5865 Owens Drive
<br /> Pleasanton, CA 94588
<br /> ELECTRICAL SPECIFICATION 925-251-7200
<br /> INTRODUCTION 3.5.1.1 SINGLE POLE SWITCHES: 3.7.4 FUSES, EQUIPMENT:
<br /> THE CONTRACTING FOR INSTALLATION OF THE ELECTRICAL SYSTEM WILL BE ACCOMPLISHED IN THE FIELD AT THE SINGLE POLE WALL SWITCHES SHALL BE SIMILAR AND EQUIVALENT; TO"LEVITON" EQUIPMENT FUSES, IF REQUIRED, SHALL BE OF THE DUAL ELEMENT, TIME DELAY VARIETY
<br /> DIVISION LEVEL. THESE SPECIFICATIONS ARE TO AID IN PREPARATION OF DIVISION LEVEL STORE PLANS AND CONTRACT #CS120-2W 20A, 120-277VAC TOGGLE SWITCH (WHITE)WITH COVERPLATE FOR SINGLE AS INDICATED ON PLANS. FUSES FOR HVAC/REFRIGERATION SHALL BE SIMILAR AND EQUIVALENT
<br /> DOCUMENTS. IN CASE OF A CONFLICT BETWEEN THIS SPECIFICATION AND THE CONTRACT DOCUMENTS PROVIDED BY GANG OR(WHITE)COVERPLATE FOR DOUBLE GANG. TO COOPER BUSSMANN FUSE TYPE LPN-RK-SP, CLASS RK1 FOR THE APPROPRIATE AMPERAGE.
<br /> THE DIVISION CONSTRUCTION MANAGER, THE DIVISION'S PLANS AND SPECIFICATIONS SHALL PREVAIL.
<br /> 3.5.1.2 3-WAY SWITCHES: 3.8 SPD SHALL BE PROVIDED BY GRAYBAR.
<br /> DEFINITIONS
<br /> THE FOLLOWING DEFINITIONS APPLY TO THIS PROJECT. 3-WAY SWITCHES SHALL BE SIMILAR AND EQUIVALENT TO"BRYANT"#4503-120A, 3.9 CONDUCTORS:
<br /> 120-277VAC 3-WAY SWITCH (WHITE HANDLE)AND (WHITE)COVERPLATE FOR
<br /> FURNISH -TO SUPPLY THE MATERIAL NECESSARY TO PERFORM THE TASK. SINGLE GANG OR(WHITE)COVERPLATE FOR DOUBLE GANG. ALL CONDUCTORS SHALL BE COPPER, TYPE THHN, UNO. MINIMUM CONDUCTOR SIZE SHALL BE
<br /> INSTALL-TO SUPPLY THE LABOR NECESSARY TO COMPLETE THE TASK. #12 AWG. CONDUCTORS#10 AWG AND LARGER SHALL BE STRANDED. INSULATION TYPE SHALL
<br /> PROVIDE-TO FURNISH AND INSTALL MATERIAL AND LABOR TO COMPLETE THE TASK. 3.5.1.3 SINGLE THROW, DOUBLE POLE EVAPORATOR SWITCH CONFORM WITH N.E.C. OR MANUFACTURER REQUIREMENTS. LIGHT FIXTURES SOMETIME REQUIRE
<br /> 90 DEGREE WIRE. FOR THE PARTICULIAR APPLICATION. USE TYPE THWN IN WET LOCATIONS.
<br /> 1. SCOPE SINGLE THROW, DOUBLE POLE SWITCHES SHALL BE SIMILAR AND EQUIVALENT TO"BRYANT"
<br /> 1.1 E.C.TO PROVIDE ALL LABOR, MATERIALS AND EQUIPMENT(U.N.O.) REQUIRED TO EXECUTE WORK PER NEC AND #30322D 120-600VAC NEMA 3R ENCLOSED AC MANUAL MOTOR CONTROLLER/DISCONNECT. 3.9.1 NM CABLE(ROMEX)SHALL NOT BE USED.
<br /> ALL APPLICABLE ELECTRICAL CODES IN FORCE AT THE TIME OF PROJECT COMPLETION. 3.5.2 NOT USED 3.9.2 ALUMINUM CONDUCTORS SHALL NOT BE USED U.N.O. CONSULTANT
<br /> 1.2 THIS WORK INCLUDES, BUT IS NOT LIMITED TO: ELECTRICAL SERVICE AND DISTRIBUTION SYSTEMS, PANELBOARDS, 3 CONVENIENCE OUTLET 3.9.3 METAL-CLAD CABLE (MC)SHALL BE PERMITTED FOR USE AS BRANCH CIRCUITS
<br /> 3.5. 20A
<br /> DISCONNECT SWITCHES, LIGHTING FIXTURES, POWER AND CONTROL WIRING WITH FINAL CONNECTIONS TO ALL ( ): IN WALL, CEILING OR CABINETRY.
<br /> EQUIPMENT REQUIRED FOR A COMPLETE SYSTEM. 20A CONVENIENCE OUTLETS SHALL BE SIMILAR AND EQUIVALENT TO"LEVITON"#CR20-W
<br /> 1.3 E.C. TO VERIFY TYPE OF POWER SERVICE AVAILABLE (UNDERGROUND OR OVERHEAD)AND 2 POLE, 3 WIRE, 20 A 125V, DUPLEX GROUNDING RECEPTACLE WITH (WHITE)COVERPLATE 4. TESTING AND INSPECTION
<br /> MAXIMUM SHORT CIRCUIT CURRENT PRIOR TO SUBMITTING A PROPOSAL. SIMILAR AND EQUIVALENT TO"LEVITON"#88003 FOR SINGLE DUPLEX OR"LEVITON" 4.1 TESTING:
<br /> #88016 FOR DOUBLE DUPLEX(QUAD).
<br /> 1.4 E.C.TO VERIFY TYPE OF TELEPHONE SERVICE AVAILABLE (UNDERGROUND OR OVERHEAD) 4 OUTLETISOLATED GROUND 4.1.1 THE E.C. SHALL TEST, PRIOR TO ENERGIZING FOR THE FIRST TIME,
<br /> 3.5. , 20A
<br /> PRIOR TO SUBMITTING A PROPOSAL. ( ): ALL PIECES OF ELECTRICAL EQUIPMENT TO ASSURE THEY HAVE THE
<br /> ISOLATED GROUND OUTLETS SHALL BE SIMILAR AND EQUIVALENT TO"LEVITON"#5362-IG PROPER PHASE TO PHASE AND PHASE TO GROUND INSULATION AND TO BE
<br /> 1.5 E.C.TO VERIFY METERING, IN ACCORDANCE WITH LOCAL ELECTRIC UTILITY COMPANY REQUIREMENTS, FOR
<br /> GENERAL SERVICE SCHEDULE. 2 POLE, 3 WIRE, 20A, 125V, SINGLE, ISOLATED GROUND RECEPTACLE (ORANGE)WITH FREE OF SHORTS.AFTER ENERGIZING, EACH LUMINAIRE SHALL BE LIT(WHITE)COVERPLATE. AND TESTED.
<br /> 1.6 E.C. SHALL INSTALL 3-PHASE 4-WIRE 120/208V WYE SERVICE. IF FOR ANY REASON, THIS IS ( ): 4.1.2 THE VARIOUS CIRCUITS SERVED FROM THE PANELBOARDS VARY IN LOADING.
<br /> 3.5.5 GFCI CONVENIENCE OUTLETS (INDOOR&OUTDOOR
<br /> NOT AVAILABLE, THE E.C. SHALL NOTIFY 7-ELEVEN, IN WRITING PRIOR TO SUBMITTING OF THE E.C. SHALL CAREFULLY BALANCE THE LOAD ON EACH LEG OF ELEvEn
<br /> PROPOSAL (U.N.O.). OUTDOOR GFCI OUTLETS SHALL BE WEATHER RESISTANT(WR) LABELED, EQUIVALENT TO THE SERVICE. WHEN ALL LOAD IS TURNED ON AND THE SYSTEM IS OPERATING
<br /> THE"LEVITON"#WR899-W 20A OUTLET WITH OUTDOOR COVERPLATE#4500B AND BACK AT 100%, THE INITIAL UNBALANCE SHALL NOT EXCEED 10%.
<br /> 1.7 E.C.TO PROVIDE PANELBOARD NAMEPLATES. PROVIDE LAMINATED PLASTIC NAMEPLATES WITH 3/4 INCH GFCI G
<br /> PLATE#63101. INDOOR OUTLETS SHALL BE EQUIVALENT TO "LEVITON"#7899-W, 20A
<br /> MINIMUM CONTRASTING-COLOR ENGRAVED LETTERS IDENTIFYING EACH PANELBOARD. WITH (WHITE)COVERPLATE.GFCI NOTE: WITH 3 PHASE DELTA, PHASES A AND C SHALL BE BALANCED WITHIN 10% PHASE B
<br /> 2. INSTALLATION
<br /> (HIGH LEG)SHALL BE BALANCED AS CLOSELY AS POSSIBLE.
<br /> 3.5.6 NOT USED
<br /> 4.2 INSPECTION:
<br /> 2.1 THE INSTALLATION SHALL COMPLY WITH ALL LAWS IN EFFECT AT THE TIME OF CONSTRUCTION APPLYING TO 3.5.7 SAFETY SWITCHES:
<br /> ELECTRICAL INSTALLATION,AND WITH THE REGULATIONS OF THE NEC, WHERE SUCH REGULATIONS DO NOT E.C. SHALL FURNISH AT THE COMPLETION OF THE PROJECT OR
<br /> CONFLICT WITH THE LAWS IN EFFECT,AND WITH THE PUBLIC UTILITY COMPANY FURNISHING THE SERVICE. SAFETY SWITCHES SHALL BE UL APPROVED GENERAL DUTY SAFETY SWITCHES WITH LOCK OFF EACH INSPECTION POINT OF THE PROJECT,AN INTERMEDIATE OR FINAL INSPECTION
<br /> HANDLES SIMILAR AND EQUIVALENT TO THOSE MANUFACTURED BY"SQUARE-D". SWITCHES CERTIFICATE FROM THE LOCAL INSPECTING AUTHORITY.
<br /> 2.1.1 THE E.C. SHALL UPGRADE THESE SPECIFICATIONS AS REQUIRED TO MEET COMPLIANCE WITH ALL OCAL CODES AND WILL BE NEMA INDICATED ON PLANS/LOCAL APPLICABLE CODES IN EFFECT; HOWEVER,WHERE THESE SPECIFICATIONS MAKE STIPULATIONS OVER AND 4.3 PERFORMANCE REQUIRED:
<br /> TYPE 1 FOR INDOOR (DRY) INSTALLATION WILL BE FUSIBLE OR NON-FUSIBLE AS INDINSTALLATION. FUSED SWITCHES SHALL HAVE REJECTION STYLE FUSE HOLDERS UT ICIC A NEMA TYPE DOOR MATCH/L ENCLOSURE FOR OUT
<br /> ABOVE THE MINIMUM REQUIREMENTS OF APPLICABLE CODES, THE CONTRACTOR SHALL NOT DOWN-GRADE
<br /> THESE SPECIFICATIONS TO MINIMUM CODE REQUIREMENTS WITHOUT PRIOR WRITTEN APPROVAL FROM LPN-RKAL CLASS RK1 FUSES4.3.1 ALL EQUIPMENT AND FIXTURES SHALL BE PROPERLY CONNECTED WITH
<br /> 7-ELEVEN. . ADEQUATE POWER AND CHECKED THOROUGHLY FOR PROPER OPERATION.
<br /> 2.2 E.C. SHALL PROVIDE ALL REQUIRED ELECTRICAL CONDUIT AND WIRING FOR ALL MOTORS, MOTOR STARTERS 3.5.8 NOT USED 4.3.2 ALL EXPOSED EQUIPMENT SHALL BE INSTALLED AS PER DRAWINGS AND IS
<br /> AND ELECTRICAL CONTROLS, U.N.O. E.C. SHALL MAKE ALL LINE VOLTAGE ELECTRICAL CONNECTIONS AS 3.5.9 PHOTO CELL(OUTDOOR): SUBJECT TO INSPECTION FOR WORKMAN-LIKE APPEARANCE.
<br /> REQUIRED FOR HVAC SYSTEMS.
<br /> ELECTRONIC LIGHT SENSOR SHALL BE THE TORK EPC-1. ENCLOSED IN A LEXAN HOUSING 5. INDUSTRY-STANDARDS
<br /> 2.3 E.C. SHALL INSTALL THE CONNECTIONS TO ALL RECEPTACLES, SALES COUNTERS,
<br /> GONDOLAS AND FINAL CONNECTIONS TO ALL FIXTURES AFTER FIXTURES ARE IN PLACE. WITH A 1/2"CONDUIT MOUNTING AND 180 DEGREE SWIVEL. INSTALL IN A WEATHERTIGHT JUNCTION BOX ON THE ROOF PER MANUFACTURER'S RECOMMENDATIONS. SET 5.1 THE FOLLOWING IS A LIST OF ABBREVIATIONS USED IN THE ELECTRICAL NOTES AND
<br /> -CANDLE LEVEL. SPECIFICATIONS.
<br /> SENSOR TO 100 FOOT
<br /> 2.4 E.C. SHALL VERIFY EXACT LOCATION OF ALL SIGNS WITH 7-ELEVEN REPRESENTATIVE. PROVIDE ALL CONDUITS AND W
<br /> WIRES WITH STUB-UPS AS DIRECTED BY THE 7-ELEVEN CORPORATION AND INSTALL FINAL CONNECTIONS AS 3.5.9.1 LIGHTING CONTROLLER(OUTDOOR LIGHTING CONTROL): NEC.....................NATIONAL ELECTRIC CODE, REF. COVERSHEET FOR APPLICABLE VERSION z W
<br /> REQUIRED. NEMA..................NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
<br /> THE LIGHTING CONTROLLER SHALL BE THE TORK LC-200 IN A NEMA 1 ENCLOSURE. UL........................UNDERWRITERS LABORATORIES, INC. 0
<br /> 2.5 WIRING THE LC-200 IS USED IN CONJUNCTION WITH THE TORK EPC-1 PHOTOCELL. LIGHTING HVAC...................HEATING,VENTILATING AND AIR CONDITIONING
<br /> 2.5.1 ALL WORK SHALL BE COMPLETED IN A NEAT AND WORKMAN-LIKE MANNER. THE E.C. SHALL CONTROLLER HAS A 2 TO 100 FOOT-CANDLE LIGHT ADJUSTMENT. IEEE......................INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERSGFCI.....................GROUND FAULT CIRCUIT INTERRUPTER
<br /> CONTACT THE 7-ELEVEN CORPORATION REPRESENTATIVE SHOULD THIS PLAN REQUIRE MODIFICATION TO 3.5.10 CONTACTOR(OUTDOOR LIGHTING CONTROL): AIC.......................AMPERES INTERRUPTING CAPACITY z
<br /> COMPLY WITH LOCAL CODES. LINO.....................UNLESS NOTED OTHERWISE
<br /> THE LIGHTINGCONTACTORS FOR USE WITH THE OUTDOOR PHOTO CELLS SHALL BE EC.........................ELECTRICAL CONTRACTOR Q U
<br /> 2.5.2 ALL CONDUCTORS SHALL BE RUN IN APPROVED METALLIC RACEWAY OR CONDUIT AND SHALL BE UNIFORMLY SIMILAR AND EQUIVALENT TO"SQUARE-D" ELECTRICALLY HELD LIGHTING CONTACTOR GC.........................GENERAL CONTRACTOR C
<br /> COLOR CODED THROUGHOUT THE ENTIRE SYSTEM. SPLICES, TAPS,AND TERMINALS SHALL BE MADE ONLY IN CLASS 8903 TYPE LG-80 FORM F WITH 120V CONTROL COIL, NORMALLY OPEN CONTACTS G z
<br /> J BOXES, OUTLET BOXES AND PANELBOARDS. RATED AT 30 AMPS CONTINUOUS, IN NEMA TYPE 1 ENCLOSURE WITH FUSED CONTROL 6. UTILITY ACCOUNT OPEN PROCESS w O
<br /> REF LIGHTING CONTACTOR DETAIL.
<br /> 2.5.3 THE E.C. SHALL ENSURE THE CONDUCTORS UTILIZED ARE IN KEEPING WITH GOOD PRACTICE FOR THE CIRCUIT. 6.1 GENERAL CONTRACTOR(GC)WORKS WITH THE UTILITY COMPANIES TO SET UP ALL. . : REQUIRED METERS AND ACCOUNTS ( ELECTRIC, NATURAL GAS, WATER)UNDER THE W
<br /> ��,,�Xt
<br /> CIRCUIT/PROTECTIVE DEVICES EMPLOYED. THE NEUTRAL CONDUCTOR(WHERE USED)SHALL HAVE 3511 PHOTO CELL BYPASS SWITCH
<br /> THE SAME AMPACITY AS THE ASSOCIATED PHASE.
<br /> 2.5.4 THE E.C. SHALL ENSURE THAT CIRCUIT AMPACITY AND SHORT CIRCUIT/OVERLOAD PROTECTION IS THE PHOTOCELL BYPASS SWITCH SHALL BE A"BRYANT"#4801-L SINGLE POLE LOCK GC COMPANY NAME Q U
<br /> APPROPRIATE FOR THE EQUIPMENT BEING INSTALLED. UL LISTING CONDITIONS SHALL BE OBSERVED. TYPE 15A 120-277 VOLT SWITCH WITH KEY#6006 AND COVERPLATE(WHITE). 6.2 FOR CORPORATE AND NON BCP FRANCHISEE, GC OBTAINS OPEN FACILITY REQUEST CO
<br /> FORM FROM DEVELOPMENT PROJECT MANAGER (DPM) O
<br /> . BLANK FORM IS LOCATED AT 3:NOTE: NO SUBSTITUTION SHALL BE PERMITTED UNLESS THE E.C. CAN PROVE TO THE 7-ELEVEN N
<br /> CORPORATION REPRESENTATIVE THAT THE PROPOSED SUBSTITUTE WILL OPERATE WITH 7-ELEVEN HUB/OPERATIONS/DEVELOPMENT PROGRAM MANAGEMENT QUICK LINKS U)
<br /> DI
<br /> 2.5.5 COMPLY WITH NEC/UL LISTING CONDITIONS, ROOFTOP UNITS MAY BE SHOWN WITH FUSED "BRYANT" KEY#6006. THE KEY SHALL BE TURNED OVER TO THE 7-ELEVEN CORPORATION z
<br /> DISCONNECT SWITCHES: REPRESENTATIVE AT ACCEPTANCE(NOT LEFT IN SWITCH, CASH REGISTER, ETC.). 6.3 AT LEAST FIFTEEN (15)DAYS PRIOR TO THE STORE OPEN DATE, GC MAILS 06 O
<br /> 2.5.5.1 ALL FUSES SERVING MOTOR LOADS WILL BE OF THE DUAL ELEMENT TYPE. COMPLETED OPEN FACILITIES REQUEST FORM TO ECOVA AT (n
<br /> 3.5.12 HEAT TRACE-FREEZER PIPE FREEZE PROTECTION (WHEN REQUIRED): 7-ELEVENOPCL@ECOVA.COM WITH A COPY TO THE DPM O J
<br /> 2.5.5.2 DUE TO DIFFERENT INTERRUPTING CHARACTERISTICS, PANELBOARD CIRCUIT BREAKERS MAY BE
<br /> RATED HIGHER THAN THE DUAL ELEMENT FUSES THEY SUPPLY TO ENSURE SUFFICIENT STARTING HEATING CABLE: FURNISH RAYCHEM 5XL1-CR WITH RAYCLIC-PC ELECTRICAL CONNECTION. XL
<br /> CURRENT. TRACE BY TYCO THERMAL CONTROLS, LLC. FOR EXTRA INFORMATION CONCERNING HEAT TRACE 6.4 BCP FRANCHISEES SET UP THEIR OWN UTILITIES AND THIS SET UP DOES NOT GO
<br /> SYSTEM CONTACT DAN PETERSEN WITH INDUSTRIAL HEATER(901-382-4761). THROUGH 7-ELEVEN,INC
<br /> 2.5.6 WIRE SIZES LISTED ARE MINIMUM. CONDUCTORS SHALL BE SELECTED SUCH THAT THE MAXIMUM VOLTAGE z
<br /> CIRCUIT BREAKER: PROVIDE SQUARED'QOI20EPD OR EQUIVALENT GFCI CIRCUIT BREAKER WITH
<br /> DROP (AT FULL LOAD AMPS)SHALL NOT EXCEED THE FOLLOWING GUIDELINES: 30mA TRIP.
<br /> rev 6/2016
<br /> 2.5.6.1 PANEL FEEDERS--2% OF CIRCUIT VOLTAGE AT SERVICE. NOTE: MECHANICAL CONTRACTOR TO INSTALL SELF REGULATING HEATING CABLE PER
<br /> 2.5.6.2 ALL BRANCH LOADS--3% OF CIRCUIT VOLTAGE AT SERVICE. MANUFACTURER'S REQUIREMENTS ON CONDENSATE DRAIN LINES INSIDE FREEZER BOXES THAT
<br /> ARE TO OPERATE AT OR BELOW 32 DEGREES F.
<br /> 2.5.6.3 TOTAL VOLTAGE DROP (SERVICE TO LOAD)--5% OF CIRCUIT VOLTAGE AT SERVICE. 3.6 SERVICE/DISTRIBUTION EQUIPMENT:
<br /> 2.5.7 SPECIAL NOTES ON SERVICES: PANEL AND DISTRIBUTION PANEL SHALL BE SQUARE'D'.ALL SWITCH GEAR TO BE FURNISHED FROM
<br /> 2.5.7.1 120/208V, 3-PHASE, WYE GRAYBAR, U.N.O. FOR PRICING AND PLACING ORDERS, CONTACT'7-ELEVEN' FOR THE APPROPRIATE
<br /> THE E.C. SHALL CHECK THE REQUIREMENTS OF ALL EQUIPMENT AND WILL INSTALL SALES DEPARTMENT.
<br /> AUTOTRANSFORM ERS (BUCK AND BOOST TRANSFORMERS)AS REQUIRED. 3.6.1 MAIN POWER SWITCHES
<br /> 2.5.8 THE E.C. SHALL PROVIDE DEDICATED CIRCUITS WITH ISOLATED GROUND FOR ALL CIRCUITS THE MAIN PANEL POWER SWITCHES/CIRCUIT BREAKERS SHALL BE SQUARE'D'TYPE I LINE, RATED AT 65,000
<br /> ORIGINATING FROM PANEL S. THE PURITY OF THE ISOLATED GROUND SHALL BE MAINTAINED BY USING ONLY
<br /> INSULATED GROUNDING CONDUCTORS AND ISOLATED GROUND. THE GROUNDING CONDUCTOR FOR THE . A.I.C. (MIN.)SWITCHES OR CIRCUIT BREAKERS SHALL BE LISTED AS INDICATED ON PLANS.
<br /> ISOLATED GROUND SHALL NOT MAKE ELECTRICAL CONTACT WITH THE COMMON EQUIPMENT GROUND ORANY ITEM NOTE: PANEL RATINGS REQUIRED FOR HIGHER AIC REQUIREMENTS SHALL BE PRESENTED TO THE
<br /> A
<br /> ETC.)A ANYPOINTPOINT OTHER THAN NNECTED TO THE OATnTHE SERVICE GROUNDINGN EUIPMENT OUND (TERMINAL.ISEE NEC O250.96( .B ITCH BOXES, DISTRIBUTOR FOR MODIFICATIONS TO THE GEAR SUBMITTAL. BLDG DEPT. 10. 11 . 1 9
<br /> 2.6 WHEN REQUIRED, E.C. TO ENSURE INTEGRITY OF FIRE RATED WALLS WHERE ELECTRICAL EQUIPMENT 3.6.2 PANELBOARDS:
<br /> PENETRATES WALLS. SEAL PER SPECIFICATIONS FOR FIRE STOPPING. SQUARE'D' PANELBOARDS USED IN SERIES WITH I-LINE CIRCUIT BREAKERS AND FITTED
<br /> 2.7 ALL PENETRATIONS THROUGH EXTERIOR WALLS ARE TO BE MADE WITH LB CONDULETS OF THE APPROPRIATE WITH SQUARE'D'BRANCH CIRCUIT BREAKERS ARE AS INDICATED ON PLANS.
<br /> SIZE PER NEC. ALL PENETRATIONS ARE TO BE SEALED PER NEC. HORIZONTAL OR VERTICAL SUPPORTS FOR USE AN APPROPRIATE SQUARED'CIRCUIT BREAKER WITH EACH PANEL. CIRCUIT X
<br /> RACEWAYS ARE TO COMPLY WITH NEC.WIRE TIES ARE NOT TO BE USED, U.N.O. BREAKERS SHALL BE TYPE QOXXX-"QO"-FRAME REVISIONS
<br /> 3. MATERIALS: 3.6.2.1 PANEL'F', IF REQUIRED, SHALL BE FED BY A SQUARED' NO. 8903SQG2V02 CONTACTOR
<br /> AND SHALL BE WIRED FOR EMERGENCY SHUT DOWN.
<br /> ALL MATERIALS AND DEVICES SHALL BE UL APPROVED AND SHALL CONFORM TO THE STANDARDS OF NEMA, NEC, 3.6.2.2 UPON COMPLETION OF WORK, E.C. SHALL PROVIDE A TYPED DIRECTORY IN EACH
<br /> AND IEEE. PANELBOARD. INCLUDE SYSTEM VOLTAGE, PHASING, CIRCUIT NUMBERING AND DESCRIPTIONS.
<br /> 3.1 LIGHT FIXTURES: PER SCHEDULE ON ELECTRICAL PLAN. 3.6.3 WIREWAY:
<br /> 3.2 RACEWAYS:ALL CONDUIT SHALL BE EITHER RIGID STEEL OR ELECTRICAL METALLIC TUBING (EMT). FOR IN SLAB THE WIREWAY SHALL BE SIMILAR AND EQUIVALENT TO"SQUARE D COMPANY"WIREWAY WITH
<br /> AND UNDERGROUND INSTALLATIONS, PVC OR RIGID STEEL SHALL BE USED. REFER TO FUELING SHEETS FOR APPROPRIATE FITTING FOR THE PARTICULAR INSTALLATION. E.C. SHALL SIZE TO INSTALLATION
<br /> APPROVED FUELING SYSTEMS CONDUIT. INSTALL PER NEC. IN ACCORDANCE WITH NEC, GOOD PRACTICE AND CODES IN EFFECT AT TIME OF
<br /> 3.3 FITTINGS AND BUSHINGS:ALL REQUIRED BENDS, FITTINGS, JUNCTION BOXES, ETC., WHETHER OR NOT THEY ARE INSTALLATION.
<br /> SHOWN ON THE DRAWINGS, SHALL BE INSTALLED TO SATISFY ALL APPLICABLE ELECTRICAL CODES AND STANDARDS 3.7
<br /> OF GOOD PRACTICE.ALL CONDUCTORS ENTERING/LEAVING A CONDUIT OR RACEWAY SHALL BE AFFORDED OVERCURRENT/SHORT CIRCUIT PROTECTIVE DEVICES:
<br /> ABRASION PROTECTION BY AN ADEQUATE BUSHING OR OTHER APPROVED MEANS. 3.7.1 PANELBOARD BRANCH/FEEDER CIRCUIT BREAKERS:
<br /> 3.4 OUTLET BOXES: SHALL BE STANDARD, STAMPED GALVANIZED STEEL BOXES; "J"-BOXES AND OUTLET BOXES USED AS ALL DOWNSTREAM BREAKERS MUST BE SQUARED'TO MAINTAIN SERIES LISTING. IF
<br /> A PULL BOX SHALL BE PROVIDED WITH A SUITABLE COVER OF SAME MATERIAL AS BOX. FUSIBLE DISCONNECTS ARE USED, SQUARE'D' PANEL BOARDS AND CIRCUIT BREAKERS
<br /> 3.5 WIRING DEVICES: SHALL BE USED.
<br /> INSTALL ON EACH AND EVERY OUTLET BOX,A WIRING DEVICE AND/OR COVERPLATE, ALL AS INDICATED BY SYMBOL 3.7.2 GROUND FAULT CIRCUIT INTERRUPTER (GFCI)BREAKERS:
<br /> ON THE DRAWINGS. GROUND FAULT CIRCUIT INTERRUPTER(GFCI)TYPE CIRCUIT BREAKERS SHALL BE
<br /> 3.5.1 WALL SWITCHES: SIMILAR TO THE PANELBOARD CIRCUIT BREAKERS BUT WITH GROUND FAULT
<br /> PROTECTION WITH MATCHING A.I.C. RATING. GFCI BREAKERS SHALL BE UL
<br /> APPROVED AS CLASS A DEVICES IN ACCORDANCE WITH UL STANDARD#943.
<br /> 3.7.3 FUSES, MAIN SWITCHBOARD:
<br /> MAIN SWITCHBOARD FUSES, IF REQUIRED, SHALL BE CLASS J CURRENT LIMITING FUSES
<br /> AS INDICATED ON PLANS.
<br /> 11/15/19
<br /> SEAL/SIGNATURE
<br /> JOB NO. 1497.009
<br /> DRAWN RB
<br /> CHECK AR
<br /> ELECTRICAL
<br /> SPECIFICATIONS