Laserfiche WebLink
B Side <br /> 8. Repeat steps 3-7 for the "B" side solenoid valve signal wires using the Channel 2 Input side of the MC100 Module. <br /> 9. Each and every product solenoid valve supplying gasoline to the nozzles should have a voltage signal "piggy-back" <br /> wire installed terminating at the MC100 Module. <br /> • "A" side valves to Input CH 1 — 1,2,3,4 • "B" side valves to Input CH 2— 1,2,3,4 <br /> Solenoid Disconnect Relay Wiring (1360A only) <br /> 10. Factory installed on the 1360A module/harness, the red &white "jumper'wire has two separate wire leads and is <br /> attached at four locations on the module: CH 1 Com 1,2,3,4; CH 2 Com 1,2,3,4; and the "Solenoid Disconnect Relay" <br /> position 1 &6. <br /> 11. The red &white "jumper"wire leads are connected to the neutral or common wiring for the solenoid valves. This <br /> jumper allows the module to reference the signal voltage from an authorized solenoid valve and also have the ability <br /> to disable the dispenser solenoids using the solenoid disconnect relay if the vacuum pump is not working properly. <br /> 12. To connect the jumper properly, locate the neutral or common wire that is associated with the control of the dispenser <br /> solenoid valves, this wire will be cut and each end separated and attached by a wire nut to the red &white `jumper' <br /> wire that has been factory installed on the MC100 Module. <br /> AC Power to the module <br /> 13. The MC100 Module requires a constant 120vac-2 amp power source from the dispenser. The power should be <br /> supplied from the main power strip or accessory connections capable of sustaining a 2 amp load. <br /> 14. Using a 3M Scotchl-ok supplied with the 1360A Module assembly, connect the factory installed black&white <br /> twisted pair on the MC100 Module to the black and white (power& neutral)from the main power strip or accessory <br /> connection of the dispenser. <br /> • •s••••• •••• <br /> • SOLENOID21 DISCO <br /> • HE T <br /> • <br /> • • <br /> • <br /> • <br /> • <br /> 610 L Vq03 801 <br /> FAULT <br /> • PMER <br /> c c � <br /> Solenoid Valve Neutral Wire Interrupt <br /> Note: The neutral wire color(AC valves)will typically be red, but may be a different color depending on solenoid type. <br /> 8-13 <br /> CARB Approved IBM 8-Healy Universal Manual-Executive Orders VR-281 and VR-202 <br />