Item 208: On your inspection report you noted that the designated operator failed to document all alarms <br />from the attached alarm history from 03/03/2021. You requested that all alarms be reported and checked <br />to confirm correct response. <br />Resolution 208: 7-Eleven’s process is for all fuel sensing (liquid) alarms to be dispatched <br />immediately to the assigned Service Provider. In reviewing the s13 no vacuum alarm with our <br />Alarm Management Team, known as Insight360 (a subgroup within Gilbarco Veeder Root), they <br />noted the alarm triggered and then appeared to have self-cleared within 1 minute. It was due to <br />the apparent resetting and the monitoring system returning to an “All Functions Normal” status, <br />that this alarm did not get dispatched. It was later determined during the 04/27/2021 witnessed <br />monitoring certification that this sensor needed to be, and was, replaced. Due to this incident, <br />Insight360 is currently reviewing this internally and discussing with their teams. As for why the <br />monitoring system returned to an All Functions Normal status versus some other trouble code, 7- <br />Eleven has reported this to Veeder Root for their internal review as well. <br />Item 210: On your inspection report you noted that the Mann Singh was not designated operator trained <br />and was the only employee onsite. You requested that all facility employees be trained by the designated <br />operator. <br />Resolution 210: The designated operator trained Mann Singh on 05/07/2021. The training roster has <br />been attached for your reference. <br />Item 307: On your inspection report you noted that there was water found in STP sumps for all products. <br />You requested that all sumps be sealed against water intrusion by a licensed contractor. <br />Resolution 307: The sump gaskets were inspected by Walton engineering on 05/22/21. Work order and <br />photos attached for your reference. <br />Item 302: On your inspection report you noted that the 91 s12 and s14 smart sensors failed when tested. <br />You requested that both sensors be replaced by a licensed contractor and retested. <br />Resolution 302: On 05/05/2021 Walton Engineering replaced both sensors and Tanknology will retest <br />on 05/28/2021, the test report will be sent once the test is completed. See attached work order. <br />This letter should address the item(s) noted on the Inspection Report. 7-Eleven assumes that all issues <br />regarding this report have been resolved and are closed at this time. The submittal of this response by 7- <br />Eleven, Inc. shall not constitute, nor be deemed to constitute, an admission of liability or responsibility <br />with respect to the alleged violations and may not be used in any administrative or judicial proceeding or <br />otherwise. <br />Very truly yours, <br />7-Eleven, Inc. <br />Ethan Valburg <br />Regional Gasoline Environmental Compliance Specialist <br />Enclosures: Tanknology letter, training roster, work orders, <br />cc: File <br />7-Eleven, Inc. <br />P.O. Box 711 – Dallas, Texas 75221-0711