N U)/'�
<br /> V I
<br /> SYMBOL LEGEND REFER TO SPEFICATIONS FOR U
<br /> ABBREVIATIONS . , w
<br /> EQUIPMENT SCHEDULE SYMBOL ITEM ABBREV. NON-STANDARD/OTHER ABBREVIATIONS:
<br /> RECTANGULAR DUCT SIZE RTU - ROOF TOP UNIT
<br /> NET INSIDE DIMENSIONS HPFC - HEATPUMP FAN COIL
<br /> MARK MAKE MODEL DESC. CAPACITIES AMB ELECTRICAL ACCESSORIES - - LINED DUCT WITH INSULATION SCHPFC - SELF CONTAINED HEAT PUMP
<br /> 102 ITEM QTY VOLT - - SEE DRAWING FOR THICKNESS FAN COIL
<br /> N CFM HEAT COOLING TOT/SENS PH FLEXIBLE SUPPLY DUCT, CLASS 1 CEF - CEILING EXHAUST FAN
<br /> IN OUT - - - - - FLEXIBLE RETURN DUCT, CLASS 1 REF - ROOF EXHAUST FAN �Ny
<br /> / VD - VOLUME DAMPER, REQUIRED NONE OHP - OUTDOOR HEAT PUMP L.L
<br /> E DAMPER FDR CU
<br /> RTU-1 CARRIER PACKAGE 3400/ 150 92.9 80 FLA 45.3 208V W/ ECONOMIZER FD - FIR - CONDENSING UNIT if
<br /> FSD - FIRE SMOKE DAMPER FSD FC - FAN COIL �l
<br /> 0 8.5 TON 48LCDD09 GAS 2500 120 80.5 65 3PH HIGH STATIC MOTOR, VD
<br /> CSFD - CEIL. FIRE SMOKE DAMPER CSFD SQ - SUARE
<br /> ELECTRIC 0,5" AFUE 82% 13.2 EER/IEER 19.8 MCA 50, MOCP 70 BYPASS CURB WT=2000# MD DM - MOTORIZED DAMPER MD DM FT - FEET RED INC ARCHITECTS
<br /> 1217 J STREET, MODESTO, CA 95354
<br /> PCF - POUNDS PER CUBIC FOOT 209.522.8900
<br /> � RTU-2,3 CARRIER PACKAGE 2000 72 55.9 80 FLA 28.5 208V W/ ECONOMIZER DUCTWORK - GI SPIRAL PIPE GA - GAGE, GAUGE
<br /> z 5 TON 48LCDA06 GAS 0.5 56 49.0 65 3PH HIGH STATIC MOTOREE
<br /> o ELECTRIC AFUE 82% 15 SEER/12.3 EER MCA 33, MOCP 45 ROOF CURB WT-750# TURNING VANES Tv
<br /> SEAL:
<br /> U
<br /> 300 FIRST LETTER CEILING
<br /> UCS-4 LOCATION: FLOOR
<br /> HPFC-1 FIRSTCO CEILING 1200 36.0 34.6 85 FLA 15.2, 208 1 PH WT=65# 12x12 WALLrSUPPLY �S\ONAL
<br /> _JF�
<br /> 36HXX**(3) MOUNTED 0.2 65 MCA 19, MOCP 20 ® CS-4 SECOND LETTER
<br /> 0 3 TON FAN COIL HTR 3KW SERVICE: [RETURN �� �C' G c
<br /> i OHP-1 CARRIER OUTDOOR NA 33.8 34.6 85 17.2 FLA, 208V CRANK CASE HEATER 01NUMBER-TYPE: EXHAUST
<br /> 25HNA636 HEAT PUMP 18.0 20.0 65 1PH MCA 21.3, WT=310# SEE SCHED. 6-
<br /> Z CR-1 300 - CFM, CUBIC FEET PER MINUTE
<br /> 3.7 COP 15 SEER MOCP 30 - * ' iuo. M29756 ...
<br /> 12x12 - GRILLE NECK SIZE IN INCHES REN. 6-30-20 Q
<br /> HPFC-2 CARRIER FOUR 1600 39.4 39.7 80 FLA 6.0 208 1 PH MB-1 MICRMETL PROVIDE VD'S AT ALL WYES AND TAPS ,yam P
<br /> UJ FE4ANF005 POSITION 0.5 - 44.3 65 HTR 28.9, 44.7 MB-GP20CA-D2ZH MIXING SUPPLYING GRILLES AND REGISTERS FOR �cHAN\G O�
<br /> FAN COIL MCA, 50 MOCP CE-1 AIR BALANCING PER T-24. F
<br /> o BOX, WT=165# OF CN
<br /> W OHP-2 CARRIER AIR COOLED NA - 80 FLA 15.2 208V 3PH CRANK CASE HTR OT THERMOSTAT, UNIT NO. -
<br /> 38QRR348 HEAT PUMP 44.3 65 MCA 18.6, FUSE 30 WT=240# © ❑N © BYPASS, NITESTAT, CLOCK -
<br /> ABBREVIATIONS W/OR WO SYMBOLS
<br /> HPFC-3 FIRSTCO CEILING 800 24.0 24.2 85 FLA 15.2, 208 1PH WT=65#
<br /> C14 24HXX**(3) MOUNTED 0.2" 65 MCA 19, MOCP 20 - WITH W/
<br /> CONSULTANT:
<br /> 0 2 TON - WITH OUT WO/ El
<br /> OHP-3 CARRIER OUTDOOR NA 24.0 24.0 85 12.8 FLA, 208V CRANK CASE HEATER ❑ ❑
<br /> Z 25HNA024 HEAT PUMP 13.4 14.4 65 1PH MCA 15.9, WT=285# - DOWN DN U O
<br /> 8.5 HSPF 15 SEER MOCP 25
<br /> N - GALVANIZED SHEET METAL GI Z
<br /> HPFC-4 FIRSTCO CEILING 1200 36.0 34.6 85 FLA 15.2, 208 1PH WT=65# ❑ ❑❑ � u n8n
<br /> UJ 36HXX**(3) MOUNTED 0.2" 65 MCA 19, MOCP 20 - ABOVE FINISHED FLOOR AFF Z W ] N ❑ �❑ n
<br /> N 3 TON FAN COIL HTR 3KW
<br /> N - 8 o0 00 BELOW FINISHED FLOOR BFF � � � CV � �
<br /> = OHP-4 CARRIER OUTDOOR NA 33.8 34.6 85 17.2 FLA, 208V CRANK CASE HEATER 7 WT- W � Cn � ❑❑ ❑
<br /> 310# - BELOW FINISHED CEILING BFC 00 LU o ZC14 _ C/) 7 n El
<br /> 25HNA636 HEAT PUMP 18.0 20.0 65 1PH MCA 21.3, -
<br /> 3.7 COP 15 SEER MOCP 30 - ABOVE FINSHED CEILING AFC 00 (� CL o o Elb
<br /> HPFC-5 FIRSTCO CEILING 800 24.0 24.2 85 FLA 15.2, 208 1PH WT=65# - - 0 Z 8 04 o �❑
<br /> 24HXX**(3) MOUNTED 0.2" 65 MCA 19, MOCP 20 NEW DUCTWORK LU J ❑ ❑
<br /> 2 TON FAN COIL HTR 3KW -X-X �� DEMOLITION TO BE REMOVED TBR � T_ a LI OHP-5 CARRIER OUTDOOR NA 24.0 24.0 85 12.8 FLA, 208V CRANK CASE HEATER ❑❑ N
<br /> 25HNA024 HEAT PUMP 13.4 14.4 65 1PH MCA 15.9, WT=285# DUCTWORK EXISTING (E) U E: El
<br /> 8.5 HSPF 15 SEER MOCP 25 Z POINT OF CONNECTION POC H
<br /> HP-1 FUJITSU OUTDOOR - - 100 FLA 20.3 208V 1PH WT=150# W t9 CUT OFF POINT COP
<br /> AOU36RLX HEAT PUMP 36.4 35.2 24.6 MCA, 30
<br /> 9.4 HSPF 18 SEER MOCP - FURNISHED BY OTHERS FBO
<br /> FC-1 A,1 B, FUJITSU CEILING 350 - 12.0 80 FLA 0.23A 208V W/CONDENSATE PUMP, - UP THROUGH ROOF UTR
<br /> 1C AUU18RLF MTD FAN 16.6 9.8 65 1PH POWER FROM HP-1
<br /> COIL - - WT=45# - UNLESS OTHERWISE NOTED UON
<br /> HP-2 FUJITSU OUTDOOR - - 100 FLA 20.3 208V 1PH WT=150# C CONDENSATE, OVERFLOW C, OF
<br /> AOU36RLX HEAT PUMP 36.0 36.0 24.6 MCA, 30.0
<br /> 10 HSPF 18 SEER MOCP HWS HEATING WATER SUPPLY, RETURN HWS,HWR
<br /> FC-2A,2B FUJITSU WALL MTD 540 - 18.0 80 FLA 0.23A 208V W/ CONDENSATE PUMP, CHWS CHILLED WATER SUPPLY, RETURN CHWS,CHWR
<br /> ASU18RLF FAN COIL 18.0 14.7 65 1PH WALL PLATE, POWER FROM - MACHINE BOLT MB
<br /> - - HP-2 WT=45#
<br /> SCHPFC-1 FRIEDERICH SELF 465 16.8 18.0 85 FLA 8.3 208V 1PH 2.55KW HEATER G,LPG NATURAL GAS, LPG LINE G, LPG
<br /> VHA18K25RTN CONTAINED - 3.0 COP 14.8 65 MCA 15.0 MOCP 15 WT=174# - ALL THREAD ROD ATR by HILTON"
<br /> HEAT PUMP 10 EER - OUTSIDE AIR OSA
<br /> PTAC-1 1FRIEDRICH ROOM PTAC 330 6.3 6.3 80 FLA 3.8 208 1 PH W/3KW ELECTRIC HEAT,
<br /> PZH07 - - 5.1 65 HTR 12.2 MCA 16.8 WALL SLEEVE, OAL-1 - FEET PER MINUTE FPM
<br /> 3.5 COP 12 EER MOCP 20 LOUVER WT-135#
<br /> � DUCT TEMPERATURE SENSOR DTS Q
<br /> PTAC-2 FRIEDRICH ROOM PTAC 1 400 8.2 9.4 80 FLA 3.8 208 1 PH W/3KW ELECTRIC HEAT, Z
<br /> FLEXIBLE DUCT CONNECTOR FC
<br /> PZH09 - - 7.7 65 HTR 12.2 MCA 16.8 WALL SLEEVE, OAL-1 -
<br /> 3.5 COP 11.8 EER MOCP 20 LOUVER WT=135# - FLEX DUCT - �_
<br /> J
<br /> STEAM PIPE S Q
<br /> U
<br /> STEAM CONDENSATE SC
<br /> MAKEUP WATER CW
<br /> DIFFUSER/REGISTER SCHEDULE DQ SHUT OFF/BALL VALVE BV
<br /> MARK MAKE DESCRIPTIO FACE BLOW DAMPER COLOR REMARKS - DUCT SMOKE DETECTOR DSD
<br /> MODEL N MOUNT OPERATING WT
<br /> CS-4 TITUS CEILING BLADE 4-WAY WYE WHITE INSTALL VD IN WYE
<br /> TDC-3-A4 SUPPLY T-BAR BRANCH BRANCH/BRANCH DUCT HVAC Notes
<br /> CS-4A TITUS CEILING BLADE 4-WAY WYE WHITE INSTALL VD IN WYE 1. Furnish and install all ductwork in accordance with the latest editions of CMC (SMACNA duct W
<br /> TDC-6-A4 SUPPLY SURFACE BRANCH BRANCH/BRANCH DUCT construction standards).
<br /> 2. All pipes, ductwork and conduit shall be installed and seismically braced per SMACNA's Seismic Restraint 0 >
<br /> + CR-1 TITUS 350R CEILING BLADE NA WYE WHITE INSTALL VD IN WYE Guidelines, OSHPD pre-approval #R0010,
<br /> RETURN T-BAR BRANCH BRANCH/BRANCH DUCT 3. All contractor furnished equipment installation and startup instructions shall be kept with the piece of
<br /> C_ )K CR-2 TITUS 350R CEILING BLADE NA WYE WHITE INSTALL VD IN WYE equipment in weatherproof pouches until final inspection, After final inspection, three sets of operation, W
<br /> RETURN SURFACE BRANCH BRANCH/BRANCH DUCT installation, maintenance and start-up instructions shall be given to the Owner for each piece of equipment
<br /> per the Ca Green Building Code. All equipment shall be installed, isolated and supported per the manufacturer's N
<br /> )K CE-2 TITUS 350R CEILING BLADE NA WYE WHITE INSTALL VD IN WYE written instructions,
<br /> EXHAUST SURFACE BRANCH BRANCH/BRANCH DUCT 4. All Fire and Fire Smoke Damper installation instructions shall be made available to the inspecting authority for O
<br /> o )K WS-1 TITUS 30ORS WALL BLADE 4-WAY WYE WHITE INSTALL VD IN WYE their review,
<br /> 0' 5. All penetrations through fire rated assemblies shall be fire stopped and sealed with a material that meets or
<br /> 0 SUPPLY SURFACE BRANCH BRANCH/BRANCH DUCT exceeds the `T' rating of the assembly penetrated. Materials to be used for sealing shall be coordinated with
<br /> o )K WR-1 TITUS 350R WALL BLADE NA WYE WHITE INSTALL VD IN WYE the General Contractor to provide one brand onsite, •
<br /> o RETURN SURFACE BRANCH BRANCH/BRANCH DUCT 6. Install all pipe and duct insulation materials per T-24 requirements. All material to be installed shall meet CBC W
<br /> `" )K DS-1 TITUS 30ORS DUCT BLADE 4-WAY WYE WHITE INSTALL VD IN WYE flame and smoke requirements per note 11,
<br /> E SUPPLY SURFACE BRANCH BRANCH/BRANCH DUCT 7. All work on this project shall conform to the following codesi
<br /> Q- )K DE-1 TITUS 350R DUCT BLADE NA WYE WHITE INSTALL VD IN WYE
<br /> 2016 CBC
<br /> EXHAUST SURFACE BRANCH BRANCH/BRANCH DUCT 2016 CPC O
<br /> LS-1 TITUS FL CEILING SURFACE 2-WAY WYE SAS INSTALL VD IN WYE 2016 CMC
<br /> o SERIES (2)1" SUPPLY BORDER BRANCH BRANCH/BRANCH DUCT 2016 CAC 0
<br /> SLOTS SEE 2016 CALIFORNIA GREEN BUILDING CODE. Z
<br /> DETAILS
<br /> OAL-1 GREENHECK JOUTSIDE BLADE NA MOTORIZ WHITE PAINT PER ARCHITECT, MD-1 8. All wye branches connected to a diffuser, grille or register shall have a manual volume damper installed in the Q
<br /> wye branch, OBD's shall only be used when wye branches will be installed over inaccessible ceiling areas or in
<br /> o ESD 403 WITH AIR LOUVER SURFACE ED 120V 1PH, SPRING RETURN the slab of the building, Dampers shall be fabricated of the same gauge as the duct with 1" standoff, locking
<br /> 0 FRAME CLOSE quadrant, and handle, Fasten red ribbon to handle to mark location. Z
<br /> o CONTRACTOR SHALL CONFIRM ALL REFLECTED CEILING GRID SYSTEMS WITH THE BORDER SPECIFIED 9. All gas pipe to be schedule 40 with screwed fittings, All air conditioning/refrigeration condensate drain lines O
<br /> 0 IN THE SCHEDULE FOR LAYIN DIFFUSERS AND SHALL SUBMIT DIFFUSER BORDERS MATCHING GRID shall be schedule 40 PVC run to the an approved receptor, Set pipe on redwood blocks with 24 ga GI cover U
<br /> SYSTEMS, unless otherwise shown differently on drawings, Z
<br /> =3 )K RUN ALL FRONT FACE REGISTER BLADES PARALLEL TO FLOOR WHEN MOUNTED IN WALLS 10. Provide smoke detectors in the supply air duct on all units when the aggregate cfm exceeds 2000 cfm of all
<br /> o SAS SAS - SEE ARCHITECTURAL SCHEDULE FOR FLOOR, CEILING AND WALL FINISHES, CONFIRM REGISTER equipment serving a room or more than one room and the room has no direct exits to the exterior. Duct (n
<br /> FINISH (MILL OR PAINT) WITH ARCHITECT PRI❑R TO ORDERING SLOTS, smoke detectors shall be installed after the supply fan before any branch takeoffs, When more than one Z Q
<br /> + NO SCREW HOLES unit serves a TI space and the aggregate cfm of the units serving the TI space exceeds 2000 cfm, all HVAC J
<br /> -� equipment shall have duct smoke detectors, All duct smoke detectors shall be wired to shut down all units
<br /> when a single unit alarms, When fire detection or alarm systems are provided for the building, all smoke
<br /> detectors including those installed for fire smoke dampers shall be supervised by such systems per 608.1 CMC.
<br /> EXHAUST FAN SCHEDULE Such connections shall be shown on the deferred fire alarm submittal. REVISIONS:
<br /> 11. Such connections shall be shown on deferred fire alarm submittal,
<br /> O MARK MAKE DESC. CAPACITIES ELECTRICAL ACCESSORIES AND OPERATING WT# 12. All exposed ductwork shall be GI pipe and fittings, Line all rectangular duct with insulation with the R-value Q2 HILTON 10/18/2018
<br /> MODEL CFM "ESP RPM SONNES ITEM QTY VOLT PH CONTROLS listed in T-24 for the location of the duct (attic, conditioned or outside). All duct materials from insulation
<br /> to mastics including but not limited to sheet metal, insulation, liners, plastics, rubber cements, latex, etc. shall
<br /> E CEF-1 BROAN L100 CEILING 60 0.25 640 1.3 100 WATT 120 10 BDD, BS, SPEED 25# be made of materials with a Flame spread <=25 and smoke <=50.
<br /> CY' EXHAUST FAN CONTROLLER AND 12. It is the responsibility of the Mechanical Contractor to coordinate the installation of his work including
<br /> DISCONNECT equipment substitutions with the other trades including but no limited to electrical, fire sprinkler, framing and
<br /> plumbing,
<br /> CEF-2 BROAN L100 CEILING 100 0.5 850 5.4 100 WATT 120 10 BDD, BS, SPEED 25# 13. Insulate all ductwork per the T-24 energy requirements found in the T-24 compliance report, All ductwork
<br /> EXHAUST FAN CONTROLLER AND shall be tested for leaks with a maximum static pressure in the duct of 1,0", maximum leakage shall not exceed
<br /> DISCONNECT 4% of the total supply and return air volumes,
<br /> IEF-1 GREENHECK INLINE 400 0.5 1550 7.6 0.25 HP 120V 10 BDD, BS, WALL 45# 14. All economizer, thermostat and fan systems shall be tested per T-24 for compliance with the T-24 report and
<br /> U„ SQ-95-VG- EXHAUST FAN MOUNTED SPEED LOW LEAK DAMPER the appropriate forms indicated in the T-24 report shall be provided and signed by the Contractor prior to
<br /> 1/4 CONTROLLER AND <2 CFM/SQ FT project close out and the HERS reports loaded up to the appropriate CHEERS or CAL-Certs hosting service.
<br /> E DISCONNECT 15. Contractor shall label all equipment with unique identification using plastic engraved plates with 1/2" tall
<br /> REF-1 GREENHECK ROOF 200 0.5 1435 7.6 0.25 HP 120V 10 BDD, BS, WALL 75# lettering indicating the equipment number and state the areas served by the equipment, See specifications on
<br /> G-097-VG- EXHAUST FAN MOUNTED SPEED LOW LEAK DAMPER dwgs.
<br /> v 1/4 CONTROLLER AND <2 CFM/SQ FT 16. All flex duct will be stretched as tight as possible and as per manufacturers listing to avoid all kinks and RED PROJECT # 18050
<br /> DISCONNECT sagging, HILTON 18-428ND
<br /> 0 17. All smoke detectors shall be tested as required with an approved smoke system per the City of Lathrop's #
<br /> wd REF-2 GREENHECK ROOF 200 0.5 1435 7.6 0.25 HP 120V 10 BDD, BS, WALL 75# standards in the presence of the inspector or fire Marshall. PLANNING # SPR-18-102
<br /> G-097-VG- EXHAUST FAN MOUNTED SPEED LOW LEAK DAMPER 18. All systems shall require an air balance report upon final inspection, Submit reports on NEBS or NABC forms
<br /> 0 1/4 CONTROLLER AND <2 CFM/SQ FT an independent certified air balance showing system has been balanced and OSA quantities set to that shown PERMIT # -
<br /> DISCONNECT on drawings,
<br /> a BDD - BACK DRAFT DAMPER, LOW LEAK 19. Condensate drain lines installed in direct or indirect sunlight shall be UV resistant CPVC or PVC pipe and shall APN # 196-270-23
<br /> o BS - BIRD SCREEN be painted to protect from UV radiation. DATE: 11.12.18
<br /> Q 20. Seal all joints and seams with DP-1010 duct sealer,
<br /> DRAWN: NR
<br /> T-24 MECH AND PLUMBING MANDATORY FEATURES CHECKED: GD
<br /> 21
<br /> 1 1. EQUIPMENT SHALL BE CERTIFIED TO MINIMUM EFFICIENCY PER SECTI❑N 110.2 - SEE SCHEDULES ON M-0.
<br /> c 2. HVAC CONTROLS AND EQUIPMENT CERTIFIED PER SECTION 1202 FOR THERMOSTATS AND DDC CONTROLS - SEE DETAILS ON
<br /> M0.
<br /> 3. SERVICE WATER HEATING SHALL COMPLY WITH SECTI❑N 1103 SHEET TITLE:
<br /> 4. USE OF PILOT LIGHTS ON HVAC, GAS COOKING POOL AND SPA HEATERS PROHIBITED PER SECTI❑N 110,5 MECHANICAL SCHEDULES
<br /> 5. LAVAT❑RIES SHALL BE SET TO MAINTAIN DISCHARGE TEMP AT 110°F OR LESS PER SECTI❑N 110,3 - SEE PLUMBING ,
<br /> SCHEDULE DETAILS, AND NOTES
<br /> v� 6. VENTILATION REQUIREMENTS PER 120.1,b,c&d M-1 AIR BALANCE
<br /> L
<br /> 7. NATURAL VENTILATION PER 120.1,1o,1 N/A
<br /> 8. CONTROLS SHALL MEET REQUIREMENTS PER 122, SEE M-0 AND NOTES.
<br /> 0 9. SHUT DOWN AND BACKDRAFT DAMPERS PER 122,E See schedules on M-0
<br /> 10. ISOLATI❑N AREA DEVICES PER 122,g N/A
<br /> O 11. PIPE INSULATI❑N PER 120,3,8 SEE NOTES, TABLE 120,3-A
<br /> 12. REQUIREMENTS FOR DUCTS AND PLENUMS PER 124 SEE M-0, NOTES AND SPECIFICATIONS
<br /> 0 13. MECHANICAL ACCEPTANCE TEST FORMS SUBMITTED AT END OF PROJECT PER SECTI❑N 120,5, 120.7 AND 120.8 - SEE T24
<br /> Q DRAWINGS FOR FORMS REQUIRED (1-17) TO BE SUBMITTED AT THE END OF THE PROJECT FOR EACH HVAC AND PLUMBING
<br /> SYSTEM, AND FOR EACH HVAC AND PLUMBING PIECE OF EQUIPMENT,
<br /> SHEET NO.:
<br /> MO
<br />
|