Laserfiche WebLink
Setup and Programming <br /> Startup <br /> Upon completing the installation of the Vapor Recovery Monitoring (VRM) System and powering up the Console, <br /> programming the setup is the next step. <br /> System Status <br /> The Console will arrive at the site with the VRM application already enabled. Upon first powering up the console you may <br /> see a screen that looks like the one in Figure 2a. The system with the screen in Figure 2a has the VRM application as well <br /> as the Fuel Management System (FMS) application enabled. These applications are set by a registration key at the time <br /> of purchase. <br /> The first step before programming the VRM is to check to see if all the modules are powered up and operational. Select <br /> the System box which brings up the System Status page as shown in Figure 2b. <br /> Figure 2a and 2b <br /> [Home]1Status [System]1Status[GUI 0.4.0.8] <br /> System FMS VRM i Module Slot S Version <br /> ACI 1 Operational <br /> RLY 2 Operational <br /> A-1 Ed QA RLY 3 Operational <br /> 420 5 Operational <br /> PR8 7 Operational <br /> Ok Ok Alarm CM CM Operational <br /> 9 02101108 rt <br /> ® 11-19— <br /> 02101108 <br /> Verify all the modules are present and operational. If all the modules are "Operational'then you may proceed to setup and <br /> programming. If not, refer to the Alarm Codes and Troubleshooting section of this manual. <br /> II-12 <br /> CANB Approved IDM 11-INCON Vapor Recovery Monitoring(VRM)-Executive Order VR-202 <br />