Laserfiche WebLink
TLS RF Installation Wiring the TLS RF <br /> Figure 12 locates the diagnostic lights and setup switches in the TLS RE <br /> Each TLS RF in the site network must have a unique device set number (0,1,2 or 3).The factory default setting is <br /> V.You must select '0'for the master TLS RE The site's Receiver must also be connected to the master TLS RE <br /> If a second TLS RF is required, enter'1' in the auxiliary TLS RE For additional TLS RFs, enter'2' for the third and <br /> '3'for the fourth. <br /> 0 D <br /> 99999999 <br /> �I■ 0 <br /> ■ ❑ 0 <br /> ■ 0 <br /> EZ�O <br /> E ■8 ■ <br /> ® ■3 ■7 <br /> ■2 ■6 <br /> ■1 ■5 I <br /> � • 964-12.eps <br /> Figure 12. TLS RF Diagnostic LEDs And Switch Locations <br /> LEGEND FOR • <br /> 1. These LEDs flash when there is comm activity on RS-232 port 5. These red LEDs flash when a message is received from a Trans- <br /> (Red =TX,Green = RX). mitter in the monitored device set.LED 1 is the device wired to <br /> 2. These LEDs flash when there is comm activity on the RS-485 I.S.output terminal 1.LED 2 is the device wired to output termi- <br /> network(between TLS RF and Receiver). nal 2,etc. <br /> 3. Red LED is lit when TLS RF is powered on. 6. Red LED flashes when TLS console is polling for device data. <br /> 4. Device time out rotary switch selects the maximum allowed 7. S2 DIP switches 1-2 enter device set address(see Appendix B). <br /> time to wait for communication from Transmitter before a <br /> Comm alarm is posted by TLS console(see Appendix B for <br /> selections).Position 1(10 minutes)is the factory default set- <br /> ting. <br /> 10-21 <br /> CARE Approved 101A 10-Veeder Root TLS RF Wireless Systems(K)-Executive order VR-202 <br />