Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST (continued) <br /> Test Method Developed by © Manufacturer ® Industry Standard C Professional Engineer <br /> Test Type C Pressure © Vacuum Ej Hydrostatic <br /> Test Equipment Used: <br /> Sump/UDC ID UDC#9-10 UDC#11-12 UDC#13-14 UDC#15-16 <br /> Sump Manufacturer Bravo (FRP) Bravo (FRP) Bravo (FRP) Bravo (FRP) <br /> Sump Depth (inches) 30 30 30 30 <br /> Sump Bottom to Top of 10 10 10 10 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 2:52 2:52 3:12 2:52 <br /> Initial Reading 4.1746 2.4892 4.8636 4.0058 <br /> Test End Time 3:07 3:07 3:27 3:07 <br /> Final Reading 4.1744 2.4902 4.8649 4.0059 <br /> Change in Reading -.0002 .0010 .0013 .0001 <br /> Pass Fail Criteria +/-0.002 +/-0.002 +/- 0.002 +/- 0.002 <br /> Tightness Test Results © Pass © Fail E/1 Pass C Fail E] Pass © Fail El Pass C Fail <br /> Sump/UDC ID <br /> Sump Manufacturer <br /> Sump Depth (inches) <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time <br /> Initial Reading <br /> Test End Time <br /> Final Reading <br /> Change in Reading <br /> Pass Fail Criteria <br /> Tightness Test Results C Pass C Fail C Pass C Fail © Pass 0 Fail 0 Pass 0 Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />