4.3 Installation of the Liquid Sensor <br /> Installation of a liquid sensor requires technician to meet applicable requirements as specified <br /> in the SWRCB Local Guidance Letter 167 (LG 167). <br /> If not already present, install a liquid sensor following the manufacture's installation instruc- <br /> tions. Set the liquid sensor two (2) inches from the bottom of the Liquid Condensate Trap. See <br /> Figure 6. Then tighten the wire grip nut (of the TSP K2A) around sensor cable. <br /> At the point where the cable exits the top of the wire grip, place a permanent indicating mark <br /> on the sheathing of the cable (e.g. using a waterproof marker such as a Sharpie TM) which indi- <br /> cates the sensor is placed two (2) inches above the bottom of the Liquid Condensate Trap (see <br /> Figure 5). <br /> When programming the LCT liquid sensor at the UST tank monitoring console, label the sensor <br /> with "LCT" in the title, e.g. L10 would be labeled "LCT High Liquid". <br /> Figure 6 <br /> Liquid Sensor Height Setting <br /> Liquid Sensor <br /> ABottom of Liquid <br /> 211 Condensate Trap <br /> s-lo <br /> GARB Approved IOM 9-Liquid Condensate Trap-Executive Orders VR-201 and VR-202 <br />