METAL SUSPENSION SYSTEMS FOR LAY -IN
<br />PANEL CEILINGS
<br />1. 12 GA. (MIN.) HANGER WIRES MAY BE USED
<br />FOR UP TO AND INCLUDING 4'-0' X 4'-0' GRID
<br />SPACING ALONG MAIN RUNNERS. SPLICES
<br />WILL NOT BE PERMITTED IN ANY HANGER
<br />WIRES UNLESS SPECIFICALLY APPROVED BY
<br />DSA/SSS.
<br />2. PROVIDE 12 GA. HANGER WIRES AT THE ENDS
<br />OF ALL MAIN AND CROSS RUNNERS WITHIN 8"
<br />FROM THE SUPPORT OR WITHIN 1 /4" OF THE
<br />LENGTH OF THE END TEE, WHICHEVER IS LEAST,
<br />FOR THE PERIMETER OF THE CEILING AREA.
<br />3. PROVIDE TRAPEZE OR OTHER SUPPLEMENTARY
<br />SUPPORT MEMBER AT OBSTRUCTIONS TO MAIN
<br />HANGER SPACING. PROVIDE ADDITIONAL
<br />HANGERS, STRUTS OR BRACES AS REQUIRED
<br />AT ALL CEILING BREAKS, SOFFITS, OR
<br />DISCONTINUOUS AREAS. HANGER WIRES THAT
<br />ARE MORE THAN I IN 6 OUT OF PLUMB TO
<br />HAVE COUNTER -SLOPING WIRES.
<br />4. CEILING GRID MEMBERS MAY BE ATTACHED
<br />TO NOT MORE THAN 2 ADJACENT WALLS.
<br />CEILING GRID MEMBERS SHOULD BE AT LEAST
<br />3/4" INCH FREE OF OTHER WALLS. IF WALLS
<br />RUN DIAGONALLY TO CEILING GRID SYSTEM
<br />RUNNERS, ONE END OF MAIN AND CROSS
<br />RUNNER SHOULD BE FREE AND A MINIMUM OF
<br />I/2" CLEAR OF THE WALL.
<br />5. AT THE PERIMETER OF THE CEILING AREA
<br />WHERE MAIN OR CROSS RUNNERS ARE NOT
<br />CONNECTED TO THE ADJACENT WALL,
<br />PROVIDE INTERCONNECTION BETWEEN
<br />RUNNERS AT THE FREE END TO PREVENT
<br />LATERAL SPREADING. A METAL STRUT OR A 16
<br />GA. WIRE WITH POSITIVE MECHANICAL
<br />CONNECTION TO THE RUNNER MAY BE USED.
<br />WHERE THE PERPENDICULAR DISTANCE FROM
<br />THE WALL TO THE FIRST PARALLEL RUNNER IS
<br />17' OR LESS, THIS INTERLOCK IS NOT REQUIRED.
<br />6. PROVIDE SETS OF FOUR 12 GA. SPLAYED
<br />BRACING WIRES ORIENTED 900 FROM EACH
<br />OTHER AT NOT MORE THAN 12'-0" X 12'-0' ON
<br />CENTER.
<br />PROVIDE BRACING WIRES AT LOCATIONS
<br />NOT MORE THAN 6'-0' FROM EACH PERIMETER
<br />WALL AND AT THE EDGE OF VERTICAL
<br />OFFSETS.
<br />THE SLOPE OF THESE WIRES SHOULD NOT
<br />EXCEED 450 FROM THE PLANE OF THE CEILING
<br />AND SHOULD BE TAUT WITHOUT CAUSING THE
<br />CEILING TO LIFT. SPLICES IN BRACING WIRES
<br />ARE NOT TO BE PERMITTED WITHOUT SPECIAL
<br />DSA/SSS APPROVAL.
<br />7. FASTEN HANGER WIRES WITH NOT LESS THAN 3
<br />TIGHT TURNS, FASTEN BRACING WIRES WITH 4
<br />TIGHT TURNS, MAKE ALL TIGHT TURNS WITHIN A
<br />DISTANCE OF 1 1 /2'. HANGER OR BRACING
<br />WIRE ANCHORS TO THE STRUCTURE SHOULD
<br />BE INSTALLED IN SUCH A MANNER THAT THE
<br />DIRECTION OF THE WIRE ALIGNS AS CLOSELY
<br />AS POSSIBLE WITH THE DIRECTION OF THE
<br />FORCES ACTING ON THE WIRE.
<br />NOTE: WIRE TURNS MADE BY MACHINE WHERE
<br />BOTH STRANDS HAVE BEEN DEFORMED OR
<br />BENT IN WRAPPING CAN WAIVE THE 1 1/2'
<br />REQUIREMENT, BUT THE NUMBER OF TURNS
<br />SHOULD BE MAINTAINED, AND BE AS TIGHT
<br />AS POSSIBLE.
<br />8. SEPARATE ALL CEILING HANGING AND
<br />BRACING WIRES AT LEAST 6 INCHES FROM ALL
<br />UNBRACED DUCTS, PIPES, CONDUIT, ETC.
<br />HVAC DUCTWORK, ELECTRICAL DISTRIBUTION,
<br />TELEPHONE SERVICES, COMPUTER CABLE
<br />DISTRIBUTION, AND OTHER SERVICES
<br />NORMALLY FOUND IN A CEILING SPACE,
<br />SHALL BE INDEPENDENTLY SUPPORTED AND
<br />APPROPRIATELY BRACED TO ELIMINATE ANY
<br />LATERAL FORCE ON THE CEILING MEMBRANE
<br />OR BRACING ELEMENTS.
<br />9. WHEN DRILL -IN CONCRETE ANCHORS OR
<br />SHOT -IN ANCHORS ARE USED IN REINFORCED
<br />CONCRETE FOR HANGER WIRES, 1 OUT OF 10
<br />MUST BE FIELD TESTED FOR 200 LBS. OF
<br />TENSION. WHEN DRILLED -IN CONCRETE
<br />ANCHORS ARE USED FOR BRACING WIRES, I
<br />OUT OF 2 MUST BE FIELD TESTED FOR 440 LBS.
<br />OF TENSION. SHOT -IN ANCHORS IN
<br />CONCRETE ARE NOT PERMITTED FOR
<br />BRACING WIRES. IF ANY SHOT -IN OR
<br />DRILLED -IN ANCHOR FAILS, ALL ADJACENT
<br />ANCHORS MUST BE TESTED. DRILLED -IN OR
<br />SHOT -IN ANCHORS MUST BE TESTED.
<br />DRILLED -IN OR SHOT -IN ANCHORS REQUIRE
<br />SPECIAL DSA/SSS APPROVAL WHEN USED IN
<br />PRE -STRESSED CONCRETE.
<br />10. ATTACH ALL LIGHT FIXTURES TO THE CEILING
<br />GRID RUNNERS TO RESIST A HORIZONTAL
<br />FORCE EQUAL TO THE WEIGHT OF THE
<br />FIXTURES.
<br />ALL RECESSED LIGHTING FIXTURES HAVING A
<br />NOMINAL END DIMENSION OF 24" OR
<br />GREATER, SHALL BE POSITIVELY ATTACHED TO
<br />THE CEILING GRID RUNNER(S) AT THE END OF
<br />THE FIXTURE WITH TWO #8 SELF TAPPING TEK
<br />SCREWS, EACH SCREW SHALL BE LOCATED
<br />WITHIN W OF THE SIDE OF FIXTURE AND
<br />ATTACHED THROUGH THE BULB OF THE CEILING
<br />GRID RUNNER(S). LIGHT FIXTURES HAVING LESS
<br />THAN A NOMINAL 24" END DIMENSION SHALL
<br />BE ATTACHED WITH ONE #8 SELF TAPPING
<br />TEK SCREW AT THE CENTER OF EACH END OF
<br />THE FIXTURE, ATTACHED TO THE BULB OF THE
<br />CEILING GRID RUNNER{S). ALL ATTACHMENTS
<br />SHALL BE CAPABLE OF LATERALLY SUPPORTING
<br />THE WEIGHT OF THE FIXTURE. ALL FIXTURES
<br />REGARDLESS OF WEIGHT OR SIZE SHALL HAVE
<br />INTERLOCKING CEILING GRID RUNNER(S) ON
<br />ALL 4 SIDES OF THE FIXTURE.
<br />11. CEILING MOUNTED AIR TERMINALS OR
<br />SERVICES SHALL BE POSITIVELY ATTACHED TO
<br />THE CEILING SUSPENSION MAIN RUNNERS OR
<br />TO CROSS RUNNERS WITH THE SAME
<br />CARRYING CAPACITY AS THE MAIN RUNNER.
<br />AIR TERMINALS WITH A NOMINAL DIMENSION
<br />OF 24" OR LESS SHALL BE POSITIVELY
<br />ATTACHED TO THE CEILING GRID RUNNERS)
<br />ON AT LEAST TWO OPPOSING SIDES WITH ONE
<br />SELF -TAPPING TEK SCREW ON EACH SIDE. EACH
<br />SCREW SHALL BE LOCATED IN THE CENTER OF
<br />THE AIR TERMINAL AND SHALL BE ATTACHED
<br />THROUGH THE BULB OF THE CEILING GRID
<br />RUNNER(S). AIR TERMINALS IN EXCESS OF 24" IN
<br />LENGTH SHALL BE ATTACHED WITH TWO #8
<br />SELF -TAPPING TEK SCREWS ON EACH END OF
<br />DIFFUSER ATTACHED TO THE BULB OF THE
<br />CEILING GRID RUNNER(S). ALL ATTACHMENTS
<br />SHALL BE CAPABLE OF LATERALLY SUPPORTING
<br />THE WEIGHT OF THE AIR TERMINAL. ALL AIR
<br />TERMINALS REGARDLESS OF WEIGHT OR SIZE
<br />SHALL HAVE INTERLOCKING GRID RUNNER(S)
<br />OF ALL 4 SIDES OF THE AIR TERMINAL.
<br />O
<br />9
<br />z
<br />Q
<br />12. FLUSH OR RECESSED LIGHT FIXTURES AND AIR
<br />TERMINALS OR SERVICE'S WEIGHING LESS THAN
<br />56 LBS. MAY BE SUPPORTED DIRECTLY ON THE
<br />RUNNERS OF A HEAVY DUTY GRID SYSTEM BUT,
<br />IN ADDITION, THEY MUST HAVE A MINIMUM OF
<br />TWO 12 GA. SLACK SAFETY WIRES ATTACHED
<br />TO THE FIXTURE AT DIAGONAL CORNERS AND
<br />ANCHORED TO THE STRUCTURE ABOVE. ALL
<br />4-a' X f-9' LIGHT FIXTURES MUST HAVE SLACK
<br />SAFETY WIRES AT EACH CORNER. ALL FLUSH OR
<br />RECESSED LIGHT FIXTURES AND AIR TERMINALS
<br />OR SERVICES WEIGHING 56 LBS. OR MORE
<br />MUST BE INDEPENDENTLY SUPPORTED BY NOT
<br />LESS THAN 4 TAUT 12 GA. WIRES EACH
<br />ATTACHED TO THE FIXTURE AND TO THE
<br />STRUCTURE ABOVE REGARDLESS OF THE TYPE
<br />OF CEILING GRID SYSTEM USED.
<br />THE 4 TAUT 12 GA. WIRES INCLUDING THEIR
<br />ATTACHMENT TO THE STRUCTURE ABOVE MUST
<br />BE CAPABLE OF SUPPORTING 4 TIMES THE
<br />WEIGHT OF THE UNIT.
<br />13. ALL FIXTURES AND AIR TERMINALS OR SERVICES
<br />SUPPORTED ON INTERMEDIATE DUTY GRID
<br />SYSTEMS MUST BE INDEPENDENTLY SUPPORTED
<br />BY NOT LESS THAN 4TAUT 12 GA. WIRES EACH
<br />ATTACHED TO THE FIXTURE OR TERMINAL AND
<br />TO THE STRUCTURE ABOVE.
<br />14. SUPPORT SURFACE MOUNTED LIGHT FIXTURES
<br />BY AT LEAST TWO POSITIVE DEVICES WHICH
<br />SURROUND THE CEILING RUNNER AND WHICH
<br />ARE EACH SUPPORTED FROM THE STRUCTURE
<br />ABOVE BY A 12 GA. WIRE. SPRING CUPS OR
<br />CLAMPS THAT CONNECT ONLY TO THE RUNNER
<br />ARE NOT ACCEPTABLE.
<br />PROVIDE ADDITIONAL SUPPORTS WHEN LIGHT
<br />FIXTURES ARE 8 FEET OR LONGER.
<br />15. SUPPORT PENDANT MOUNTED LIGHT FIXTURES
<br />DIRECTLY FROM THE STRUCTURE ABOVE WITH 9
<br />GA. HANGER WIRES OR CABLES PASSING
<br />THROUGH EACH PENDANT HANGER AND
<br />CAPABLE OF SUPPORTING 4 TIMES THE WEIGHT
<br />OF THE FIXTURE. SPECIAL DETAILS ARE
<br />NECESSARY FOR THIS CONDITION AT THE
<br />CEILING GRID.
<br />16. CEILING AREAS EXCEEDING 1,000 S.F. SHALL
<br />HAVE HORIZONTAL RESTRAINT OF THE CEILING
<br />TO THE STRUCTURAL SYSTEM.
<br />17. POSITIVE BRACING TO THE STRUCTURE SHALL BE
<br />PROVIDED AT CHANGES IN THE CEILING PLANE
<br />ELEVATION OR AT DISCONTINUITIES IN THE
<br />CEILING GRID SYSTEM.
<br />18. ALL SPRINKLER HEADS (DROPS), AND ALL
<br />OTHER PENETRATIONS SHALL HAVE 7OVERSIZE
<br />TRIM TO ALLOW 1"HORIZONTAL MOVEMENT IN
<br />ALL HORIZONTAL DIRECTIONS.
<br />19. WHEN A CEILING SYSTEM SPAN BETWEEN
<br />PERIMETER WALLS IS GREATER THAN 251N BOTH
<br />DIRECTIONS, A MINIMUM WALL ANGLE SIZE OF
<br />AT LEAST A TWO INCH (52MM) HORIZ. LEG
<br />SHALL BE USED AT THE PERIMETER WALLS AND
<br />INTERIOR FULL HEIGHT PARTITIONS. THE FIRST
<br />CEILING TILE SHALL MAINTAIN 3 INCH (19MM)
<br />CLEAR FROM THE FINISH WALL SURFACE
<br />20. WHEN THE DISTANCE BETWEEN THE CEILING
<br />SUSPENSION SYSTEM AND THE STRUCTURAL
<br />DECK ABOVE EXCEEDS 4 FEET, THE CEILING
<br />SYSTEM SHALL BE CONNECTED AND BRACED
<br />DIRECTLY TO THE STRUCTURE AT THE MEANS OF
<br />EGRESS SERVING AN OCCUPANT LOAD OF 30
<br />OR MORE AND AT LOBBIES ACCESSORY TO
<br />GROUP 'WOCCUPANCIES. SPACING OF
<br />VERTICAL HANGERS SHALL NOT EXCEED 2 FEET
<br />(61 OMM) ON CENTER ALONG THE ENTIRE
<br />LENGTH OF THE MEANS OF EGRESS OR LOBBY.
<br />21. WITHIN A, E, AND M -OCCUPANCIES, AND
<br />FIRE -RATED CORRIDORS, ALL LAY4N PANELS
<br />SHALL BE SECURED TO THE SUSPENSION SYSTEM
<br />WITH TWO HOLD-DOWN CLIPS MINIMUM FOR
<br />EACH TILE WITHIN A 4 FOOT RADIUS OF THE EXIT
<br />LIGHTS AND EXIT SIGNS.
<br />22. INDEPENDENT SUPPORTS AND BRACES SHALL
<br />BE PROVIDED FOR LIGHT FIXTURES FOR EXIT
<br />ILLUMINATION. POWER SUPPLY FOR EXIT
<br />ILLUMINATION SHALL COMPLY WITH THE
<br />REQUIREMENTS OF SECTION 1008 OF THE 2016
<br />CBC
<br />23. SEPARATE SUPPORT FROM THE STRUCTURE
<br />SHALL BE PROVIDED FOR ALL APPENDAGES
<br />SUCH AS LIGHT FIXTURES, AIR DIFFUSERS, EXIT
<br />SIGNS AND SIMILAR ELEMENTS.
<br />24. CLASSIFICATION OF CEILING GRID IS HEAVY
<br />DUTY. COMPONENTS SHALL COMPLY WITH THE
<br />FOLLOWING SCHEDULE:
<br />MANUFACTURER: RUNNER RUNNER
<br />ARMSTRONG 7301 7341 (1)
<br />CHICAGO METALLIC 200 1204 (2)
<br />DONN CORP. DX26 DX424 (3)
<br />FOOTNOTES:
<br />(1) FOR 2 X 2 GRID USE 7328
<br />(2) FOR 2 X 2 GRID USE 1226
<br />(3) FOR 2 X 2 GRID USE DX216
<br />25, ANCHORS FOR WALL ANGLES:
<br />A. AT METAL STUD WALL 1 1 /8" TYPE'S" BUGLE
<br />HEAD DRYWALL SCREW AT 16" O.C.
<br />26. MAIN BEAMS AND CROSS TEE INTERSECTIONS
<br />AND SPLICES MUST HAVE CONNECTION
<br />STRENGTHS OF AT LEAST 180 POUNDS IN
<br />COMPRESSION AND TENSIONS.
<br />27. CEILINGS EXCEEDING 2,500 SQ FT SHALL HAVE
<br />A SEISMIC SEPARATION OR A FULL HEIGHT
<br />PARTITION THAT BREAKS THE CEILING UP TO
<br />AREA NOT EXCEEDING 2,500 SQ FT.
<br />INSTALL BOLT TO SECURE ONE —
<br />TUBE TO THE OTHER. TUBES SHALL
<br />LAP ONE ANOTHER AT LEAST 4" IN
<br />A FULLY EXTENDED POSITION.
<br />PIPE SLEEVE INSIDE DIMENSION —
<br />SHALL BE SLIGHTLY LARGER
<br />THAN THE OUTSIDE DIMENSION
<br />OF THE COMPRESSION STRUT
<br />3 - TURNS OF WIRE- TYPICAL —i
<br />3/4" LAG SCREW
<br />STRUCTURE
<br />RIGID STEEL TUBING (ADJUSTABLE RESISTANCE
<br />STRUT) - SEE SCHEDULE FOR SIZE
<br />NO. 12 GA. VERTICAL WIRE HANGER, SECURE TO
<br />STRUCTURE PRIOR TO SETTING TUBE.
<br />DRILL 3/37 HOLE AND INSTALL BOLT AND
<br />LOCKING NUT
<br />RIGID STEEL TUBING - NOTCHED AT RUNNER
<br />12 GA. GALV. WIRE AT 450 TO STRUCTURE ABOVE
<br />MAIN RUNNER
<br />COMPRESSION PIPE STRUT
<br />SIZE DIAM X WALL THICKNESS
<br />L MAX HEIGHT
<br />1 /7 x 22 GA
<br />3'-0'
<br />314'X 22 GA
<br />4'-3"
<br />1" X 20 GA
<br />5'-0'
<br />1 114'X 20 GA
<br />7-0'
<br />1 1 /7 X 20 GA
<br />8'-6"
<br />7' X 20 GA
<br />ill -61
<br />2 112'X 18 GA
<br />14'-6"
<br />3'X 18 GA
<br />17-3'
<br />3 1/2'X 16 GA
<br />20'-0'
<br />4" X 16 GA
<br />23'3"
<br />3
<br />a
<br />NOTES:
<br />9 • THESE COMPRESSION STRUTS SHALL BE PLACED 12'40" OC IN BOTH DIRECTIONS WITH THE FIRST
<br />z POINT 6'-0" FROM EACH WALL.
<br />u • SUSPENDED CEILINGS WHICH REQUIRE A PANELIZED SYSTEM, SHALL BE INSTALLED PER ASTM C635
<br />Q AND CBC SECTION 2506.2.1
<br />1 0) CSOMPRESSION CALE STRUT
<br />NO
<br />A WOOD JOIST OR RAFTER
<br />g AT WOOD JOIST OR
<br />RAFTER
<br />C AT WOOD JOIST OR BLOCK
<br />K 9 GA. STAPLES OR
<br />GHOLD "J" NAILS AT EACH WIRE LOOP
<br />RAFTER
<br />WIRE
<br />WIRE
<br />JOIST OR RAFTER
<br />114- DIA. EYE SCREW WITH FULL THREAD
<br />EMBEDMENT (2 1 /7'MIN.)
<br />BRACING WIRE
<br />3- 1 112- X 9 GA. STAPLES OR
<br />3 - STRONGHOLD "J" NAILS AT EACH WIRE LOOP
<br />2X BLOCKING WITH 2 -16d COMMON NAILS
<br />EACH END
<br />FOR BRACING WIRES - 114- CLOSED EYE SCREW
<br />THREADS IN DIRECTION OF WIRE - 1 1 /4" MIN..
<br />EMBEDMENT
<br />1 /4" DIA. DRILLED HOLE
<br />N SADDLE TIE - (SEE DETAIL G)
<br />HANGER WIRE
<br />NOTE: SOLID BLOCKING REQUIRED
<br />FOR EITHER TYPE OF BRACING
<br />IBER
<br />IE - (SEE DETAIL G)
<br />CHORD
<br />WIRE
<br />WIRE
<br />BRACING WIRE PARALLEL TO WOOD TRUSS
<br />D TO BOTTOM OF JOIST
<br />DO NOT INSERT SCREW EYES INTO SIDE OF
<br />MICRO -LAM FLANGE
<br />BRACING WIRE
<br />�1 MICRO -LAM UPPER FLANGE
<br />I
<br />DIMENSIONS GREATER THAN 1/2"
<br />HANGER WIRES AND BRACING WIRES - 3 TURNS
<br />G TYPICAL SADDLE TIE
<br />1/4" DIA. SCREW EYE WrTH 1 1/4" MIN.
<br />PENETRATION
<br />o HANGER WIRE
<br />^� 1" MIN.
<br />z
<br />MICRO -LAM LOWER FLANGE NOTE: DO NOT INSERTSC RE
<br />W EYES
<br />U I"'I PARALLEL TO LAMINATIONS (SEE DETAIL F)
<br />E (DETAIL MAY ALSO BE USED AT TOP CHORD)
<br />1 5) SUSPENDED CEILING NOTES (1 2) WIRE CONNECTIONS TO WOOD CONSTRUCTION
<br />SCALE: V= 1'-0" SCALE: 11/2"= 1'-0"
<br />3
<br />O
<br />zZ
<br />6
<br />NOTES:
<br />1. ALL WIRE TO BE SADDLE TIED
<br />2. INSTALLATION TO COMPLY WITH
<br />2016 CBC SECTION 808, ASCE 7-10,
<br />ASTM C 635 & C 636
<br />A.C. LAY -IN PANEL
<br />7) SUSPENDED CEILING DETAIL AT WALL
<br />SCALE: NTS
<br />0
<br />TYPICAL CEILING DETAILS
<br />SCALE: 1/8" = V-0'
<br />PERIMETER STARTER
<br />WALLS
<br />4 EACH, 12 GA. SPLAY
<br />WIRES 0 12'-0" O.C.
<br />MAX & 6'-0' MAX
<br />FROM WALLS - SEE
<br />DETAILS 7/AD8
<br />COMPRESSION STRUT
<br />AT 12'-0" O.C. MAX
<br />(6'-0" MAX FROM END
<br />OF RUNNER) - SEE
<br />DETAIL 10/AD8
<br />'ti" STRUT AS REQUIRED
<br />2XBLOCKAT24" O.C. KVVr IKU�
<br />WITH A35 EACH END
<br />TO TRUSS
<br />ESUSPENDED CEILING
<br />(3) #12D VT/
<br />ADIABRA
<br />\..
<br />— — — _ — —
<br />A35 EACH
<br />2X4 STUDS AT 24"
<br />O.C. WITH (4) SDS
<br />TO 2X BLOCK
<br />2X4 � 24" O.C. WITH
<br />(3) # 10 SDS EACH
<br />STUD
<br />16 GA. CORNER
<br />ANGLE
<br />5/8" GYPSUM BOARD -
<br />CONTINUE TO WALL AT I LINE OF WALK-IN
<br />AREA BETWEEN COOOLER I COOLER AS OCCURS
<br />1
<br />1)
<br />CEILING FRAMING
<br />9) C6
<br />HANGER WIRES 0 ALTERNATE
<br />CORNERS TO THE STRUCTURE ABOVE
<br />FIXTURE BRACING DETAIL
<br />SCALE: 1 /2" = V-0'
<br />O
<br />O
<br />9
<br />z
<br />6
<br />K�
<br />LATERAL FORCE BRACING
<br />4 EACH #12 GAUGE WIRE
<br />SEC U RED TO MAIN
<br />RUNNER WITHIN 7' OF
<br />CROSS TEE INTERSECTION
<br />AND SPLAYED 900 FROM
<br />BOTH DIRECTIONS WITH
<br />FIRST POINT WITHIN 6'
<br />FROM STARTING CORNER
<br />COMPRESSION POST —
<br />ATTACHED TO THE
<br />STRUCTURE W/ (2) #12
<br />SCREWS TO ROOF DECK
<br />1 /4" MACHINE -
<br />BOLT
<br />HEAVY DUTY —
<br />CROSSRUNNER
<br />HEAVY DUTY —
<br />MAIN RUNNER
<br />SPLAY BRACING NOTE:
<br />CROSS -FURRING SHALL BE SECURELY ATTACHED TO THE MAIN
<br />RUNNER BY SADDLE TYING WITH NOT LESS THAN ONE STRAND
<br />OF NO. 16 OR TWO STRANDS OF NO. 18 US. GAUGE TIE WIRE
<br />OR APPROVED EQUIVALENT ATTACHMENTS.
<br />RUNNERS AND FURRING: THE MAIN RUNNER AND
<br />CROSS -FURRING SHALL BE NOT LESS THAN THE SIZES SET FORTH
<br />IN TABLE NO. 47-A, EXCEPT THAT OTHER SECTIONS OF
<br />EQUIVALENT STRENGTH MAY BE SUBSTITUTED FOR THOSE SET
<br />FORTH IN THIS TABLE.
<br />#12 GAUGE
<br />\ T WIRTICALHANGER
<br />'O.C.
<br />WIRE @ 4'-0" O.C.
<br />TYPICAL CEILING DETAILS
<br />SCALE: NTS
<br />44W.?. P PRy PROP
<br />W-tRGN.I OF 1Nl
<br />X� QNG t#A M
<br />3pl COPYRIGHT 2019
<br />REVISIONS
<br />THIS DOCUMENT, AND THE IDEAS AND DESIGNS
<br />INCORPORATED HEREIN, AS AN INSTRUMENT OF
<br />PROFESSIONAL SERVICE, IS THE PROPERTY OF
<br />"api" AND IS NOT TO BE USED, IN WHOLE OR IN
<br />PART, FOR ANY OTHER PROJECT WITHOUT
<br />WRITTEN AUTHORIZATION.
<br />PLANNING ■ ■ ■
<br />ARCHITECTURE
<br />ARCHITECTURE PLUS INC.
<br />4335-B NORTH STAR WAY
<br />MODESTO, CA 95356
<br />ph. 209.577.4661
<br />fx. 209.577.0213
<br />www.apiarc.com
<br />FRANK C. BOOTS
<br />JOSEPH L. SMITH
<br />RODNEY C. ALONZO
<br />ARCHITECTS
<br />W Z a
<br />W owe
<br />DC�z
<br />a W O
<br />99
<br />�0m
<br />S
<br />H
<br />Q d O
<br />Nc�z
<br />•d
<br />�Q Z a
<br />ii Q OOC
<br />OC
<br />Lu
<br />UJ W
<br />Q
<br />ru
<br />in
<br />DATE: JULY 2619
<br />JOB NO.: 18-114
<br />DRAWN: A. ZAPIEN
<br />CHECKED: J. SMITH
<br />SHEET:
<br />AD3
<br />U
<br />z
<br />0
<br />OC
<br />7/8" WALL ANGLE
<br />NOTE:
<br />8" MAX.
<br />• COMPRESSION STRUTS: STEEL SECTION WITH L/R RATIO OF
<br />#12 GAUGE VERTICAL HANGER
<br />200 MAX, SECURE TO MAIN RUNNERS WITH 1 /4" MB AND TO
<br />WIRE @ 4'-0' O.C.
<br />STRUCTURE WITH 3/16" 0 POWER DRIVEN CLIPS
<br />`a
<br />• COMPRESSION STRUT SHALL NOT REPLACE HANGER WIRE
<br />HEAVY DUTY MAIN RUNNER
<br />ATTACHED
<br />I °,
<br />VERIFY LAYOUT WITH REFLECTED
<br />WALL W/POP RIVET
<br />COMPRESSION STRUT-
<br />12 GA. VERT. HANGER
<br />CEILING PLAN
<br />°Qp
<br />SEE DETAIL 10/ADS
<br />WIRE @ 4'-0"O.C. W/MIN
<br />(3) TIGHT TURNS IN 1 1/7'
<br />NOTES:
<br />12 GA. SPLAYED WIRE
<br />• HANGER WIRES TO BE 12 GAGE FOR 48" SPACING
<br />7/8" WALL ANGLE
<br />BRACE WITH MIN {4)
<br />TIGHT TURNS IN 1 1 /2"
<br />• SUSPENSION SYSTEM ARMSTRONG "PRELUDE XL" OR APPROVED STRUCTURAL EQUAL
<br />BERC2
<br />8" MA)
<br />#12 GAUGE VERTICAL HANGER
<br />•ENDS OF MAIN RUNNERS AND CROSS MEMBERS TO BE TIED TOGETHER WITH 16 GA. WIRE 70 PREVENT
<br />WIRE 0 4'-0' O.C.
<br />SPREAD
<br />• WIRES GREATER THAN I IN 6 OUT OF VERTICAL TO HAVE COUNTER WIRING
<br />HEAVY DUTY MAIN RUNNER
<br />• CEILING MAY BE ATTACHED AT 2 WALLS MAX - PROVIDE 3/4" MIN CLEAR AT FREE ENDS
<br />d
<br />450
<br />ATTACHED
<br />°' `a
<br />• 4 DIAGONAL BRACING WIRES / 144 S.F. (MIN 7T DISTANCE FROM WALLS)
<br />WALL W/BERC2 CLIP
<br />tl,
<br />6
<br />• HANGER WIRES, 5 TIGHT TURNS - 12 GAUGE BRACE WIRES, 4 TIGHT TURNS
<br />• ALL CEILING WIRES AND UNBRACED DUCTS, PIPES, ETC. TO HAVE MIN 6' SEPARATION
<br />450
<br />SCO
<br />7
<br />• ALL LIGHT FIXTURES AND DUCT TERMINALS ATTACHED TO CEILING GRID TO RESIST HORIZONTAL FORCES
<br />MAX
<br />MAX
<br />EQUAL TO WEIGHT
<br />7/8" WALL ANGLE
<br />• RECESSED FIXTURES AND DUCT TERMINALS LESS THAN 56 LBS, SHALL BE SUPPORTED BY SAFETY WIRES
<br />BERC2
<br />8" MA
<br />{SLACK) TO OVERHEAD STRUCTURE
<br />#12 GAUGE VERTICAL HANGER
<br />WIRE 0 4'4'0.C.
<br />• SURFACE MOUNTED FIXTURES AND DUCT TERMINALS TO BE SUPPORTED WITH MINIMUM OF 2 - 14 GAGE
<br />CLAMPS WHICH SURROUND RUNNER SUPPORT BY 12 GAGE WIRE TO OVERHEAD STRUCTURE (NO
<br />0
<br />' ".
<br />(7
<br />ROTATIONAL SPRING CUPS)
<br />3:
<br />*' F
<br />30
<br />2" MAX FROM
<br />O
<br />,
<br />'
<br />/g
<br />`c
<br />HEAVY DUTY MAIN RUNNER
<br />BRACE WIRES TO
<br />\ MAIN RUNNER
<br />3
<br />• PENDANT FIXTURES TO BE SUPPORTED TO OVERHEAD STRUCTURE WITH DEVICE CAPABLE OF CARRYING 4
<br />R
<br />UNATTACHED
<br />WALL W/BERC2 CLIP
<br />CROSS RUNNERS
<br />R
<br />XTHE FIXTURE'S WEIGHT
<br />Z
<br />tl`a
<br />"ARMSTRONG - SEISMIC Rx"
<br />z
<br />CROSS RUNNER
<br />• FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS
<br />w
<br />U
<br />SUSPENSION SYSTEM
<br />U
<br />ICC - ESR -1308
<br />Q
<br />u
<br />• FIXTURES AT 1 HOUR CONSTRUCTION TO BE WRAPPED TO MAINTAIN CONTINUITY OF FIRE ASSEMBLY
<br />Q
<br />• PROVIDE RIGID STEEL TUBING STRUTS AS REQUIRED BY ASTM C635 AND CBC SECTION 2506.2.1
<br />r8)
<br />SUSPENDED
<br />CEILING
<br />GRID ATTACHMENT
<br />r5)
<br />TYPITCAL CEILING DETAIL
<br />r2)
<br />SUSPENDED CEILING
<br />9) C6
<br />HANGER WIRES 0 ALTERNATE
<br />CORNERS TO THE STRUCTURE ABOVE
<br />FIXTURE BRACING DETAIL
<br />SCALE: 1 /2" = V-0'
<br />O
<br />O
<br />9
<br />z
<br />6
<br />K�
<br />LATERAL FORCE BRACING
<br />4 EACH #12 GAUGE WIRE
<br />SEC U RED TO MAIN
<br />RUNNER WITHIN 7' OF
<br />CROSS TEE INTERSECTION
<br />AND SPLAYED 900 FROM
<br />BOTH DIRECTIONS WITH
<br />FIRST POINT WITHIN 6'
<br />FROM STARTING CORNER
<br />COMPRESSION POST —
<br />ATTACHED TO THE
<br />STRUCTURE W/ (2) #12
<br />SCREWS TO ROOF DECK
<br />1 /4" MACHINE -
<br />BOLT
<br />HEAVY DUTY —
<br />CROSSRUNNER
<br />HEAVY DUTY —
<br />MAIN RUNNER
<br />SPLAY BRACING NOTE:
<br />CROSS -FURRING SHALL BE SECURELY ATTACHED TO THE MAIN
<br />RUNNER BY SADDLE TYING WITH NOT LESS THAN ONE STRAND
<br />OF NO. 16 OR TWO STRANDS OF NO. 18 US. GAUGE TIE WIRE
<br />OR APPROVED EQUIVALENT ATTACHMENTS.
<br />RUNNERS AND FURRING: THE MAIN RUNNER AND
<br />CROSS -FURRING SHALL BE NOT LESS THAN THE SIZES SET FORTH
<br />IN TABLE NO. 47-A, EXCEPT THAT OTHER SECTIONS OF
<br />EQUIVALENT STRENGTH MAY BE SUBSTITUTED FOR THOSE SET
<br />FORTH IN THIS TABLE.
<br />#12 GAUGE
<br />\ T WIRTICALHANGER
<br />'O.C.
<br />WIRE @ 4'-0" O.C.
<br />TYPICAL CEILING DETAILS
<br />SCALE: NTS
<br />44W.?. P PRy PROP
<br />W-tRGN.I OF 1Nl
<br />X� QNG t#A M
<br />3pl COPYRIGHT 2019
<br />REVISIONS
<br />THIS DOCUMENT, AND THE IDEAS AND DESIGNS
<br />INCORPORATED HEREIN, AS AN INSTRUMENT OF
<br />PROFESSIONAL SERVICE, IS THE PROPERTY OF
<br />"api" AND IS NOT TO BE USED, IN WHOLE OR IN
<br />PART, FOR ANY OTHER PROJECT WITHOUT
<br />WRITTEN AUTHORIZATION.
<br />PLANNING ■ ■ ■
<br />ARCHITECTURE
<br />ARCHITECTURE PLUS INC.
<br />4335-B NORTH STAR WAY
<br />MODESTO, CA 95356
<br />ph. 209.577.4661
<br />fx. 209.577.0213
<br />www.apiarc.com
<br />FRANK C. BOOTS
<br />JOSEPH L. SMITH
<br />RODNEY C. ALONZO
<br />ARCHITECTS
<br />W Z a
<br />W owe
<br />DC�z
<br />a W O
<br />99
<br />�0m
<br />S
<br />H
<br />Q d O
<br />Nc�z
<br />•d
<br />�Q Z a
<br />ii Q OOC
<br />OC
<br />Lu
<br />UJ W
<br />Q
<br />ru
<br />in
<br />DATE: JULY 2619
<br />JOB NO.: 18-114
<br />DRAWN: A. ZAPIEN
<br />CHECKED: J. SMITH
<br />SHEET:
<br />AD3
<br />U
<br />z
<br />0
<br />OC
<br />
|