> Change in Reading 0.00033 <br /> Pass/Fail Criteria 0.002 <br /> Tightness Test Results ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ® Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />