COMPONENTS SCHEDULE KEYNOTES - LIGHTING LIGHTING CONTROL INSTALLATION NOTES
<br /> REMOTE CONTROL FOR MANUAL ON/OFF SWITCHING FOR SMARTCAST ZONES a, b,
<br /> TYPE MANUFACTURER PART DESCRIPTION c,AND f. LOCATED IN MANAGER'S DESK FOR EASY ACCESS. SEE ARCHITECTURAL 1. ENSURE ALL SMARTCAST CONTROL MODULES ARE PLUGGED
<br /> NUMBER SHEET EF-L FOR ORDERING INFORMATION. INTO EACH SMARTCAST FIXTURE PRIOR TO INSTALLING.
<br /> OCCUPANCY SENSOR'A', RE:4/E2.1, +42",TYP.
<br /> REMOTE CONTROL FOR MANUAL ON/OFF SWITCHING FOR SMARTCAST E212. DURING INSTALLATION OF THE SMARTCAST FIXTURES, ORIENT
<br /> 1O CREE CCT-CWC-1 FIXTURES LOCATED IN MANAGER'S DESK. SEE ARCHITECTURAL SHEET OCCUPANCY SENSOR'B', RE:3/E2.1, TYP. ALL SENSORS AWAY FROM WINDOWS.
<br /> EF-L FOR ORDERING INFORMATION.
<br /> 2O LEVITON OSSMT-MDW OCCUPANCY SENSOR ON/OFF SWITCHING
<br /> LIGHTING. FOR AUTOMATIC CONTROL OF REFER TO SITE PLAN FOR PARKING AREA LIGHTING LAYOUT. 3. ENSURE ALL SMARTCAST FIXTURES ARE POWERED PRIOR TO 1
<br /> BEGINNING ONEBUTTON SETUP.
<br /> O LEVITON OSFHU-CTW OCCUPANCY/VACANCY SENSOR CEILING MOUNTED IN COOLER VAULT FOR
<br /> AUTOMATIC CONTROL OF LIGHTING. LIGHT SWITCH FOR COOLER TO HAVE WET LOCATION SWITCH COVER. 4. TO BEGIN ONEBUTTON SETUP, TURN ON THE CONFIG TOOL.
<br /> OCCUPANCY/VACANCY SENSOR CEILING MOUNTED IN STOCKROOM FOR 5
<br /> 4O LEVITON OSC20-MOW AUTOMATIC CONTROL OF STOCKROOM LIGHTING.
<br /> ❑ PHOTOCELL(PC)MOUNTED ON CEILING IN PRIMARY DAYLIGHT ZONE FOR 5. THE CONFIG TOOL WILL SEARCH FOR THE NETWORKS WITHIN
<br /> 6 AUTOMATIC CONTROL OF PRIMARY AND SECONDARY DAYLIGHT ZONES. CONTROL THE STORE.
<br /> 5O RACO 5121-0 ON/OFF LIGHT SWITCH WITH WET LOCATION COVER FOR VAULT COOLER. INTENT IS FOR PRIMARY AND SECONDARY DAYLIGHT ZONES('a','b')TO 5865 Owens Drive
<br /> 2 AUTOMATICALLY DIM UP/DOWN BASED UPON THE AMOUNT OF DAYLIGHT PRESENT. 6. IF NONE ARE FOUND, THE CONFIG TOOL WILL ASK THE USER TO Pleasanton, CA 94588
<br /> 6O LEVITON ODCOP-OOW PHOTOCELL(PC) MOUNTED ON CEILING IN PRIMARY DAYLIGHT ZONE FOR CONTRACTOR TO CONFIRM POWERPACK AND DIMMING TYPE OF FIXTURES PRIOR PRESS OK TO BEGIN ONEBUTTON SETUP. 925-251-7200
<br /> AUTOMATIC CONTROL OF PRIMARY AND SECONDARY DAYLIGHT ZONES. TO ORDERING. PROVIDE ALL ACCESSORIES REQUIRED FOR A COMPLETE AND
<br /> O
<br /> DIMMER SWITCH LOCATED IN STOCKROOM FOR MANUAL CONTROL OF OPERATIONAL SYSTEM. 7. IF THE CONFIG TOOL DISCOVERS EXISTING NETWORKS, THE LEVITON DS710-10Z STOCKROOM LIGHTING.
<br /> USER WILL BE OFFERED THE OPTIONS OF CONNECTING TO THE
<br /> 7 DIMMER SWITCH LOCATED IN STOCKROOM FOR MANUAL CONTROL OF EXISTING NETWORK OR CREATING A NEW NETWORK.
<br /> O LEVITON OPP20-D2 POWER PACK LOCATED IN CEILING PLENUM NEAR MANAGER'S OFFICE. STOCKROOM LIGHTING.
<br /> POWER PACK LOCATED IN CEILING PLENUM NEAR MANAGERS OFFICE. 8. ONCE THE USER BEGINS THE ONEBUTTON SETUP, SET THE
<br /> EMS SYSTEM LIGHTING E81CONFIG TOOL DOWN IN A SAFE LOCATION IN THE STORE. MOVING
<br /> CONTROL SIGNAL SMARTCAST WIRELESS SUMMARY OCCUPANCY/VACANCY SENSOR CEILING MOUNTED IN STOCKROOM FOR THE CONFIG TOOL DURING ONEBUTTON SETUP CAN MAKE
<br /> (EMS TO BE INSTALLED O AUTOMATIC CONTROL OF STOCKROOM LIGHTING. COMMISSIONING TAKE LONGER.
<br /> L-11DURING TENANT FINISH OUT) ZONE LOCATION OCCUPIED UNOCCUPIED OCCUPANCY DAYLIGHT HARVEST 10 LIGHTS TO BE CONTROLLED THROUGH LIGHTING CONTACTOR.SEE DETAIL 5/E.2.1
<br /> LEVEL LEVEL TIMEOUT MIN LEVEL FOR DETAILS. 9. DURING ONEBUTTON SETUP THE FIXTURES WILL DIM, WILL BE
<br /> HOT /7LC_1_
<br /> NEUTRAL BRIGHT, WILL TURN OFF FOR A FEW MINUTES, AND WILL FLICKER.
<br /> a FRONT RETAIL AREA 100% 90% 30 MINUTES 35% NOTE: CONTRACTOR TO CONTACT LIGHT SWITCHES 10. NAVIGATE THE MENU TO DIAGNOSTICS > IDENTIFY NETWORK.
<br /> LEVITON TECHNICAL SUPPORT WITH ALL OCCUPANCY SENSING SWITCHES ARE TO BE VERIFY ALL SMARTCAST DEVICES ARE IN THE NETWORK. CONSULTANT
<br /> C
<br /> ANY QUESTIONS IN REGARD TO MULTI-TECHNOLOGY WALL SWITCH SENSOR, 1200 SQ. FT.
<br /> b FRONT RETAIL AREA 100% 90% 30 MINUTES 35% INSTALLATION. MAJOR MOTION COVERAGE, 400 SQ. FT., MINOR MOTION
<br /> 11. CREATE ONE OF THE TWO GROUPS SHOWN ON THE PLAN USING
<br /> L-41 — SITE LIGHTINGEMCAtechsupport@leviton.com COVERAGE, 800W@120V INC, 1200VA@120V FL, MODIFY GROUP > MODIFY GROUP > CREATE GROUP >
<br /> C SALES 100% 90% 30 MINUTES 5% 800-959-6004 2700VA@277V FL, 1/4HP@120V MOTOR, COMMERCIAL OCCUPANCY.
<br /> L-1 EXT. LIGHTING EMS SYSTEM LIGHTING GRADE -WHITE CALIFORNIA TITLE 24 COMPLIANT. ALL TO
<br /> CONTROL SIGNAL f BEVERAGE WALL 100% 80% 30 MINUTES 20% BE PROVIDED BY GRAYBAR AND INSTALLED BY G.C.
<br /> °--I SPARE (EMS TO BE INSTALLED 12. NAVIGATE THE MENU TO DIAGNOSTICS> IDENTIFY GROUP >
<br /> SPARE DURING TENANT FINISH OUT) OCCUPANCY.VERIFY THE GROUPS MATCH THE PLAN.
<br /> L-11
<br /> HOTNEUTRAL 13. REPEAT STEPS 11 AND 12 FOR EACH GROUP IN THE TABLE.
<br /> EMS SYSTEM LIGHTING ELEVEn
<br /> CONTROL SIGNAL 14. NAVIGATE THE MENU TO DEVICE SETTINGS> OCCUPANCY TO
<br /> (EMS TO BE INSTALLED LC2 SET THE OCCUPIED LEVEL, UNOCCUPIED LEVEL, AND
<br /> L-11
<br /> DURING TENANT FINISH OUT) C OCCUPANCY TIMEOUT TO APPLY THESE SETTINGS TO EACH
<br /> HOT NEUTRAL I I GROUP AS LISTED IN THE SETTINGS TABLE ON THE PLAN.
<br /> SIGNAGE 15. NAVIGATE THE MENU TO DEVICE SETTINGS > DAYLIGHT TO SET
<br /> 2 ° o SPARE THE MINIMUM LEVEL OR DISABLE DAYLIGHT PER THE SETTINGS
<br /> /FLC3 TABLE ON THE PLAN.
<br /> C L-15 BUILDIN SIGNAGE PROVIDE TORK DIGITAL DGLC SERIES, MODEL#DGLC200A-NC1
<br /> o--I I--o SPARE (2-CHANNEL, SPDT)TIMECLOCK TO CONTROL LIGHTING 16. NAVIGATE TO THE MAIN MENU OF THE CONFIG TOOL (MODIFY
<br /> L-33 MONUMENT SIGNAGE L-35 CA P SIGNAGE CONTACTORS PRIOR TO THE EMS SYSTEM BEING INSTALLED. GROUPS, DEVICE SETTINGS, ETC.)AND POWER OF THE CONFIG
<br /> LIGHTING CONTACTOR LC1 AND LC2 SHALL BE CONTROLLED TOOL.
<br /> L-10 MONUMENT SIGNAGE L-37 CANOPY LIGHTING ON 1-CHANNEL AND LC3 SHALL BE CONTROLLED ON THE
<br /> o �-o SPARESECOND CHANNEL.
<br /> L-39 - CANOPY LIGHTING 17. FOR THE SMARTCAST 7-11 INSTALLATION VIDEO, SEE YOUTUBE
<br /> o o SPARE CHANNEL LINK(https://youtu.be/XNV400hlRYA).
<br /> LU
<br /> z w
<br /> OI-
<br /> 5 LIGHTING CONTACTOR Cn z
<br /> N.T.S. CT CABINET DIST. Q
<br /> (TYP) Q U
<br /> 10 UTILIMETER �MAIN
<br /> PANEL'MDP' � C
<br /> LT-4 G
<br /> LT-4 LT-4 LT-4 L-1 PANELBOARD 'F' z
<br /> L-1 L-1 L-1 LLQ O
<br /> ❑ � 0 0
<br /> 1 z 06 �
<br /> _ PANELBOARD 'C' ( Q O
<br /> PANELBOARD 'L' ^ ' 0
<br /> DP4E ` V
<br /> A2sc A2Esc A2sc A2Esc A2sc A2Esc - L-3 LT-3 z
<br /> L-J
<br /> L-4,f L-4,f L-4,f L-4,f L-4,f L-4,f L-1 O
<br /> Neutral
<br /> LEVITON L-6 J D 34E ;- PANELBOARD 'S' O J
<br /> MODEL#OSSMT-MDW L 7 PANELBOARD 'A'
<br /> O o LT-3 L-2 2' z
<br /> a L-1
<br /> C d 2 A2sc A2sc A2sc A2sc A2sc A2sc A2
<br /> Line Black White LAC LAC LAC L-4,c LAC L-4,c L-4, - N
<br /> L-8 L-1
<br /> Blue X1 A2sc A2EsC
<br /> o L-8 LAC LAC
<br /> Green
<br /> e o
<br /> _ I J
<br /> Ground C
<br /> L-1
<br /> A2Esc A2sc A2EsC A2sc A2Esc A2sc A2Esc
<br /> O LAC L-4,c L-4,c LAC LAC LAC LAC 2
<br /> n H 2
<br /> L-2 A2 E
<br /> NOTE: RESTROOM SET TO 10 MINUTES. BACKROOM L-3,d BLDG DEPT. 10.11 .19
<br /> AND OFFICES SET TO 20 MINUTES. BACKROOM WITH C
<br /> HIDDEN AREAS SET TO 30 MINUTES. —SECONDARY DAYLIGHT DS4E•
<br /> ONE BOUNDARY _ r L-3'• > ' ;
<br /> "A" OCCUPANCY SENSOR LT-4 3 A2sc A2sc A2sc A2sc A2sc A2sc A2s L-1 /^\ REVISIONS
<br /> L-1 LAC LAC LAC LAC LAC LAC L-4, °
<br /> 4 N.T.S. 3
<br /> 0 1 PR#1 12.20.19
<br /> I
<br /> 2 PR#2 01.06.20
<br /> H I A2E A2
<br /> L-2 I L-3,d L-3,d
<br /> o m A2Esc A2sc A2Esc I A2sc A2Esc A2sc
<br /> Black v
<br /> LAC L-4,c LAC I L-4,b L-4,b L-4,b
<br /> White I 7 7
<br /> Red PRIMARY DAY IGHT b c Od
<br /> Load I ZON E BOUN ARY E] 9 4
<br /> I g g
<br /> LEVITON
<br /> MODEL#OSFHU-CTW — —
<br /> rev.8/2012 A2sc A2sc A2sc I A2sc A2sc A2sc A2 A2
<br /> TIME DELAY ADJUSTMENT LAC L-4,c LAC I L-4,a L-4,a L-4,a L-3,d L-3,d
<br /> LT-4
<br /> NOTE: COOLER PLACEMENT SET TO 10 MINUTES. LT-3
<br /> L_1 O 2 L-1
<br /> 5
<br /> El 5
<br /> n n I 6 6
<br /> 3 B OCCUPANCY SENSOR A2Esc A2sc A2Esc I A2sc A2Esc ®a°b A2sc a A2
<br /> N.T.S. L-4,C LAC LAC I L-4,a L-4,a L-4,a -2' ` - 1' L-3,d
<br /> DS4E•
<br /> X1 _L-3' ,
<br /> L-8
<br /> Aq N
<br /> �
<br /> L-1 J JI J J LT-4 2.5
<br /> LT-3 L-1 L-1 L-1 L-1 L-1
<br /> L-1
<br /> NORMALLY 1711
<br /> ON O O O O
<br /> LINE BLACK BLACK
<br /> PURE WAVE SWITCH
<br /> INVERTER INPUT NEUTRAL WHITEBROWN
<br /> (UNSWITCHED) SERIES DEVICE
<br /> 11/15/19
<br /> INVERTER DIMMER EARTH GROUND GREEN UNIT WHITE SEAL/SIGNATURE
<br /> 4 JOB NO. 1497.009
<br /> GROUND NORMALLY LIGHTING
<br /> WIRE OFF LOAD
<br /> LED D C B A DRAWN RB
<br /> NOTE:CAP UNUSED WIRES
<br /> NEUTRAL
<br /> CHECK AR
<br /> INVERTER WIRING DIAGRAM LIGHTING CONTROLS PLAN LIGHTING CONTROL
<br /> 2 1 PLAN
<br /> N.T.S. SCALE: 1/4"= 1'-0"
<br /> SHEET
<br /> 1 2 4 8
<br /> SCALE: 1/4"= 1'-0" PROJECT
<br /> NORTH E201
<br />
|